88
RT-SVD03L-EN
Table 52.
Test modes for Voyager
™
™
Commercial VAV units with IGV/VFD
Test
Step
Mode
IGV/
VFD
Fan
Econ
EXH
Fan
Power
Exhaust
Damper
Comp
1
Comp
2
HT 1 HT 2
Mod.
Heat
Cool
Valve
Re-
heat
Valve
Reheat
Pump
Out
VHR
Relay
OHMS
1
IGV/VFD
Test
Open/
100%
Off
Closed
Off
Min
Off
Off
Off
Off
0%
100%
0%
Off
On
2.2k
2
IGV/VFD
Test
Closed/
0%
OFF
Closed
Off
Min
Off
Off
Off
Off
0%
100%
0%
Off
On
3.3k
3
Minimum
Ventilation
In
Control
On
Min
Off
Min
Off
Off
Off
Off
0%
100%
0%
Off
On
4.7k
4
Econo-
mizer
In
Control
On
100%
On
100%
Off
Off
Off
Off
0%
100%
0%
Off
On
6.8k
5
Cool Stage
1
In
Control
On
Min
Off
Min
On
Off
Off
Off
0%
100%
0%
On/Off
(a)
On
10k
6
Cool Stage
2
In
Control
On
Min
Off
Min
Off
(b)
On
(b)
(c)
Off
Off
0%
100%
0%
On
On
15k
7
Cool Stage
3
In
Control
On
Min
Off
Min
On
(c)
Off
Off
0%
100%
0%
On
On
22k
8
Reheat
In
Control
On
(d)
Min
Off
Min
On
Off
Off
0%
50%
50%
Off
On
27k
9
Heat
Stage 1
Open/
100%
(e)
On
Min
Off
Min
Off
Off
Off
50%
100%
0%
Off
On
33k
10
Heat
Stage 2
Open/
100%
On
Min
Off
Min
Off
Off
On
100% 100%
0%
Off
On
47k
11
Reset
Notes:
1
.
The IGV/VFD will be controlled to the supply pressure setpoint unless test mode has been running for six minutes or longer. After six minutes, the
IGV damper will be allowed to drive to 100% for step nine and ten.
2
.
The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. It will not turn off until the
economizer damper position is at the exhaust enable setpoint - 10% or lower.
3
.
The VHR relay output will be energized at the start of the test mode to allow time for the VAV boxes to open. It takes six minutes for the boxes to
drive from the full closed position to the full open position. The timing cannot be changed in the field.
4
.
Economizer, Power Exhaust Damper, HT1, HT2, Mod. Heat, Cool Valve, Reheat Valve, and Reheat Pump Out = with optional feature
(a)
27½ to 35 (On), 30 to 50 (Off)
(b)
27½ to 35 ton units have two stages of mechanical cooling. Both compressors run during cool stage two.
(c)
The condenser fan will operate any time a compressor is ON providing the outdoor temperatures are within normal operating range.
(d)
The supply fan will not be allowed to go from an off state to an on state until the IGV are fully closed.
(e)
The heat outputs will not be allowed to come on until the unit has been in test mode for at least six minutes and the IGV/VFD is at 100%.
Table 53.
CV Test modes (also VAV w/o IGV) 27.5 to 50 tons without reheat
Test
Step
Mode
SF
Econ. Exh Fan
Power Exh
Damper
Comp 1 Comp 2 Heat 1
Heat 2
Mod
Heat
Ohms
1
Minimum
Ventilation
On
Min
Off
Min
Off
Off
Off
Off
0%
4.7k
2
Economizer
Test Open
On
100%
On
100%
Off
Off
Off
Off
0%
6.8k
3
Cool Stage 1
On
Min
Off
Min
On
(a)
Off
Off
Off
0%
10k
4
Cool Stage 2
On
Min
Off
Min
Off
(b)
On
(a)(b)
Off
Off
0%
15k
5
Cool Stage 3
On
Min
Off
Min
On
On
Off
Off
0%
22k
6
Heat Stage 1
On
Min
Off
Min
Off
Off
On
Off
50%
33k
7
Heat Stage 2
On
Min
Off
Min
Off
Off
On
On
100%
47k
8
Reset
Notes:
1
.
Steps for optional accessories and modes not present in unit will be skipped.
2
.
Economizer, Power Exhaust Damper, Heat 1 & 2, and Modulating Heat = with optional feature.
3
.
The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. It will
not turn off until the economizer damper position is at exhaust enable setpoint - 10% or lower.
(a)
The condenser fans will operate any time a compressor is ON providing the outdoor air temperatures are within normal operating range.
(b)
27.5 to 35 ton units have two stages of mechanical cooling. Both compressors run during cool stage two.