background image

EN-15   

80446339

 Rev B

EN

Service warnings

SERVICE

 - Service warnings occur when the compressor has operated a 

certain number of hours, based on the total hours. Service warnings can have 

multiple levels, depending on the service level selection.

This will be set prior to the compressor being shipped from the factory. When 

a service warning occurs, contact your local 

Ingersoll Rand

 service provider.

Initial check trips:

The following trips will only occur when the compressor is not running. These 

trips are related to high temperature, power loss, and sensor calibration. They 

will have the same display mode as other trips.

HIGH AIREND DISCH TEMP

- Will occur if the airend discharge temperature is 

greater than 95% of 109° C (228° F).

CHECK SETPOINTS

 - Will occur if the controller has determined that some of 

the data stored in memory contains unacceptable values.

INVALID CALIBRATION

 - Will occur if the sensor zero value is -10% to +1% of 

its scale. See Sensor Calibration.

Trips

Figure 12: Trip Screen

When a trip occurs, a large exclamation mark in a triangle will flash on the 

display screen. The display message will indicate what caused the trip.

The compressor will stop and cannot be re-started again until the trip 

condition no longer exists and the trip message reset.

Pressing the STATUS button will display the STATUS screen. The presence of 

the TRIP button indicates that a trip condition still exists. Trip Status is the list 

of compressor operating conditions that existed at the time of the trip.

The name and value of each of the items listed can be seen by moving the list 

up and down using the arrow buttons. Pressing the TRIP button will return 

the display to the trip screen and the RESET button.

The trip needs to be reset by the operator by pressing the RESET button 

twice. Any exceptions to this are explained in the trip descriptions.

The possible trip messages are as follows;

EMERGENCY STOP

- This will occur if the emergency stop button is engaged. 

The button shall be disengaged before the trip can be cleared.

BLOWER FAULT

- This will occur if a blower fault is sensed.

HIGH AIREND DISCH TEMP

- This will occur if the airend discharge 

temperature is greater than 109° C (228° F).

REMOTE START FAILURE

- This will occur if the remote start button is pressed 

after the compressor is running or if the remote start button remains closed.

REMOTE STOP FAILURE

- This will occur if the remote stop button remains 

open and either start button is pressed.

SENSOR FAILURE

 - This will occur if a sensor is recognized as missing or 

broken.

VSD FAULT

 - The VSD fault is read from the drive. The controller will read the 

status menu of the variable speed drive. If a fault condition is returned in the 

status information, the controller will issue a VSD FAULT trip and display the 

number of the fault condition.

STOP FAILURE

 - This will occur if the compressor should be stopped but the 

motor is still running above minimum speed 4 seconds after the stop signal 

is given.

HIGH START PRESSURE

 - If the sump pressure is above 6.9 bar (100 psi) 

when the compressor starts, the controller will open the blowdown valve 

during the first few seconds of starting ( to 7 seconds). If the sump pressure 

does not fall to 6.9 bar (100 psi) during that time period, this shutdown will 

occur.

CHECK MOTOR ROTATION

 - This will occur if the controller reads a negative 

speed from the VSD when starting.

VSD COMMUNICATION FAILURE

 - This will occur if the controller does not 

receive a response from the VSD when requesting information. This trip will 

take about 8 seconds to occur.

VSD INITIALIZATION FAULT

 - Will occur if the controller is unable to 

establish communications with the VSD after a power up.

LOW SUMP PRESSURE

 - Will occur if the compressor is operating at or above 

the minimum speed and the sump pressure drops below 1 bar (15 psi) for  

15 seconds.

REPLACE COOLANT FILTER

 - This will occur if the coolant filter is blocked 

and requires changing.

INCORRECT VSD TYPE

 - Will occur at power up if the VSD type does not 

match the size of the compressor.

CHECK INCOMING POWER

 - This will occur if the compressor should be 

running and the AC input voltage, as read from the VSD, falls below 100 VAC. 

There is a delay of 2 seconds on this trip in case the power quickly returns. 

Phase monitor can also cause this trip.

HIGH INTERSTAGE PRESSURE

 - If the interstage pressure is over 7 bar  

(100 psi) while the compressor is running and the compressor is a two stage 

compressor.

HIGH COOLANT FILTER PRESSURE DROP

 - Occurs if the compressor has 

been running for at least 7 seconds, the compressor is warm, already has a 

change coolant filter warning, the motor is running, and the coolant filter 

pressure drop is greater than 2.5 bar (5 psi).

HIGH INLET VACUUM

 - Occurs if the compressor is running loaded, the 

motor is running, and the inlet vacuum is greater than 0.1 bar (1.8 psi) 

(vacuum).

HIGH SUMP PRESSURE 

- Occurs if the compressor is running, the 

compressor is warm, and any one of the three following conditions exist.

1.  The sump pressure is above the maximum offline pressure by  

25 psi.

2.  The separator pressure drop is measured to be more than 25 psi 

and the package discharge pressure is at least 65 psi.

.  The sump pressure is above 170 psi.

 110812.16.23

Содержание R132

Страница 1: ...80446339 Revision B October 2012 Save These Instructions Contact Cooled Rotary Screw Air Compressor Product Information R37 160 110812 16 23 PRINT LANGUAGE ENGLISH SPANISH FRENCH PORTUGUESE...

Страница 2: ...ice warnings 15 Initial check trips 15 Trips 15 OPERATING INSTRUCTIONS FOR FIXED SPEED FS 16 SG Controller Controls Fixed Speed 16 Display screen 16 Current status 17 Main menu 18 Operator setpoints 1...

Страница 3: ...ks are fully engaged on both sides Alternatively a special lifting frame can be used to enable a crane or hoist to move the compressor Use only marked lifting points Once the packaging and pallet are...

Страница 4: ...volume is sufficient 1 2 4 5 6 7 8 Discharge piping should be at least as large as the discharge connection of the compressor All piping and fittings should be suitably rated for the discharge pressur...

Страница 5: ...agram furnished separately from this manual NOTICE Main and fan motor insulation shall be tested by a qualified electrician prior to initial start up or following an extended shutdown period in cold a...

Страница 6: ...surface Perhaps the largest contributor to scale formation is the precipitation of calcium carbonate out of the water This is dependent on temperature and pH level The higher the pH value the greater...

Страница 7: ...the system is enhanced by a control logic that varies the cooling blower speed dependent on the intake and discharge temperatures and hence controls the injection temperature even closer while saving...

Страница 8: ...by a local or remote stop a shutdown due to a trip or an emergency stop All of the above conditions will cause the compressor to stop immediately except the local or remote stop A local or remote stop...

Страница 9: ...ow the display screen are defined by the words immediately above them in the bottom line of the screen Each function such as MAIN MENU STATUS etc is described in appropriate sections in this manual Di...

Страница 10: ...when the ENERGY STATUS screen is displayed pressing the STATUS button will toggle the display to the CURRENT STATUS screen The ENERGY STATUS screen displays the following items ENERGY STATUS Items Ave...

Страница 11: ...ser adjustable variables in the controller logic that can be set using the OPERATOR SETPOINTS screen shown here The name and value of each of the setpoints listed can be seen on the screen by moving t...

Страница 12: ...is pressure The range for this setpoint will be the automatic stop pressure to automatic stop pressure 10 psi Blowdown Mode Two stage compressors will always blowdown when signalled to stop If this mo...

Страница 13: ...the day that a scheduled start will take place The selections are Sunday Monday Tuesday Wednesday Thursday Friday Saturday Daily Su Sa Weekdays M F or Weekends This option setpoint will work with the...

Страница 14: ...f the compressor for the time period that was started by selecting the reset averaging setpoint This is calculated by multiplying the kW hours of the motor and the blower by the energy rate ENERGY SAV...

Страница 15: ...ecognized as missing or broken VSD FAULT The VSD fault is read from the drive The controller will read the status menu of the variable speed drive If a fault condition is returned in the status inform...

Страница 16: ...ultiple functions relating to the right half of the display screen When lists are presented the buttons are used to move up or down through the items on the list The small arrow s displayed in the upp...

Страница 17: ...r IN PR Coolant Filter OUT PR Inlet Vacuum Inlet Filter Total Hours Loaded Hours Software Title and Version Figure 16 Operator Panel Flow Diagram The controller automatically returns the display to th...

Страница 18: ...onal compressor hardware and the correct Option Module to plug into the controller Descriptions of the options operations can be found later in this section The name and value of each of the following...

Страница 19: ...s each of the Trip messages for the last 15 Trips experienced by the compressor It also gives access to displaying the compressor operating conditions that existed at the time of each Trip The first o...

Страница 20: ...exceptions to this are explained in the Trip descriptions The possible Trip messages are as follows CHECK MOTOR ROTATION This will occur if the compressor is started and the compressor has incorrect r...

Страница 21: ...he main electrical isolation switch Stopping the compressor in an emergency If the compressor has to be stopped in an emergency DEPRESS THE EMERGENCY STOP BUTTON 1 This will over ride the normal unloa...

Страница 22: ...d logged in the event log Table 9 Command Keys Icon Name Function None Load Puts the compressor into the selected mode of operation Unit will load if the pressure conditions are right Unload Puts the...

Страница 23: ...Indicates that there are more pages available by navigating left Accessing parameters After the desired page is selected the page s parameters can be selected by using the DOWN key The cursor will mov...

Страница 24: ...ble from the General Settings folder Run Hours indicate the number of hours the compressor has been running NOTICE The online and offline set points can be selected and modified on this page All other...

Страница 25: ...perator Options Selection Min Max Def Step Unit Installed option required Enable Auto Restart ON OFF Off No Auto Restart Time 2 60 10 1 min No Auto Restart Delay 0 60 0 1 sec No Comm Control ON OFF Of...

Страница 26: ...See the following lists for details about messages in each type of event Warning Events List Change Inlet Filter Will occur if 1AVPT is greater than 0 7 psi vacuum or 1 3 psi vacuum if the high dust...

Страница 27: ...709 about 5 C However the warning will still be displayed Dryer High Pressure On compressors with the integrated dryer this will occur if the dryer high pressure switch opens while the dryer is runni...

Страница 28: ...r if the sensor zero value is 10 of its scale This will only occur when a sensor is calibrated Start Inhibit List High Airend Discharge Temperature This will occur if 2ATT is greater than 95 of 228 F...

Страница 29: ...ian Chinese simplified Croatian Czech Danish Dutch Estonian Finish French German Greek Hungarian Italian Indonesian Korean Latvian Lithuanian Maltese Norwegian Polish Portuguese Romanian Russian Slova...

Страница 30: ...y Confirm New Time and Date Used to verify that changes to selections are desired An x must appear in the checkbox before any changes will take affect The controller will continue to display any chang...

Страница 31: ...Discard any changes made to the Ethernet settings Status folder NOTICE All information on these pages is read only Pages 1 3 Analog Inputs Figure 50 Analog Inputs The following inputs are displayed i...

Страница 32: ...ues in this folder This folder is used for setting parameters that are specific to that compressor and displaying software information for the controller Page 1 Password Figure 55 Password Table 21 Pa...

Страница 33: ...lways centered on the gauge This is the pressure that the compressor is trying to maintain Automatic Stop Setpoint is indicated in the white box and by the white arrow which is always right of center...

Страница 34: ...e Injected Coolant Temperature Aftercooler Discharge Temperature Separator Pressure Drop Coolant Filter Pressure Drop Inlet Vacuum Remote Pressure optional Aftercooler Discharge Pressure integrated dr...

Страница 35: ...perature is only adjustable if the low ambient factory set point is on A value of 0 will disable the lead lag cycle time feature Pages 6 7 Sensor Calibration Figure 63 Sensor Calibration Sensor calibr...

Страница 36: ...occur if the compressor is running and 2ATT is greater than 221 F 97 of 228 or the compressor is in idle mode 3 3 7 1 and 2ATT is greater than 184 F This warning will normally have a 5 second delay h...

Страница 37: ...en a sensor is recognized as missing or broken The sensors affected by this trip are 4APT 3APT 2APT 1AVPT 5CPT 6CPT and 2ATT The sensor should be displayed along with the sensor failure message The se...

Страница 38: ...168 psi Start Inhibit List High Airend Discharge Temperature This will occur if 2ATT is greater than 95 of 228 F High Sump Pressure This will occur if the sump pressure 3APT is 25 psi or higher than...

Страница 39: ...after the service has been performed General settings folder NOTICE All parameters in this folder are adjustable Page 1 Language Selection Figure 70 Language Selection Language is selectable from the...

Страница 40: ...elect Home Page Used to select the Home Page within the selected Home folder Page 4 5 Time Date Settings Figure 73 Time Date Settings All items are adjustable The following settings are displayed in t...

Страница 41: ...ed this setpoint sets the IP address of the controller IP Address Actual This will match the IP address setting when DHCP is not enabled If DHCP is enabled this will display the address assigned to th...

Страница 42: ...er Feedback is TRUE when its input is in the high state where as E Stop is TRUE when its input is at 0Vdc The following are displayed in this section Emergency Stop Main Motor Overload Fan Motor Overl...

Страница 43: ...able the password time feature Timeout Delay This timeout along with the password timeout enable allows the user to set an adjustable amount of time to require a valid password to be re entered Once t...

Страница 44: ...page highlighting this button and hitting enter will cause the controller to clear all history of maximum values and begin recording them again The password must be entered in order to use this reset...

Страница 45: ...110812 16 23...

Страница 46: ...110812 16 23...

Страница 47: ...writing to the Company in said period whereupon the Company shall at its option correct such nonconformity by suitable repair to such equipment or furnish a replacement part F O B point of shipment p...

Страница 48: ...ingersollrandproducts com 2012 Ingersoll Rand plc 110812 16 23...

Отзывы: