on/off cooling valve
003
=2 and
025
=5 (DO1) or
026
=5 (DO2) or
027
=5 (DO3) or
028
=5 (DO4) or
029
=5 (DO5),
or on/off mixed-use valve in cooling
002
=4,
003
=2 and
025
=6 (DO1) or
026
=6 (DO2) or
027
=6 (DO3) or
028
=6 (DO4) or
029
=6
(DO5),
or modulating cooling valve
003
=1 and
030
=4 (AO1) or
031
=4 (AO2) or
032
=4 (AO3),
or modulating mixed-use cooling valve
002
=2
003
=1 and
030
=5 (AO1) or
031
=5 (AO2) or
032
=5 (AO3).
Operation with on/off bypass:
Do following settings:
-
170
=2 or 3 (authorization of free heating regardless the season),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- on/off bypass damper for heat exchanger
010
=2,
011
=1 and
012
=1,
025
=13 (DO1) or
026
=13 (DO2) or
027
=13 (DO3) or
028
=13 (DO4) or
029
=13 (DO5),
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
178
178
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
122
/2
WCS
178
178
100%
0%
Treg
WHS
123
100%
0%
Treg
WCS
123
178
178
100%
0%
Treg
WCS
178
100%
0%
Treg
WHS
178
Treg: control temperature
WCS: cooling operation setpoint
122
: neutral zone
178
hysteresis regulation free heating/cooling
In the presence of free heating conditions:
If Treg < (WCS -
123
) the on/off bypass damper is activated.
If Treg >= (WCS -
123
+
178
) the damper is disabled.
Note: the presence of the cooling battery is not mandatory.