rt up for “PARALLEL” UPSs not on Maintenance Bypass Mode;
1.
Switch the Bypass circuit breaker on the distribution panel to
“ON”
position.
2.
Switch the input circuit breaker on the distribution panel to
“ON”
position.
3.
Switch
F4
(Bypass) circuit breakers of all UPSs
“ON”
position.
4.
Switch
F1
(Input) circuit breakers of all UPSs to
“ON”
position.
5.
Switch
F6
(Inrush) circuit breakers of all UPSs to
“ON”
position.
6.
Touch Battery icon to see
Battery / DC
menu measurement. Do not close the battery circuit breakers
(F5)
until the difference between DC bus and Battery voltages decreases below 10V.
7.
If exists, switch external
Battery circuit breaker to
“ON”
position.
8.
Switch
F2
(Output) circuit breakers of all UPSs to
“ON”
position.
9.
Switch the output circuit breakers on the distribution panel to
“ON”
position.
Start up for “PARALLEL” UPSs on Maintenance Bypass Mode;
1.
Switch
F4
(Bypass) circuit breakers of all UPSs
“ON”
position.
2.
Switch
F1
(Input) circuit breakers of all UPSs to
“ON”
position.
3.
Switch
F6
(Inrush) circuit breakers of all UPSs to
“ON”
position.
4.
LCDs will be ON. See
“M. Bypass Mode”
written on LCD of all UPS.
5.
Touch Battery icon to see
Battery / DC
menu measurement. Do not close the battery circuit breakers
(F5)
until the difference between DC bus and Battery voltages decreases below 10V.
6.
If exists, switch external
Battery circuit breakers to
“ON”
position.
7.
Switch
F5
(Battery) circuit breakers of all UPSs to
“ON”
position.
8.
Switch
F2
(Output) circuit breakers of all UPSs to
“ON”
position.
9.
Switch
F3
(Maintenance Bypass) circuit breakers of all UPSs to
“OFF”
position.
10.
See
“Online Mode”
written on LCDs.
In case the communication cable is removed or damaged during parallel operation and the communication is
lost then the slave UPS which cannot communicate with the master UPS will disconnect from the output bus
and turn off. The other UPSs will continue normal operation. In such a case, this UPS should be turned off
completely in order to insert its communication cable again and then switched on again.
CAUTION:
Do not remove the communication cabl
es between the UPS’s during parallel
operation.
CAUTION:
Do not try to insert its communication cable while it is operating.
The Redundancy System expects to have at least one more UPS than N value. Otherwise it
shall provide
“Redundancy Lost”
alarm. The same alarm shall also appear in case:
Load % > N / ( N+1 ) * 100
Содержание PYRAMID DSP PREMIUM Series
Страница 15: ...9 10 15 20 30kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 16: ...10 40 60kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 17: ...11 80kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 18: ...12 100 120kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 19: ...13 160kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 20: ...14 200 250 300kVA Terminal Connections Separate Bypass Terminal Bypass L1 L2 L3 N version is optional...
Страница 65: ...59 The manufacturer reserves the rights to change the technical specifications and design without notice...