background image

Installation Manual

 | ACINV Series 1RU Rack Mount Inverters

10

11

 +1 (208) 635-6400  |  www.transtector.com

 +1 (208) 635-6400  |  www.transtector.com

   

2.3.1  Dry - Do not allow water to drip or splash on the inverter.

   

2.3.2  Elevated Operating Ambient - if the inverter is installed in a closed or multi-unit rack assembly the operating 

ambient temperature of the rack environment may be greater than the room ambient.  consideration should 

be given to installing the inverter in an environment compatible with the maximum ambient temperature of 

60°C.

   

2.3.3  Safe - Do not install the inverter in a battery compartment or other areas where flammable fumes may exist, 

such as fuel storage areas or engine compartments.

   

2.3.4  Reduced Airflow - Installation of the inverter in a rack should be such that the amount of airflow required for 

safe operation is not compromised.

   

2.3.5  Dust Free - Do not install the inverter in a dusty environment as dust and other particles such as wood 

shavings, filings can be pulled into the unit when the cooling fans are operating.

   

2.3.6  Close to Batteries - Avoid excessive cable lengths but do not install the inverter in the same compartment 

as the batteries.  Use the recommended wire lengths and sizes (see section 2.6).  Also, do not mount the 

inverter where it will be exposed to gasses produced by the battery as these gasses are highly corrosive 

and prolonged exposure will damage the inverter.

   

2.3.7  Mechanical Loading - Mounting of inverter in the rack should be such that a hazardous condition is not 

achieved due to uneven mechanical loading.

   

2.3.8  Circuit Overload - Consideration should be given to the connection of the inverter to the supply circuit and 

the effect that overloading of these circuits might have on over current protection devices and supply wiring.  

Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.

   

2.3.9  Reliable Earthing - Reliable earthing of rack-mounted equipment should be maintained.  Particular attention 

should be given to supply connections other than direct connections to the branch circuit (e.g. use of power 

strips).

   

2.3.10  The unit shall be connected directly to the DC supply system earthing electrode conductor or to a bonding 

jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode is connected.

   

2.3.11  The unit shall be located in the same immediate area (such as adjacent cabinets) as any other equipment 

that has a connection between the earthed conductor of the same DC supply circuit and the earthing 

conductor, and also the point of earthing of the DC system. The DC system shall not be earthed elsewhere.

   

2.3.12  The DC supply source must be located within the same premises as the unit.

   

2.3.13  Switching or disconnecting devices shall not be in the earthed circuit conductor between the DC source and 

the point of connection of the earthing electrode conductor.

   

2.3.14  This unit is intended for connection to a branch circuit with maximum 20A fuse protection. 

   

2.3.15  Please confirm that the AC input breaker is set to the OFF position before connecting/disconnecting the AC 

power.  Do not touch the AC INPUT terminals other than with properly insulated tools so as to avoid electric 

shock.  Ensure that the protective cover has been correctly fitted after installation or when any maintenance 

has taken place.

   

2.3.16  Protection in PRIMARY CIRCUITS against over currents, short circuits and earth faults shall be provided, 

either as an integral part of the unit or as part of the building installation.

   

2.3.17  Aluminium conductors must not be used for protective earthing connections.

   

2.3.18  For supply connections, use wires suitable for at least 105°C since, from test results, cable temperatures 

may exceed 90°C.

  2.4 Quick Hook-up and Testing

   

2.4.1  Unpack and inspect the power inverter.  If any damage is visible do not proceed any further.  Contact 

TRANSTECTOR Customer Service immediately

   

 

Ensure that the power switch and the AC input breaker are in the OFF position.

   

2.4.2  Connect the cables to the power input terminals on the rear panel of the power inverter. 

   

 

The red terminal is positive [+] and black terminal is negative [-]. 

   

 

Insert the cables into the terminals and tighten the Allen nut to clamp the wires securely.

    

 

 

WARNING!

   

 

 

 

You may observe a spark when you make this connection since

   

 

 

 

current may flow to charge capacitors in the power inverter.

   

 

 

 

Do not make this connection in the presence of flammable fumes. 

 

 

 

 

 

Explosion or fire may result.

    

 

 

WARNING!

   

 

 

 

Make sure all the DC connections are tight (torque to 9-10 ft-lbs,

   

 

 

 

11.7-13Nm). Loose connections will overheat and could result in

   

 

 

 

a potential hazard.

   

2.4.3  If connecting to a utility or other AC supply make the L, N and FG connections after placing the supplied 

safety cover over the AC supply cable.  See figure A below.

   

 

Note that it will be necessary to remove the two screws fixing the AC input connector in place and replace 

them with the two hex nut pillars supplied with the safety cover before it can be fitted.  See figure B below.

    

  WARNING! 

   

 

 

 

Connect to the utility supply only after the safety cover has

   

 

 

 

been installed.

AC Supply

Содержание Transtector ACINV Series

Страница 1: ...Installation Manual 2020 Infinite Electronics Inc Transtector is a registered trademark of Infinite Electronics Inc ACINV M Rev 1 ACINV Series 1RU Rack Mount Inverters...

Страница 2: ...with Batteries 16 6 DIP switch settings 17 7 Communications Protocol Remote ON OFF Function 17 REV DESCRIPTION CHK d APPR d DATE 1 Initial Release DWR 09 15 20 Product Support Product support can be...

Страница 3: ...for 1 minute 2040W for 20 seconds Efficiency FL 89 90 Output Voltage 100 110 115 120VAC 3 switch selectable Output Frequency 50Hz or 60Hz 0 05 switch selectable Peak Output Current 15A Output Waveform...

Страница 4: ...ON OFF Switch Switches the inverter electronics ON and OFF Should be in the OFF position during installation 2 1 2 Function Selector LEDs Display When the function selector is sequentially pushed the...

Страница 5: ...inal of the battery or DC source must be connected to the negative terminal of the battery or DC source WARNING Reverse polarity connection will blow an internal fuse and may also damage the unit beyo...

Страница 6: ...tion between the earthed conductor of the same DC supply circuit and the earthing conductor and also the point of earthing of the DC system The DC system shall not be earthed elsewhere 2 3 12 The DC s...

Страница 7: ...nce with the electrical codes or regulations applicable to your installation Cables that are not an adequate gauge too narrow or are too long will cause decreased inverter performance such as poor sur...

Страница 8: ...ecause it has been operated at power levels above its rating or because it has been installed in a location which does not allow it to dissipate heat properly The unit will automatically restart once...

Страница 9: ...tall in compartments containing batteries or flammable materials or in locations where require ignition protected equipment This includes any space containing gasoline powered machinery fuel tanks or...

Страница 10: ...V SPEC AC I P fault voltage is 140 0V SPEC AC O P voltage is 208 4V AC O P current is 34 AC O P frequency is 59 9 HZ DC I P voltage is 54 2V Temperature is 35 0 degrees centigrade RS232 Hardware conne...

Отзывы: