Installation Manual

 | ACINV Series 1RU Rack Mount Inverters

4

5

 +1 (208) 635-6400  |  www.transtector.com

 +1 (208) 635-6400  |  www.transtector.com

1. Features

 • R load Pure sine wave output (THD <3%)

 • By-pass function (when external AC source connected)

 • Programmable output frequency, 50/60Hz (front panel DIP switch)

 • RS232 Serial interface provides unit status

 • Thermostatically controlled cooling fans

 • Advanced microprocessor design

 • Protection: Input Low Voltage, Input Overvoltage, Overload, Output Short Circuit, Over Temperature

 

1.1 Applications

  

  

Office equipment – computers, printers, monitors, facsimile machines, scanner.

  

  

Applications should be limited only to ITE and office equipment.

1.2 Specifications

MODEL NUMBER

ACINV1-1KVA

ACINV2-2KVA

100-120VAC Models

Inverter Section

Input Voltage Range

42-62VDC

Input Current (Max.)

22.8A

45.0A

Input Current (NL)

0.3A

0.45A

Output Power

1000VA @ ±0.85 PF

850W @ 1 PF

2kVA @ 0.85 PF

1700W @ 1 PF

Surge Rating

900W for 1 minute, 950W for 3 second,

1000W for 1 second

1870W for 1 minute, 2040W for 20 seconds

Efficiency @ FL

89%

90%

Output Voltage

100/110/115/120VAC ±3%

(switch selectable)

Output Frequency

50Hz or 60Hz ±0.05%

(switch selectable)

Peak Output Current

15A

Output Waveform

Pure Sine Wave <3% THD (R Load)

Protection

Output Overload - Output Short Circuit

Input Reverse Polarity (fuse) - Input Undervoltage - Input Overvoltage

Over Temperature

Digital Display

OVP - UVP - OTP - OLP - VAC

AMP - WATT - VDC - TEMP - Hz

Control Port

RS232C

Baud Rates - 2400, 4800, 9600, 19200 (switch selectable)

STS Section

(By-Pass)

AC Input Range

90 - 130VAC (110VAC nominal)

Frequency

47 - 63Hz

Transfer Time

4 - 6ms

Alarm Relay

Form-C dry contacts, indicates presence of AC Utility supply

(NOTE: Not suitable for direct connection to SELV circuits)

THE STS BY-PASS SECTION IS ONLY ACTIVE WHEN A UTILITY OR OTHER AC SOURCE IS CONNECTED.

NORMAL OPERATION , WITH OR WITHOUT A UTILITY OR OTHER AC SOURCE IS ‘ON-LINE’ , WITH THE INVERT-

ER DELIVERING REGULATED AC TO THE OUTLETS.

General

Temperature Range

-20°C to +60°C Operating

-30°C to +70°C Storage

Safety

UL60950-1 (Listed - E130645)

EMC

FCC Class B

Dimensions

16.1”(d) x 19”(w) x 1.73”(h)

408.7mm(d) x 484.0mm(w) x 44.0mm(h)

Mounting

19” rack-mount, 1RU high

Weight

16.5lbs / 7.5Kg

Содержание Transtector ACINV Series

Страница 1: ...Installation Manual 2020 Infinite Electronics Inc Transtector is a registered trademark of Infinite Electronics Inc ACINV M Rev 1 ACINV Series 1RU Rack Mount Inverters...

Страница 2: ...with Batteries 16 6 DIP switch settings 17 7 Communications Protocol Remote ON OFF Function 17 REV DESCRIPTION CHK d APPR d DATE 1 Initial Release DWR 09 15 20 Product Support Product support can be...

Страница 3: ...for 1 minute 2040W for 20 seconds Efficiency FL 89 90 Output Voltage 100 110 115 120VAC 3 switch selectable Output Frequency 50Hz or 60Hz 0 05 switch selectable Peak Output Current 15A Output Waveform...

Страница 4: ...ON OFF Switch Switches the inverter electronics ON and OFF Should be in the OFF position during installation 2 1 2 Function Selector LEDs Display When the function selector is sequentially pushed the...

Страница 5: ...inal of the battery or DC source must be connected to the negative terminal of the battery or DC source WARNING Reverse polarity connection will blow an internal fuse and may also damage the unit beyo...

Страница 6: ...tion between the earthed conductor of the same DC supply circuit and the earthing conductor and also the point of earthing of the DC system The DC system shall not be earthed elsewhere 2 3 12 The DC s...

Страница 7: ...nce with the electrical codes or regulations applicable to your installation Cables that are not an adequate gauge too narrow or are too long will cause decreased inverter performance such as poor sur...

Страница 8: ...ecause it has been operated at power levels above its rating or because it has been installed in a location which does not allow it to dissipate heat properly The unit will automatically restart once...

Страница 9: ...tall in compartments containing batteries or flammable materials or in locations where require ignition protected equipment This includes any space containing gasoline powered machinery fuel tanks or...

Страница 10: ...V SPEC AC I P fault voltage is 140 0V SPEC AC O P voltage is 208 4V AC O P current is 34 AC O P frequency is 59 9 HZ DC I P voltage is 54 2V Temperature is 35 0 degrees centigrade RS232 Hardware conne...