6. Specifications
E4 LCD
5000 (S)
E4 LCD
6000 (S)
E4 LCD
10k (S)
5000 VA
6000 VA
10000 VA
4000 W
4800 W
8000 W
INPUT
Low voltage
range
Battery mode transfer
110 V
-
230 V
176 VAC at 100% load / 110 VAC at 50% load
Low Line comeback
110 V
-
230 V
186 VAC at 100% load / 120 VAC at 50% load
High voltage
range
Battery mode transfer
110 V
-
230 V
300 VAC
High Line comeback
110 V
-
230 V
290 VAC
Frequency range
46~54 Hz at 50Hz / 56~64 Hz at 60Hz
Phase
Single phase with ground
Power factor
≧
0.99 at 100% load
OUTPUT
Voltage
208-220-230-240 VAC
AC voltage regulation
± 1%
Frequency range (synchronized range)
46 ~ 54 Hz at 50 Hz / 56 ~ 64 Hz at 60 Hz
Frequency range (battery mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current crest ratio
3:1 max
Harmonic distortion
≦
2% THD (Linear load)
≦
6% THD (Non linear load)
Transfer time
AC mode to battery mode
Zero
Inverter to Bypass
Zero
Waveform
Pure Sinewave
Backup time
From 8 to 30 minutes depending on connected load
Output outlets IEC 10A (or NEMA 110V)
standards/programmables
2 / 0
2 / 0
2 / 0
Output terminal standard/programmable
yes / yes
yes / yes
yes / yes
EFFICIENCY
AC mode
89%
Battery mode
88%