Installation Manual

 | ACINV Series 1RU Rack Mount Inverters

16

17

 +1 (208) 635-6400  |  www.transtector.com

 +1 (208) 635-6400  |  www.transtector.com

 •  Make sure that the chassis ground lug at the rear of the unit is solidly connected to the ground system of the rack or 

cabinet in which it is installed.

 •  Keep the cables between the battery or other DC source and the unit as short as possible and twist them together 

about 2 to 3 twists per foot.  This will minimise radiated interference from the cables.

Problem and Symptoms

Possible Cause  

Solution

Low output voltage

(120V : 95-105VAC)

Incorrect type of voltmeter

Use true RMS meter  (See section 2.4.7)

Display indicates OLP

Overload condition

Reduce load

No output voltage

Input voltage fault

Low / High input voltage

Recharge battery, check connections.

No output voltage

Display indicates OTP

Load <500W (1kVA unit)

Load <1000W (2kVA unit)

Thermal shutdown

Ensure ventilation openings are clean and

not obstructed.

Improve ventilation.

Reduce ambient temperature.

No output voltage

Display indicates OLP

Short circuit or wiring error

Excessive load

Check AC wiring for short circuit or

improper polarity (L and N reversed)

Remove load

If none of the above solves the problem please contact customer support, see inside front cover.

5. Important Safety Instructions

 

 

   

WARNING!

  

 

 

 

Before installing and using this inverter, be sure to read these

 

 

   safety 

instructions.

  

 

 

 

Keep them in a safe place for future reference.

 

  5.1 General Safety Precautions

   

5.1.1  Do not expose the Inverter to rain, snow, spray or dust. To reduce risk of hazard, do not cover or obstruct 

the ventilation openings.  Do not install the Inverter in a zero-clearance compartment as overheating may 

result.

 

   

5.1.2  To avoid a risk of fire and electronic shock. Make sure that existing wiring is in good electrical condition; and 

that wire size is not undersized. Do not operate the Inverter with damaged or substandard wiring.

  

      

5.1.3  This equipment contains components which can produce arcs or sparks.  To prevent fire or explosion do not 

install in compartments containing batteries or flammable materials or in locations where require ignition 

protected equipment.

   

 

This  includes  any  space  containing  gasoline-powered  machinery,  fuel  tanks,  or  joints,  fittings,  or  other 

connection between components of the fuel system.

  5.2 Precautions When Working with Batteries

     

5.2.1  Ensure the installer is familiar with the material safety data sheet from the manufacturer of the batteries 

concerning safe use and medical treatment.

     

5.2.2  NEVER smoke or allow a spark or flame in the vicinity of batteries.

     

5.2.3  Do not drop a metal tool on the battery. The resulting sparks or short-circuit on the battery or other electrical 

part may cause an explosion.

   

5.2.4  Remove personal metal items such as rings, bracelets, necklaces, and watches when working with batteries.  

Lead-acid batteries produces a short-circuit current high enough to weld a ring or the like to metal, causing 

severe burn.

6. DIP switch settings

The follow tables define the various settings of the DIP switches mounted at the left side of the front panel of the Inverter.

Note that when changes are made to these settings it is necessary to recycle the power to the Inverter to allow 

the internal microprocessor to read the new settings.

S1

FREQ. (Hz)

S2

S3

BAUD RATE

S4

S5

VOLTAGE OUTPUT

ON

60 *

OFF

OFF

2400

OFF

OFF

100VAC

OFF

50

OFF

ON

4800 *

OFF

ON

110VAC

----

----

ON

OFF

9600

ON

OFF

115VAC *

----

----

ON

ON

19200

ON

ON

120VAC

* default setting as shipped.

7. Communications Protocol & Remote ON/OFF Function 

ACINV series inverters can communicate their status to a computer via an RS232 connection by sending a single ‘Status 

Inquiry’ Telnet command from the computer as follows.

Using a Terminal programme such as Hyperterminal create a profile with the following parameters:

  

Baud rate: to match setting on unit (default 2400)

  

Data bits: 8

  

Parity:  none

  

Stop bits: 1

  

Flow control: none

From the properties tab (in Hyperterminal) settings and then ASCII and make sure that all boxes are checked with the 

exception of ‘Force incoming data to 7-bit ASCII.

Make sure the profile is saved for future use.

At the computer type: Q1<cr>

The inverter will respond as follows:

INV INV data stream,  (MMM.M NNN.N PPP.P QQQ RR.R S.SS TT.T b7b6b5b4b3b2b1b0<cr>

Содержание Transtector ACINV Series

Страница 1: ...Installation Manual 2020 Infinite Electronics Inc Transtector is a registered trademark of Infinite Electronics Inc ACINV M Rev 1 ACINV Series 1RU Rack Mount Inverters...

Страница 2: ...with Batteries 16 6 DIP switch settings 17 7 Communications Protocol Remote ON OFF Function 17 REV DESCRIPTION CHK d APPR d DATE 1 Initial Release DWR 09 15 20 Product Support Product support can be...

Страница 3: ...for 1 minute 2040W for 20 seconds Efficiency FL 89 90 Output Voltage 100 110 115 120VAC 3 switch selectable Output Frequency 50Hz or 60Hz 0 05 switch selectable Peak Output Current 15A Output Waveform...

Страница 4: ...ON OFF Switch Switches the inverter electronics ON and OFF Should be in the OFF position during installation 2 1 2 Function Selector LEDs Display When the function selector is sequentially pushed the...

Страница 5: ...inal of the battery or DC source must be connected to the negative terminal of the battery or DC source WARNING Reverse polarity connection will blow an internal fuse and may also damage the unit beyo...

Страница 6: ...tion between the earthed conductor of the same DC supply circuit and the earthing conductor and also the point of earthing of the DC system The DC system shall not be earthed elsewhere 2 3 12 The DC s...

Страница 7: ...nce with the electrical codes or regulations applicable to your installation Cables that are not an adequate gauge too narrow or are too long will cause decreased inverter performance such as poor sur...

Страница 8: ...ecause it has been operated at power levels above its rating or because it has been installed in a location which does not allow it to dissipate heat properly The unit will automatically restart once...

Страница 9: ...tall in compartments containing batteries or flammable materials or in locations where require ignition protected equipment This includes any space containing gasoline powered machinery fuel tanks or...

Страница 10: ...V SPEC AC I P fault voltage is 140 0V SPEC AC O P voltage is 208 4V AC O P current is 34 AC O P frequency is 59 9 HZ DC I P voltage is 54 2V Temperature is 35 0 degrees centigrade RS232 Hardware conne...

Отзывы: