EN
66
80448608 Rev B
MODBUS
Register
(40XXX)
Variable
Read/
Write
Range
Notes
1
Status/Control
R/W
See table 1
3
Discharge Pressure
R
4
2nd Stage Inlet Pressure
R
5
2nd Stage Discharge Pressure
R
6
Inlet Vacuum
R
Value Divided by 10
7
Oil Filter Pressure Drop
R
8
Bearing Oil Pressure
R
9
2nd Stage Inlet Temp
R
10
1st Stage Discharge Temp.
R
11
2nd Stage Discharge Temp.
R
12
Bearing Oil Temp.
R
13
Package Discharge Temp.
R
19
1st Stage Inlet Temp
R
20
Percent Capacity
R
21
Percent Energy Savings
R
22
Blower Speed
R
25
Motor Speed
R
26
Motor Current
R
27
Input Voltage
R
28
DC Bus Voltage
R
29
Remote Pressure
R
Remote Sensor Option
30
Motor Voltage
R
31
Package kW
R
32
kW Hours
R
0 - 999
Add to (mW hours * 1000)
33
mW Hours
R
34
Motor kW
R
48
Average Package kW-hr
R
49
Average % Capacity
R
50
Average Capacity
R
51
Package Energy Cost (Low)
R
0 – 99.99
Divide by 100
52
Package Energy Cost (High)
R
Multiply by 100
53
Energy Savings (Low)
R
0 – 99.99
Divide by 100
54
Energy Savings (High)
R
Multiply by 100
55
Lifetime Energy Savings (Low)
R
0 – 99.99
Divide by 100
56
Lifetime Energy Savings (High)
R
Multiply by 100
64
Running Hours (<10,000 hours)
R
0 - 9999
Less Than 10000
65
Ten Thousand Running Hours
R
Multiply value by 10000
94
Modbus Pressure Unit
R
See table 2
95
Modbus Temperature Unit
R
See table 2
98
Compressor Type
R
0 - 10
See table 2
99
Service Level
R
0 - 2
See table 2
101
Service Interval
R
1000 - 8000
hours
102
Hot Discharge
R
0 or 1
112
Target Pressure
R/W
65 - 150