52
Free Running Frequency
[Hz]
± % 0.01
Voltage THD @ Rated
Linear Load
<%3
Nominal Apparent
Power [kVA]
10
15
20
30
40
60
80
100
120
Maximum Load P. F.
0.8
Nominal active power
[kW]
8
12
16
24
32
48
64
80
96
Nominal current [A] at
380V
15
23
30
45
61
91
121
151
182
Load Crest Factor @
Rated Power
3:1
Overload Duration
>1min @ %150 load
Efficiency (normal
operation) @rated linear
load with 0.8 PF
Up to 94% *
OUTPUT @ 1PH OUTPUT UPS’S
Performance
Classification
VFI-SS-111
-
Number of Phases
1PH+N+PE
-
Nominal Voltage [V]
220 / 230/ 240 (LINE-NEUTRAL)
-
Static
Voltage
Regulation
Normal
<%1
-
@ %100
Linear Load
Battery
Nominal Frequency [Hz]
50 / 60
-
Free Running Frequency
[Hz]
± % 0.01
-
Voltage THD @ Rated
Linear Load
<%3
-
Nominal Apparent
Power [kVA]
10
15
20
30
40
-
Maximum Load Power
Factor
0.8
-
Nominal Active Power
[kW]
8
12
16
24
32
-
Nominal current [A] at
380V
45
68
91
136
182
-
Load Crest Factor @
Rated Power
3:1
-
Overload Duration
>30sec @ %150 load
-
Efficiency (normal
operation) @rated linear
load with 0.8 PF
Up to 94%*
-
STATIC BY-PASS LINE @ 3PH OUTPUT UPS’S
Number of Phases
3P+N+PE