Screen 6.
Alarms:
Current inverter alarm status.
0000H,
Everything is operating correctly.
0001H,
Grid frequency is out of range
0002H,
Grid voltage is out of range
0004H,
Current PI saturation (internal alarm)
0008H,
Unexpected reset (internal alarm)
0010H,
Continuous over-current at the output (Internal alarm)
0020H,
Temperature, power electronics
0040H,
AD converter reading (inverter internal alarm)
0080H,
Instantaneous overcurrent at the output (Internal alarm)
0100H,
AC circuit protections
0200H,
DC circuit protections
0400H,
DC circuit insulation failure
0800H,
Failure in power electronic
1000H,
Alarm due to a manual stop
2000H,
Alarm caused by a configuration change
4000H,
Overvoltage at the input from the panels
8000H,
Voltage very low at the input from the panels
Alarmas Hist: From the«Alarma Inv» menu, pressing provides access
to the submenu «Hist.Alarm», which shows the history of all alarms
that have been activated since the inverter was last connected to the
grid.
TempInt:
Inverter Power Electronics Temperature
.
TempCI:
Inverter Control Electronics Temperature
.
Screen 7.
N.Conex
:
The number of connections to the Grid made throughout all
the
operating hours.
N.ConexPar
: The number of connections to the Grid made since last RE-
SET.
T.Conex:
The number of hours that the inverter has been active since
last
RESET.
T.ConexPar:
The number of connections to the Grid made since last RESET.
Installation and Operation Manual
INGECON
®
SUN SMART U
AAS2000IKI05
AAS2000IKI05
Rev. _
Date: February 2011
Page 63