Table 5: Controller Faults (indicated on the controller)
Xe-50 DISPLAY
MEANING
CAUSE
REMEDY
Warnings
A:2040
“Freeze Warning
(Dryer Package Only)”
Dryer low temperature warning.
This serves as a log that the compressor is running in low-
ambient conditions.
A:2050
“Dryer High Pressure
(Dryer Pressure Only)”
Dryer high pressure warning.
This is a locking switch and the dryer high pressure switch
must be reset (contact closed) before this warning can be
reset.
A:2118
High Airend Discharge
Pressure
Discharge pressure is greater than
offline pressure by 1.45 psi for a
period of 3 seconds or longer
Discharge pressure must fall to the rated pressure value
before the unit is available for reload.
A:2128
High Airend Discharge
Temperature (above
105°C)
Compressor operating above rated
pressure.
Check and modify settings. Review system requirements
and contact your local
Ingersoll Rand
representative.
Low coolant level.
Check for leaks. See also if discharge air is contaminated
with coolant. Top off coolant.
High ambient temperature.
Review installation and system parameters.
Insufficient cooling air.
Check ducting and cooling air path.
Dirty, blocked coolant cooler
(cooling air side).
Clean or replace.
Fan motor direction of rotation
incorrect.
Wire correctly.
A:2816
Power Failure Detected
If power supply to controller is
inconsistant.
Check power supply.
A:4804
Service Due
Service interval hours counter has
reduced to zero
Service compressor.
Trips
E:0010
Emergency Stop
24Vac input not being detected
on terminal R1C (emergency stop
button pressed)
Identify reason why, repair fault, disengage button (if
pressed) and reset conroller.
E:0020
Main or Blower Motor
Overload
Will occur if the fan or main motor
overload relays open for three
seconds. Fan is blocked, damaged
or blower fan is faulty.
Remove blockage, repair or replace damaged
components.
E:0115
Pressure Sensor Fault
4-20mA signal out-of-range
(<3.8mA or >20.8mA)
Install, repair or replace faulty sensor.
E:0119
High Airend Discharge
Pressure
Discharge pressure is greater than
offline pressure by 4.35 psi
Check and modify settings. Review system requirements
and contact your local
Ingersoll Rand
representative.
E:0125
Temperature Sensor
Fault
Signal out of range (<-50°C or
>250°C)
Install, repair or replace faulty sensor.
E:0129
Excess Temperature
Shutdown limit exceeded
Can be reset only when airend discharge temperature is
lower than 107°C.
E:0866
Power Supply 24V DC
Low
24V DC power supply to controller
is low.
Check controller power supply and call your local
Ingersoll Rand
representative.
E:0821
Power Supply Analog
Inputs Low
Analog input power supply to
controller is low.
Check controller power supply and call your local
Ingersoll Rand
representative.
Start
Inhibit
A:3129
High Airend Discharge
Temperature (above
103°C)
Airend discharge temperature
above 103°C.
Abnormal operating condition which is self-clearning.
A:3123
Run Inhibited
Temperature is below set low
temperture run inhibit limit.
Will self-reset when temperature increases above the
temperature limit; cannot be manually reset.
A:3423
Load Inhibited
Temperature is below set low
temperature load inhibit limit.
Will self-reset when temperature increases above the
temperature limit; cannot be manually reset.
RELEASED 16/Dec/2014 10:49:53 GMT
Содержание R4-11 kW
Страница 19: ...RELEASED 16 Dec 2014 10 49 53 GMT...
Страница 20: ...ingersollrandproducts com 2014 Ingersoll Rand RELEASED 16 Dec 2014 10 49 53 GMT...
Страница 39: ...RELEASED 16 Dec 2014 10 49 53 GMT...
Страница 40: ...ingersollrandproducts com 2014 Ingersoll Rand RELEASED 16 Dec 2014 10 49 53 GMT...
Страница 60: ...ingersollrandproducts com 2014 Ingersoll Rand RELEASED 16 Dec 2014 10 49 53 GMT...
Страница 80: ...ingersollrandproducts com 2014 Ingersoll Rand RELEASED 16 Dec 2014 10 49 53 GMT...