6.7.4. Additional available Input/output (Optional)
1. T27 and T29 are configurable for digital input or output.
Digital output can be either digital or pulse output. The options for parameters 530 and 531 are all digital, however,
to enable pulse output the parameters in the table below should be set as shown. The pulse output variable can then be
selected using parameters 560 and 563.
VFD Parameter
Function
Setting
501
Terminal 27 mode
[1] Output
502
Terminal 29 mode
[1] Output
530
Terminal 27 Digital Output
[55] Pulse Output
531
Terminal 29 Digital Output
[55] Pulse Output
560
Terminal 27 Pulse Output Variable
Select output variable to display from the list
552
Pulse Output Max Freq #27
5000 (default)
563
Terminal 29 Pulse Output Variable
Select output variable to display from the list
555
Pulse Output Max Freq #29
5000 (default)
2. T42 analog output
Refer to Personal menu table (650, 651 and 652) to set parameter in VFD for this terminal.
3. Relays
Two relays are available for use (Parameter 540).
Refer to section 8.6.11 (page – 69) in VFD manual for detailed relay information.
6.8. Configured Input / Output Summary - Ordinary
Intended function
Alarm
Digital I/O Terminal
Ground Terminal
24VDC Terminal
Diaphragm 1 Leak Detect
AA1 - Diaphragm 1 Leak
18
20, 39 or 55
12 or 13
Diaphragm 2 Leak Detect
AA2 - Diaphragm 2 Leak
19
20, 39 or 55
12 or 13
Diaphragm 3 Leak Detect
AA3 - Diaphragm 3 Leak
32
20, 39 or 55
12 or 13
PTO (normally closed) -
Ordinary pump only
Alarm 11
33
20, 39 or 55
N / A
Safe Stop (E Stop)
Alarm 68
37
N / A
12 or 13
User Configurable I/O
27
20, 39 or 55
N / A
User Configurable I/O
29
20, 39 or 55
N / A
Analog In Terminal
Ground Terminal
10VDC Terminal
Speed Control
53
20, 39 or 55
50
Torque Control
54
20, 39 or 55
50
Analog Out Terminal
User Configurable Output
42
20, 39 or 55
N / A
6.9. VFD serial communication
1. Drive will have RS485 serial communication port.
Connect RS485 serial communication wiring to terminals (+) 68 and (-) 69.
2. Connect RS485 serial communication wiring to terminals (+) 68 and (-) 69.
3. Drive will support Modbus RTU field communication.
4. Set the below parameter for serial communication set-up.
VFD Parameter Function
8-30
Select Option [2] for Modbus RTU. Changing parameter is not
effective until after powering off frequency converter.
8-31
Enter the valid address for the frequency converter
(standard) port. e.g. [1-247]
8-32
Select option for the Baud rate match with FC (standard) port.
531
Terminal 29 Digital Output
560
Terminal 27 Pulse Output Variable
552
Pulse Output Max Freq # 27
563
Terminal 29 Pulse Output Variable
555
Pulse Output Max Freq # 29