Notes:
1. Utility Interconnection Voltage and Frequency Trip Limits and Trip
Times:
Condition
Simulated utility source
Maximum time (sec) at 60 Hz
before cessation of current to the
simulated utility
Voltage (V)
Frequency (Hz)
A
< 0.50 Vnor
Rated
0.16
B
0.50 Vnor ≤ V < 0.88 Vnor
(Adjustable Set Points)
Rated
0.16 to 2.667 (Adjustable Set
Points)
C
1.10 Vnor < V < 1.11 Vnor
(Adjustable Set Points)
Rated
0.16 to 2 (Adjustable Set Points)
D
1.20 Vnor ≤ V
Rated
0.16
E
Rated
f > 60.5
0.16
F
Rated
f < (59.8 – 57.0)
(Adjustable Set
Points)
0.16 to 300
G
Rated
f < 57
0.16
2. Utility interactive evaluations were conducted with the following
firmware:
15 kW.
DSP Firmware versions (208V):
AAS1038
Check sums:
0x1DF3
MICRO Firmware versions (208V): NA
Check sums: NA
DSP Firmware versions (480V):
AAS1037
Check sums:
0xB734
MICRO Firmware versions (480V): NA
Check sums: NA
25 kW.
DSP Firmware versions (208V):
AAS1036
Check sums:
0x59OA
MICRO Firmware versions (208V): NA
Check sums: NA
DSP Firmware versions (480V):
AAS1035
Check sums: 0x2981
MICRO Firmware versions (480V): NA
Check sums: NA
3. Surge Testing for Combination Wave (1.2/50us) was done at 6
kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100kHz)
was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were
performed using both polarities, for common mode and differential mode
coupling, 20 pulses each test. After surge testing the unit was operational
with control functionally verified by frequency and voltage disconnect
tests.