62
3-9. Fault Code
Fault
Fault code
Icon
Fault
Fault code
Icon
Bus start failure
01
None
Negative power fault
1A
None
Bus over
02
None
Battery SCR short-circuited
21
None
Bus under
03
None
Inverter relay short-circuited
24
None
Bus imbalance
04
None
Battery voltage loss
28
Bus short circuited
05
None
Parallel communication
failure
35 None
Inverter soft start failure
11
None
Output short-circuited
36
None
High Inverter voltage
12
None
Over temperature
41
None
Low Inverter voltage
13
None
CPU communication failure
42
None
Inverter output short-circuited
14
Overload 43
3-10. Warning Indicator
Warning Icon
(flashing)
Alarm
Battery low
Beeping every second
Overload
Beeping twice every second
Battery unconnected
Beeping every second
Over charge
Beeping every second
EPO enable
Beeping every second
Fan failure/Over temperature
Beeping every second
Charger failure
Beeping every second
I/P fuse broken
Beeping every second
Overload 3 times in 30min
Beeping every second