If the temp is below 35º F for 10 more continuous
minutes all compressors will stage off and the ID
fan will continue to run.
•
Once reaching 45º F the compressor (circuit) will be
re-enabled.
•
The condenser fans will be staged differently in
reheat mode than cooling mode.
•
Single circuit units (3 total condenser fans): A
maximum of 2 outdoor fans above 85ºF and a
maximum of 1 outdoor fan below 80ºF.
•
Dual circuit units (4 total condenser fans): A
maximum of 4 outdoor fans above 85ºF and a
maximum of 2 outdoor fans below 80ºF.
•
Service mode operation
•
Reheat step will follow the last cooling step in
service test mode.
•
All compressors energized.
•
Reheat/cooling modulating valve positions are 50%.
•
Pump out solenoid de-energized.
•
60 minute service test interval timer will be in
control.
Figure 95.
Voyager
™
™
Commercial modulating hot
gas reheat
S
S
C
O
M
P
R
E
S
S
O
R
Time Delayed
LPC
Modulating
Valves
C
O
N
D
+
S
B
C
L
R
E
H
E
A
T
E
V
A
P
O
R
A
T
O
R
0.1” Bleed
Line
TXV bulb
RH
Check
Valve
•
RTRM handles the main dehumidification logic.
•
RTOM contains the humidity and supply air set
point.
•
RTDM (new module) handles the reheat/cooling
valve and pump out relay control.
•
Customer adjustable set points
•
Supply air reheat set point located on RTOM (65-
80ºF default 70ºF)
•
Dehumidification (humidity) set point located on
RTOM (40-65% default 50%)
•
VAV dehumidification override zone cooling and
heating setpoints (75ºF cooling, 68ºF heating). A
customer can adjust them if a CV remote zone
sensor is connected to the RTRM or by using
resistors.
Figure 96.
Modulating hot gas reheat control
boards
SETPOINT LEGEND
1.Discharge Air Heat SP
- 50-150°
F
2.Exhaust Fan Enable SP
- 0 to 100%
3.Supply Air Reheat SP
- 65-80°
F
4.Dehumidification SP (%)
- 40 to 65% RH
J1-1
J3-1
J5-1
R50
J8-1
J6-1
J4-1
J2-1