RT-SVD03L-EN
159
If the HPC opens and closes four times during an active
call for cooling, the unit will be shut down and locked
out, and will require a manual reset.
If any time during the counter routine, the call for
cooling goes away, the counter will reset and the logic
sequence starts all over again.