Register Description
Default
Min
Max
R/W
9108
SAT_HOUR_ON_4
→
Start of Saturday hour timer period 4
21
0
23
R/W
9109
SAT_MIN_ON_4
→
Start of Saturday minute timer period 4
0
0
59
R/W
9110
SAT_HOUR_OFF_4
→
End of Saturday hour timer period 4
23
0
23
R/W
9111
SAT_MIN_OFF_4
→
End of Saturday minute timer period 4
0
0
59
R/W
9112
TYPE_OF_HARDWARE
0=1 digital output, 3 analogue outputs
1=2 digital outputs, 2 analogue outputs
2=3 digital outputs, 1 analogue output
3=3 digital outputs, 2 analogue outputs
4=5 digital outputs
H01
0
4
R
9113
RTC_PRESENCE
0=not present
1=present
H02
0
1
R
9114
IR_PRESENCE
0=not present
1=present
H03
0
1
R
9115
HUM_PRESENCE
0=not present
1=present
H04
0
1
R
9116
TYPE_COMMUNICATION
0=not present
1=MODBUS
H05
0
1
R
9117
TYPE_SENSOR_REG
→
type of control sensor
0=control with room sensor
1=control with supply sensor
001
0
0
1
R/W
9118
TYPE_HEATING_COIL
→
type of heating battery
0=no heating battery
1=modulating electrical resistance
2=modulating valve
3=on/off electrical resistance
4=on/off valve
002
0
0
4
R/W
9119
TYPE_COOLING_COIL
→
type of cooling battery
0=no cooling battery
1=modulating valve
2=on/off valve
003
0
0
2
R/W
9120
TYPE_POST_HEATING_COIL
→
type of post-heating battery
0=no post-heating battery
1=modulating electrical resistance
2=modulating valve
3=on/off electrical resistance
4=on/off valve
004
0
0
4
R/W
9121
FUNC_POST_HEATING_COIL
→
Post-heating battery operation
0=post-heating
1=integration and post-heating
2=additional heating battery
005
0
0
2
R/W
9122
TYPE_HUMIDIFICATOR
→
Type of humidifier battery
0=no humidifier battery
1=modulating
2=on/off
006
0
0
2
R/W
9123
TYPE_DEHUMIDIFICATOR
→
Type of dehumidifier battery
0=cooling battery
1=modulating
2=on/off
007
0
0
2
R/W
9124
TYPE_VENTILATOR
→
Type of fan
0=non-controlled fan
1=single-speed on/off fan
2=two-speed on/off fan
3=three-speed on/off fan
4=modulating fan
008
0
0
4
R/W
9125
REG_TYPE_VENTILATOR
→
Type of fan control
0=manual
1=control based on
CO
2
2=controlled based on temperature
3=controlled based on on/off temperature
4=controlled based on temp
CO
2
5=controlled based on pressure (direct action)
6=controlled based on pressure (reverse action)
7=controlled based on dehumidification
009
0
0
7
R/W