32/160
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
180
: proportional post-heating band
If Tsup <
179
-
180
post-heating or the additional heating stage is activated, the
(or
) icon is displayed if the post-heating
is a valve (or electrical resistance). If Tsup >=
179
post-heating (or the additional heating stage) is deactivated. The
(or
)
icon switches off if the post-heating or the additional heating is a valve (or electrical resistance) and if the heating stage is also
deactivated.
• Modulating integration operation:
- integrational stage with valve:
004
=2 and
030
=7 (AO1) or
031
=7 (AO2) or
032
=7 (AO3).
- integrational stage with electrical resistance:
004
=1 and
030
=8 (AO1) or
031
=8 (AO2) or
032
=8 (AO3).
100%
0%
Tsup
180
179
100%
0%
Treg
180
WHS
100%
0%
Treg
180
WHS
100%
0%
Tsup
180
179
Treg: control temperature
WHS: heating control setpoint
180
: proportional post-heating band
During control, the
(or
) icon is displayed if the signal applied to the valve (or the modulating resistance) in integration is
not equal to 0: Tsup<WHS.
The
(or
) icon switches off if the signal applied to the valve (or the modulating resistance) in integration is equal to 0
(Tsup>=WHS) and if the heating stage is also deactivated.
• Integration on/off operations:
- integration stage with valve:
004
=4 and
025
=8 (DO1) or
026
=8 (DO2) or
027
=8 (DO3) or
028
=8 (DO4) or
029
=8 (DO5).
- integration stage with electrical resistance:
004
=3 and
025
=9 (DO1) or
026
=9 (DO2) or
027
=9 (DO3) or
028
=9 (DO4) or
029
=9 (DO5).
100%
0%
Tsup
180
179
100%
0%
Treg
180
WHS
100%
0%
Treg
180
WHS
100%
0%
Tsup
180
179
Treg: control temperature
WHS: heating control setpoint
180
: proportional post-heating band
If Treg < WHS -
180
the heating integration stage is activated, the
(or
) icon is displayed if the integration is a valve
(or electrical resistance).
If Treg >= WHS the heating integration stage is disabled. The
(or
) icon switches off if the integration is a valve (or
electrical resistance) and if the heating stage is also disabled.