RT-SVD03L-EN
85
Table 44.
Voyager
™
™
& Precedent
™
™
heat pump units 3 to 20 tons
Step
Mode
IDM
Econ
CPR1
CPR2
HT1
HT2
SOV1
ODM1
ODM2
1
Fan On
On/Low
(a)
Min
Off
Off
Off
Off
Off
Off
Off
2
Econ.
Open
Off
Off
Off
Off
Off
Off
Off
3
Cool 1
On/Low
Min
On
On
(b)
Off
Off
On
On
(c)
4
Cool 2
On/Low
Min
On
On
(d)
Off
Off
On
On
5
Cool 3
On/High
Min
On
On
Off
Off
On
On
6
Reheat
On/High
Min
On
On
(e)
Off
Off
Off
On
On
7
Heat 1
On/High
Min
On
On
On
(f)
Off
Off
On
On
8
Heat 2
On/High
Min
On
On
On
On
(g)
Off
On
On
9
Heat 4
On/High
Min
On
On
On
On
Off
On
On
10
(h)
Defrost
On/High
Min
On
On
On
On
On
Off
Off
11
Em Heat
On/High
Min
Off
Off
On
On
Off
Off
Off
Note:
Steps for optional accessories and modes not present in unit will be skipped.
(a)
With optional accessory
(b)
CPR2 ON during Cool 1 if configured for 3-step cooling; CPR1 OFF.
(c)
"Off" if OAT falls below 60°F, "On" if OAT rises above 65°F. During Reheat, if the unit is configured with 1 compressor, ODM2 is "Off" if the OAT falls below
70°F, "On" if the OAT rises above 75°F.
(d)
CPR2 OFF during Cool 2 on a 3-step cooling unit.
(e)
CPR2 OFF during Heat 1 if configured for 2-Step mechanical heating.
(f)
HT1 OFF during Heat 2 if the unit is configured for 2-Step mechanical heating.
(g)
HT2 OFF during Heat 3 if the unit is configured for 2-Step mechanical heating.
(h)
Defrost cycle in test mode runs for at least 1 minute, up to 10 minutes, depending on outdoor ambient and outdoor coil temperature.
Table 45.
Precedent
™
™
electric/electric — 17 SEER
Test
Step
Mode
Fan
Econ
Comp 1 Comp 2 Heat 1
Heat 2 Resistance Output
Multi-
Speed Fan
Output
1
Fan
On
Minimum Position
Setpoint 0%
Off
Off
Off
Off
2.2KΩ
50%
low
Minimum Ventilation
On
Selectable
Off
Off
Off
Off
2
Economizer Test Open
On
Open
Off
Off
Off
Off
3.3KΩ
50%
(a)
low
3
Cool Stage 1
On
Minimum Position
On
(b)
Off
Off
Off
4.7KΩ
82%
low
4
(c)
Cool Stage 2
On
Minimum Position
On
On
Off
Off
6.8KΩ
100%
High (2-step
cooling) Low
(3-step
cooling)
Cool Stage 3
On
Minimum Position
On
On
Off
Off
8.2KΩ
100%
High
Reheat
On
Minimum Position
On
On
Off
Off
33KΩ
100%
(d)
High
Heat Stage 1
On
Minimum Position
Off
Off
On
Off
10KΩ
100%
High
Heat Stage 2
On
Minimum Position
Off
Off
On
On
15KΩ
100%
High
Notes:
1
.
The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint.
2
.
The modulating output is in reference to the user selected maximum unit fan speed.
(a)
Regardless of the economizer mode configuration, the unit will run the supply fan at the minimum speed during the economizer step of the service test.
(b)
The condenser fans will operate any time a compressor is ‘On’ providing the outdoor air temperatures are within the operating values.
(c)
Steps for optional accessories and non-applicable modes in unit will be skipped.
(d)
Units with enhanced dehumidification only will not perform this step during service test.