20
Danger
Please utilise extreme caution when performing work within the compressor. Wear
appropriate PPE
(Personal Protective Equipment)
, follow
lock out-tag out
procedures, and
ensure all safety procedures
.
Factory Settings
HV (380-460 Volts)
11kW / 10bar
11kW / 8bar
7.5kW / 10bar 7.5kW / 8bar
5.5kW / 10bar
5.5kW / 8bar
15HP / 150PSI 15HP / 115PSI 10HP / 150PSI 10HP / 115PSI 7.5HP / 150PSI 7.5HP / 115PSI
1.06
Limit Maximum (speed)
5800
6755
4065
4670
3150
3600
1.22
Limit Maximum (speed)
0
0
0
0
0
0
4.01
AMP
READ
READ
READ
READ
READ
READ
5.01
Frequency
READ
READ
READ
READ
READ
READ
5.02
Motor Voltage
READ
READ
READ
READ
READ
READ
5.03
Output Power
READ
READ
READ
READ
READ
READ
5.04
Motor Speed
READ
READ
READ
READ
READ
READ
5.05
DC Bus Voltage
READ
READ
READ
READ
READ
READ
5.06
Motor Nominal Frequency
84
84
84
84
84
84
5.07
Motor Nominal Current
34
34
34
34
34
34
5.08
Motor Nominal Speed
5040
5040
5040
5040
5040
5040
5.09
Motor Nominal Volts
370
370
370
370
370
370
5.11
Motor Poles
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
5.12
Autone
Off
Off
Off
Off
Off
Off
6.04
Start/Stop Logic Select
Run no Latch Run no Latch Run no Latch Run no Latch Run no Latch Run no Latch
6.10
Low or High Voltage setting
6.30
Drive Output Achieved
7.01
POD (REF ONLY)
7.02
Pressure Transducer (REF ONLY)
7.03
POD (REF ONLY)
7.06
ANA/DIGIT Input
8.01
Fan Control Running
8.02
Start Button
8.03
H.A.T.S.
8.04
Fixed / Constant speed
8.09
E-stop
8.31
Fan Output
10.20
10 Last Fault Codes
10.34
Reset Fault Times
5
5
5
5
5
5
14.14
PID Low Limit
43
30
62
43
79
55
22.01
Drive Type
12,5HxLV34
12,5HxLV34
12,5HxLV34
12,5HxLV34
12,5HxLV34
12,5HxLV34
The readout on the CDC will show ENABLED when blower is running. When not running
the read will show DISABLED.
DISABLED = High voltage.
Turn the knob for the Potentiometer and notice the percentage value move down when
the knob is turned to the left and to the right the value goes up to 100% (50% TAS).
Turn the knob for the Potentiometer completely to the right, the value to be read is 100%
(50% TAS). If value is lower than 97% (47% TAS), investigate further
Enabled = compressor running / Disabled = compressor not running.
Pressure feedback
ANA/DIGIT Input 1 mode
Fan output digital 1
Display of the last ten faults
When compressor is not running this parameter will read DISABLED, when start button is
pressed ENABLED will appear.
This parameter will show ENABLED, USER 1FAULT.
When the selector is in the constant speed position, ENABLED is displayed. When in the
fixed speed position, DISABLED will be displayed.
When the e-stop is open, the display will show DISABLED. When the e-stop is closed, the
display will show ENABLED.
With the CDC you will have access to all of these parameters when using the Up
Down arrows. ( High voltage )
Appendix 6