27
Chapter 3
– Inputs-Outputs
XtrapulsPac Installation Guide
Chapter 3 – Inputs - Outputs
3.1 - DISPLAY
3.1.1 - Leds
RUN
: status of the CANopen® or EtherCAT® communication bus connection (according to drive version)..
ERROR
: faults grouped on the ‘ERROR’ LED: these errors are coded and can be displayed by means of the
parameterization software tool.
ERROR
LED unlit if no fault.
ERROR
LED flashing: ‘UNDERVOLTAGE’ error: no power supply voltage.
ERROR
LED continuously lit: fault.
The
ERROR
LED groups the following faults:
Power supply overvoltage.
24 V
DC
logic supply < 17.5 V
DC
.
Motor phase / GND short-circuit.
Braking system short-circuited or overheated, or braking resistor in open circuit.
Motor phase / motor phase short-circuit, power stage overtemperature, defective IGBT module.
Triggering of the I
2
t protection.
Counting error.
Position following error
EEPROM error.
Procedure execution error (busy).
Current offset error.
Drive rating overcurrent.
Motor temperature error.
Resolver or encoder cable interruption.
Hall sensors or absolute encoder error.
Notes
Any of these errors (except for the "Undervolt." error) involves:
The continuous lighting of the red
ERROR
LED,
The drive disabling,
The motor brake control if one of the logic outputs is configured as brake output,
The opening of the
AOK
relay contact. This relay must be wired as described in the connection diagrams of
section 4.1, in order to switch-off the power supply and keep a zero type standstill.
The ‘UNDERVOLTAGE’ error (flashing
ERROR
LED) involves:
The drive disabling,
The motor brake control.
RUN (green)
ERROR (red)