24
When UPS has no separate bypass mains input, bypass line is also fed from the mains input. Thus, if such a
device is in question, mains input shall be comprehended when the bypass mains input is referred in the
following sections of the manual.
UPS behavior at the start-up is different from the usual operation. The UPS can only operate in bypass mode
during start-up. So, in order for the UPS to start-up, frequency/waveform/rms value of the bypass mains
voltage shall be in acceptable limits and bypass shall be enabled.
After start-up, the following applies: