background image

EN-5   

80446339

 Rev B

EN

Electrical

A qualified electrician shall perform all electrical installations and service.

The compressor shall be properly grounded / earthed in compliance with all 

applicable standards and regulations (local, state, country, federal, etc.).

Installation of this compressor shall be in compliance with all applicable 

standards and regulations (local, state, country, federal, etc.).

The compressor shall have its own isolator situated adjacent to it. The fuse 

protecting the circuit and the compressor shall be selected in accordance 

with recognized code requirements on the basis of the data provided in the 

specification sheet.

Feeder cables shall be sized to ensure that the circuit is balanced and not 

overloaded by other electrical equipment. The length of wiring from a 

suitable electrical feed point is critical as voltage drops may impair the 

performance of the compressor.

NOTICE

For VSD, cable sizes may vary considerably so the line reactor is 

equipped with copper bus connections . These connections can accept 

bolts between 6 mm and 12 mm .

Feeder cable connections to incoming terminals L1-L2-L shall be tight and 

clean.

The applied voltage shall be compatible with the compressor data plate 

ratings.

The control circuit transformer has different voltage tappings. Ensure that 

these are set for the specific applied voltage prior to starting.

Remove the blind plate to cut a hole for incoming power connection. If it 

is necessary to make a hole in the control box in a different location, care 

should be taken to not allow metal shavings to enter the starter and other 

electrical components within the box. If another hole is used, the original 

hole shall be blocked off.

The feeder cable shall be suitably glanded in to the starter box to maintain 

proper ingress protection. Fixed speed starter boxes are rated for NEMA 4 

/IP65, and variable speed drive starter boxes are rated for NEMA12/IP54. 

For variable speed drive starter boxes, the feeder cable shall be glanded to 

ensure that dirty air does not by-pass the filters.

On completion of electrical installation, check that the blower or fan motor 

rotation is correct. 

Variable speed drive compressors are designed for use, where the electricity 

supply is separated from nearby residential and commercial areas. If the 

compressor is to be used in a light industrial, residential or commercial 

environment where the local supply network is shared, further radio 

frequency (RF) screening measures may be required. Consult your local 

distributor/supplier for details of the optional RF filter. 

Variable speed drive compressors have an anti-condensation heater 

and thermostat in the electrical box. This circuit can be connected to 

an independent electrical supply of either 110 V or 20 V single phase, 

dependent on the country of installation. The supply shall be suitably fused 

and an independent isolator installed adjacent to the compressor. Verify that 

the thermostat is adjusted to 29˚ C (85˚ F). This shall be done in accordance 

with recognized codes. It is good practice, and sometimes mandatory, 

to display suitable signs warning that the compressor has two separate 

electrical supplies which both shall be isolated before any work is attempted.

For Variable speed drive compressors, the heater circuit can also be supplied 

from the 110 V tapping of the control transformer and connected as shown 

on the schematic wiring diagram furnished separately from this manual.

NOTICE

Main and fan motor insulation shall be tested by a qualified electrician 

prior to initial start-up or following an extended shutdown period in 

cold and damp conditions .

Watercooled

Cooling Water Piping

NOTICE

Water piping to and from the compressor package shall be at least 

as large as the package connection size . Do not undersize the water 

piping .

Isolation valves with side drains should be installed on both the inlet and 

outlet lines. To maintain cooler cleanliness and reliability, it is important to 

install a strainer of 2 mm mesh size on the inlet line. Strainers are available 

from 

Ingersoll Rand

.

For sea water applications (sea water option only) a zinc anode is not 

recommended as it will deteriorate the copper oxide film on the 70/0 

copper-nickel alloy tubes in contact with sea water. To minimize galvanic 

corrosion and provide the greatest corrosion protection to the coolers, it 

is strongly recommended that a section of iron pipe (>00 mm length) be 

connected as close as possible to the air compressor package water inlet 

connection. The iron pipe will act as the sacrificial anode for the copper-

nickel tubes and therefore shall be considered a regular maintenance and 

replacement item. For this reason, the section of iron pipe should be installed 

so that it can be easily replaced (e.g. with a union joint.). 

The air compressor has a normally closed solenoid valve that is fitted to 

the water outlet side within the package. The valve is wired into the air 

compressor control circuit and closes when the compressor stops.

Carefully inspect the water system before installing the air compressor 

package. Ensure that the piping is free of scale and deposits that may 

restrict water flow to the air compressor package. If water cleanliness is poor, 

filtration installed on the water inlet pipe line is recommended.

Proper operation of the compressor requires that the cooling water flow 

be provided at a maximum supply temperature of 46° C (115° F). See the 

compressor engineering data sheets for cooling water flow rates.

Water temperature and pressure gauges should be installed in the water 

piping for use in any fault finding of the water system. Water pressure should 

ideally be between  and 5 bar (4.5 and 72.5 psi) but shall not be above 10 

bar (145 psi).

Water cleanliness is also extremely important. Cleaning of coolers as a result 

of fouling is a customer responsibility. Therefore, it is highly recommended 

that proper water quality shall meet the requirements listed in WATER 

QUALITY RECOMMENDATIONS later in this section.

Venting the water system

Air should be vented from the water side of the system to avoid poor 

performance and water hammer. Since the air compressor uses different 

type heat exchangers depending on your selection of “fresh water cooled” 

or “harsh water cooled” system, the venting procedure is different. Be sure to 

use the correct procedure below.

Fresh water coolers (brazed plate heat exchangers):

1.  Disconnect the water stop valve in the water outlet line of the 

compressor.

2.  Open the inlet water valve(s) to allow the water to flow to the 

compressor.

.  Allow all the air to escape from the system and observe water at the 

water outlet port.

4.  Connect the water stop valve.

Harsh water coolers (shell and tube heat exchangers):

1.  Locate the water system vent cocks on top of the aftercooler and oil 

cooler.

2.  Open the water valve(s) allowing water to flow to the package.

.  Open the vent cocks and allow all air to escape from the system. 

When water is observed at the vent cocks, close them.

 110812.16.23

Содержание R132

Страница 1: ...80446339 Revision B October 2012 Save These Instructions Contact Cooled Rotary Screw Air Compressor Product Information R37 160 110812 16 23 PRINT LANGUAGE ENGLISH SPANISH FRENCH PORTUGUESE...

Страница 2: ...ice warnings 15 Initial check trips 15 Trips 15 OPERATING INSTRUCTIONS FOR FIXED SPEED FS 16 SG Controller Controls Fixed Speed 16 Display screen 16 Current status 17 Main menu 18 Operator setpoints 1...

Страница 3: ...ks are fully engaged on both sides Alternatively a special lifting frame can be used to enable a crane or hoist to move the compressor Use only marked lifting points Once the packaging and pallet are...

Страница 4: ...volume is sufficient 1 2 4 5 6 7 8 Discharge piping should be at least as large as the discharge connection of the compressor All piping and fittings should be suitably rated for the discharge pressur...

Страница 5: ...agram furnished separately from this manual NOTICE Main and fan motor insulation shall be tested by a qualified electrician prior to initial start up or following an extended shutdown period in cold a...

Страница 6: ...surface Perhaps the largest contributor to scale formation is the precipitation of calcium carbonate out of the water This is dependent on temperature and pH level The higher the pH value the greater...

Страница 7: ...the system is enhanced by a control logic that varies the cooling blower speed dependent on the intake and discharge temperatures and hence controls the injection temperature even closer while saving...

Страница 8: ...by a local or remote stop a shutdown due to a trip or an emergency stop All of the above conditions will cause the compressor to stop immediately except the local or remote stop A local or remote stop...

Страница 9: ...ow the display screen are defined by the words immediately above them in the bottom line of the screen Each function such as MAIN MENU STATUS etc is described in appropriate sections in this manual Di...

Страница 10: ...when the ENERGY STATUS screen is displayed pressing the STATUS button will toggle the display to the CURRENT STATUS screen The ENERGY STATUS screen displays the following items ENERGY STATUS Items Ave...

Страница 11: ...ser adjustable variables in the controller logic that can be set using the OPERATOR SETPOINTS screen shown here The name and value of each of the setpoints listed can be seen on the screen by moving t...

Страница 12: ...is pressure The range for this setpoint will be the automatic stop pressure to automatic stop pressure 10 psi Blowdown Mode Two stage compressors will always blowdown when signalled to stop If this mo...

Страница 13: ...the day that a scheduled start will take place The selections are Sunday Monday Tuesday Wednesday Thursday Friday Saturday Daily Su Sa Weekdays M F or Weekends This option setpoint will work with the...

Страница 14: ...f the compressor for the time period that was started by selecting the reset averaging setpoint This is calculated by multiplying the kW hours of the motor and the blower by the energy rate ENERGY SAV...

Страница 15: ...ecognized as missing or broken VSD FAULT The VSD fault is read from the drive The controller will read the status menu of the variable speed drive If a fault condition is returned in the status inform...

Страница 16: ...ultiple functions relating to the right half of the display screen When lists are presented the buttons are used to move up or down through the items on the list The small arrow s displayed in the upp...

Страница 17: ...r IN PR Coolant Filter OUT PR Inlet Vacuum Inlet Filter Total Hours Loaded Hours Software Title and Version Figure 16 Operator Panel Flow Diagram The controller automatically returns the display to th...

Страница 18: ...onal compressor hardware and the correct Option Module to plug into the controller Descriptions of the options operations can be found later in this section The name and value of each of the following...

Страница 19: ...s each of the Trip messages for the last 15 Trips experienced by the compressor It also gives access to displaying the compressor operating conditions that existed at the time of each Trip The first o...

Страница 20: ...exceptions to this are explained in the Trip descriptions The possible Trip messages are as follows CHECK MOTOR ROTATION This will occur if the compressor is started and the compressor has incorrect r...

Страница 21: ...he main electrical isolation switch Stopping the compressor in an emergency If the compressor has to be stopped in an emergency DEPRESS THE EMERGENCY STOP BUTTON 1 This will over ride the normal unloa...

Страница 22: ...d logged in the event log Table 9 Command Keys Icon Name Function None Load Puts the compressor into the selected mode of operation Unit will load if the pressure conditions are right Unload Puts the...

Страница 23: ...Indicates that there are more pages available by navigating left Accessing parameters After the desired page is selected the page s parameters can be selected by using the DOWN key The cursor will mov...

Страница 24: ...ble from the General Settings folder Run Hours indicate the number of hours the compressor has been running NOTICE The online and offline set points can be selected and modified on this page All other...

Страница 25: ...perator Options Selection Min Max Def Step Unit Installed option required Enable Auto Restart ON OFF Off No Auto Restart Time 2 60 10 1 min No Auto Restart Delay 0 60 0 1 sec No Comm Control ON OFF Of...

Страница 26: ...See the following lists for details about messages in each type of event Warning Events List Change Inlet Filter Will occur if 1AVPT is greater than 0 7 psi vacuum or 1 3 psi vacuum if the high dust...

Страница 27: ...709 about 5 C However the warning will still be displayed Dryer High Pressure On compressors with the integrated dryer this will occur if the dryer high pressure switch opens while the dryer is runni...

Страница 28: ...r if the sensor zero value is 10 of its scale This will only occur when a sensor is calibrated Start Inhibit List High Airend Discharge Temperature This will occur if 2ATT is greater than 95 of 228 F...

Страница 29: ...ian Chinese simplified Croatian Czech Danish Dutch Estonian Finish French German Greek Hungarian Italian Indonesian Korean Latvian Lithuanian Maltese Norwegian Polish Portuguese Romanian Russian Slova...

Страница 30: ...y Confirm New Time and Date Used to verify that changes to selections are desired An x must appear in the checkbox before any changes will take affect The controller will continue to display any chang...

Страница 31: ...Discard any changes made to the Ethernet settings Status folder NOTICE All information on these pages is read only Pages 1 3 Analog Inputs Figure 50 Analog Inputs The following inputs are displayed i...

Страница 32: ...ues in this folder This folder is used for setting parameters that are specific to that compressor and displaying software information for the controller Page 1 Password Figure 55 Password Table 21 Pa...

Страница 33: ...lways centered on the gauge This is the pressure that the compressor is trying to maintain Automatic Stop Setpoint is indicated in the white box and by the white arrow which is always right of center...

Страница 34: ...e Injected Coolant Temperature Aftercooler Discharge Temperature Separator Pressure Drop Coolant Filter Pressure Drop Inlet Vacuum Remote Pressure optional Aftercooler Discharge Pressure integrated dr...

Страница 35: ...perature is only adjustable if the low ambient factory set point is on A value of 0 will disable the lead lag cycle time feature Pages 6 7 Sensor Calibration Figure 63 Sensor Calibration Sensor calibr...

Страница 36: ...occur if the compressor is running and 2ATT is greater than 221 F 97 of 228 or the compressor is in idle mode 3 3 7 1 and 2ATT is greater than 184 F This warning will normally have a 5 second delay h...

Страница 37: ...en a sensor is recognized as missing or broken The sensors affected by this trip are 4APT 3APT 2APT 1AVPT 5CPT 6CPT and 2ATT The sensor should be displayed along with the sensor failure message The se...

Страница 38: ...168 psi Start Inhibit List High Airend Discharge Temperature This will occur if 2ATT is greater than 95 of 228 F High Sump Pressure This will occur if the sump pressure 3APT is 25 psi or higher than...

Страница 39: ...after the service has been performed General settings folder NOTICE All parameters in this folder are adjustable Page 1 Language Selection Figure 70 Language Selection Language is selectable from the...

Страница 40: ...elect Home Page Used to select the Home Page within the selected Home folder Page 4 5 Time Date Settings Figure 73 Time Date Settings All items are adjustable The following settings are displayed in t...

Страница 41: ...ed this setpoint sets the IP address of the controller IP Address Actual This will match the IP address setting when DHCP is not enabled If DHCP is enabled this will display the address assigned to th...

Страница 42: ...er Feedback is TRUE when its input is in the high state where as E Stop is TRUE when its input is at 0Vdc The following are displayed in this section Emergency Stop Main Motor Overload Fan Motor Overl...

Страница 43: ...able the password time feature Timeout Delay This timeout along with the password timeout enable allows the user to set an adjustable amount of time to require a valid password to be re entered Once t...

Страница 44: ...page highlighting this button and hitting enter will cause the controller to clear all history of maximum values and begin recording them again The password must be entered in order to use this reset...

Страница 45: ...110812 16 23...

Страница 46: ...110812 16 23...

Страница 47: ...writing to the Company in said period whereupon the Company shall at its option correct such nonconformity by suitable repair to such equipment or furnish a replacement part F O B point of shipment p...

Страница 48: ...ingersollrandproducts com 2012 Ingersoll Rand plc 110812 16 23...

Отзывы: