37
Table 4.1 Customer-supplied equipment and services
Item
Purpose
Restrictions
a
Lock
Supports restricted access to
the unit's interior.
Suitable for the installation location.
a
All customer-supplied equipment, tools, and services must comply with and be used in ways that meet any restrictions imposed by the
hazardous-classified area; local, state, or national codes, regulations, standards, permits, or other requirements; and the AHJ.
b
Ensure a minimum distance of 5 m (16 ' 4
″
) between a unit and its optional power-supply accessory from Industrial Scientific, or any that
are in use nearby.
Site Selection
Choose an operation location (site) that is in compliance with the product's
certified use restrictions
and
product specifications.
Ensure the site also supports the following.
x
The unit is hinged on its left side and is opened from right to left. Avoid locations that that block this
movement.
x
If the RGX will be used with a compatible power-supply accessory from Industrial Scientific (ISERTPS
or ERTPS), ensure the site allows sufficient space for the RGX and its Intrinsic Safety (IS) Cable
Adapter, which extends down 62.2 cm (24.5
″
) from IS power port on the left side of the RGX. Ensure
the ISERTPS and ERTPS are installed and used in accordance with the instruction provided in their
respective product manuals.
x
If the RGX will be used with the ISERTPS or ERTPS power-supply accessory, maintain a minimum
distance of 5 m (16 ' 4
″
) between the RGX and the accessory or any nearby ISERTPS or ERTPS
accessories (see Figure 4.1 below). This allows the RGX to be operated in a manner designed to
prevent radio frequency interference per FCC (Federal Communications Commission) requirements.
x
If the RGX will be connected to a compatible customer-supplied, customer-installed fixed DC power
source, Ethernet cable, or both, ensure the site will accommodate the length of the intended conduit.
x
To support the unit's wireless performance (Wi-Fi and LENS Wireless), ensure its placement or
installation allows for a minimum distance of 1 m (3 ' 3
″
) between the bottom of the unit and the
ground.
x
If the unit will use cellular, Wi-Fi, or both of these communication methods, ensure the site serves any
connection-range requirements of those services and is not shielded.
x
To achieve best performance for a unit that will use GPS, cellular communication, or both, ensure the
site provides large, open-sky access and allows the unit to be mounted or placed using a vertical
orientation, its handle toward the sky. Units used in an indoor environment
cannot
receive the signal
required for GPS functionality.
x
Ensure the unit and any cable or cord connections are situated away from standing water.
Document Number: 0000037533
DO NOT CHANGE WITHOUT THE FOLLOWING AGENCY APPROVALS(S):N/A
Modified: 2018-05-25 13:18:14 EDT
State:In Work
INDUSTRIAL SCIENTIFIC CORPORATION
Title: PRODUCT MANUAL RGX GATEWAY-EN-1
Eng:
Drawing No: 17158071-1
Drawn By: Gaygan, Nancy
Created: 2018-05-16 10:24:51 EDT
Rev: 1
Printed By: Kuzmich, Bob
Int: 1.5
Date:May 29, 2018