NetTEST II Menu Guide
©
COMSOFT
21
5.2.1.7 Slave signal quality
Figure 13:
Screen ‘Slave signal quality’
With the
Slave signal quality,
the signal level of the addressed
DP Slave is measured. This should be with an impeccable unit
and correctly terminated bus and a cable length of 1 m from
the measuring point to the Slave at approx. 6.3 Volt. Per
100 m more cable between
NetTEST II
and the device to be
scanned, the level reduces by approx. 0.2 Volt.
U < 2.5 V:
Weak level or no longer detectable.
2.5 - 7.2 V:
Level is ok.
U > 7.2 V:
If the indicated level is >7.2 Volt, this is an
indication for a faulty power supply of the
Slaves or for reflections at the bus.