Table 60.
Test mode states for Voyager
™
™
Commercial SZVAV units with modulating dehumidification and
modulating heat
Test
Step
Mode
Fan
VFD
Command
Econ.
Comp 1 Comp 2 Comp 3
Heat
Output
Pumpout
Cool
Valve
Reheat
Valve
1
FAN ON
ON
45% (0
VDC)
MIN
OFF
OFF
OFF
OFF
OFF
100%
0%
2
ECONO-
MIZER
ON
45% (0
VDC)
OPEN
OFF
OFF
OFF
OFF
OFF
100%
0%
3
COOL 1
ON
80% (6.67
VDC)
MIN
ON
OFF
OFF
OFF
IN-
CONTROL
100%
0%
4
COOL 2
ON
IN-
CONTROL
MIN
ON
ON
OFF
OFF
IN-
CONTROL
100%
0%
5
COOL 3
ON
IN-
CONTROL
MIN
ON
ON
ON
OFF
IN-
CONTROL
100%
0%
6
REHEAT
ON
73% (5.24
VDC)
MIN
ON
ON
ON
OFF
IN-
CONTROL
50%
50%
7
HEAT 1
ON
100% (10
VDC)
MIN
OFF
OFF
OFF
50%
OFF
100%
0%
8
HEAT 2
ON
100% (10
VDC)
MIN
OFF
OFF
OFF
100%
OFF
100%
0%
9
RESET
Notes:
1
.
2 & 3 stage standard efficiency units: For Traditional VAV units, the VFD Command when “In-Control” will be controlled based on
supply air pressure requirements. For SZVAV units, the VFD command will be at discrete points during Test Mode.
2
.
2 & 3 stage standard efficiency units: For 27.5 to 35 ton units, both compressors will be energized during the Cool 2 Step. For 40-50T
units, only Compressor 2 will be energized during the Cool 2 Step.
3
.
2 & 3 stage standard efficiency units: The reheat pumpout relay will be energized any time the reheat circuit is energized in active
Cooling Mode.
4
.
2 & 3 stage standard efficiency units: For units with Statitrac™ installed, the exhaust damper will track the Economizer position
during Service Test Mode and the Exhaust Fan will be energized once the economizer rises above the exhaust enable setpoint.
5
.
5 stage high efficiency units: Compressor 1 is the smaller compressor on the circuit.
6
.
5 stage high efficiency units: Condenser fans are controlled as defined for normal operation.
7
.
5 stage high efficiency units: Exhaust fan operates as defined for normal operation based on economizer position.
8
.
5 stage high efficiency units: When compressor 1 is energized with either C1, C2, or with both for 30 minutes continuously, C3 will be
required to de-energize for 30 seconds.
Table 61.
Sequence of operation reference
Product Family
Publication Number
Short Description
Odyssey
™
SSA-SVX06*-EN
Split System Air Handlers 5 to 25 Tons
Odyssey
™
SS-SVX10*-EN
Split System Cooling Condensers 6 to 25 Tons
Odyssey
™
SSP-SVX14*-EN
Split System Heat Pump Condensers, R-410A 6 to 20 Tons
Odyssey
™
SSP-SVX15*-EN
Split System Heat Pump Condensers R-22 Dry Charge 7.5 and 10 Tons, 60
Hz
Odyssey
™
SS-SVX12*-EN
Split System Cooling Condensers R-22 Dry Charge 7.5 and 10 Tons, 60 Hz
Precedent
™
Refer to Product Service
Facts
Voyager
™
Light Commercial
Refer to Product Service
Facts
Voyager
™
Commercial
RT-SVX34*-EN
Voyager
™
Commercial - 27.5 to 50 Tons, 60 Hz
Units with Two Heat Exchangers (High Heat
Models)
Heat Stage one - The two stage burner runs high heat
for 60 seconds, then drops to low heat. Modulating gas
heat stays off.
Heat Stage two - The two stage burner stays on low.
Modulating burner comes on and stays at 100%.