52
10.10. Maintenance bypass active Alarm
If Maintenance Bypass circuit breaker is brought to “ON” position, this alarm appears. Refer to
check if Maintenance Bypass decommissioning procedure has been respected.
10.11. Battery test failure Alarm
UPS tests the batteries periodically. In case the batteries failed in the battery test, this alarm appears.
Perform the test again when the batteries have been charged for min. 10 hours and verify the battery circuit
breaker is a
t “ON” position.
If the alarm continues, contact to Inform UPS Technical Service.
10.12. Input voltage failure Alarms
If the input voltage is not in specified limits, these alarms appear and In this case UPS operates in Battery
Operation mode. As soon as the mains voltage returns to specified limits, the alarms will disappear.
10.13. Inverter temperature high/ Rectifier temperature high Alarms
If temperature of the inverter or rectifier block rises, these alarms appear. The reasons can be: overload, fan
failure, high ambient temperature, and dusty environment. If fans failed or any other problem is identified,
contact Inform UPS Technical Service.
If any other alarm occurs or if the above alarms cannot be cleared, contact Inform UPS Technical Service.
Please prepare the following information before you contact Inform UPS Technical Service:
•
Ensure you read and apply troubleshooting procedure carefully
•
UPS Model Type
•
Serial Number
•
Firmware version
•
Date of failure or problem
•
Date of commissioning
•
Symptoms of failure or problem
•
Customer site address and contact information
•
Service contract references if any
Make sure that the UPS is not overloaded to provide a higher quality supply to the loads.
Содержание PYRAMID DSP PREMIUM Series
Страница 15: ...9 10 15 20 30kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 16: ...10 40 60kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 17: ...11 80kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 18: ...12 100 120kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 19: ...13 160kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 20: ...14 200 250 300kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 65: ...59 The manufacturer reserves the rights to change the technical specifications and design without notice...