Parameter
Logic
015
=12 (
Input DI1
) or
017
=12 (
Input DI2
)
Stop all alarm
Logic DI1
016
=
Logic DI2
018
=
0
1
No stop all alarm
Stop all alarm
015
=13 (
Input DI1
) or
017
=13 (
Input DI2
)
Fan alarm
Logic DI1
016
=
Logic DI2
018
=
0
1
No fan alarm
Fan alarm
015
=14 (
Input DI1
) or
017
=14 (
Input DI2
)
Frost protection
heat exchanger
alarm
Logic DI1
016
=
Logic DI2
018
=
0
1
No frost protection
heat
exchanger
Frost protection
heat ex
-
changer