MICROCOM
®
TEMPERATURE CONTROLLER
INSTRUCTION MANUAL
Pg.
www.incoe.com
©INCOE
®
CORPORATION 4/2010
When temperature reaches setpoint, the ramp is
complete. Its duration depends on the variation
between setpoint and temperature and on the
increase per minute selected.
While the ramp is operating, it is possible
to modify the setpoint, which allows for
adjustments whether the temperature is below or
above the setpoint.
Example :
Initial temperature is 70°F, setpoint is 430°F, Rate
Ramp is 60°F/min.
The ramp will last 6 minutes, because (430 - 70) /
60 = 6 steps of 60°.
Navigation via “Click & Rotate” switch:
If “Increase” display
If “Decrease” display
If “Selected” (Push 2 seconds):
It is possible to modify the
parameter value. Value in °F/
min or °C/min.
2.6.2 CONFIGURATION 2 MENU:
The configuration 2 menu is as follows.
Temperature unit:
This parameter allows for the selection of the
temperature unit, in either °F or °C.
Navigation via “Click & Rotate” switch:
If “Increase” display
If “Decrease”display
If “Selected” (Push 2 seconds):
It is possible to modify the
parameter value. Value in
°F or °C.
Thermocouple type:
Parameter allows the selection of the type of
thermocouple used. Either a type J, or type K
(displayed as “nl”). The default thermocouple
is a J type.
Navigation via “Click & Rotate” switch:
If “Increase” display
If “Decrease” display
If “Selected” (Push 2 seconds):
It is possible to modify the
parameter value.
J Thermocouple / K
thermocouple
(displayed as “nI”).
Select type of output:
This parameter allows to select the type of output
power, either Phase Angle mode (PhA), or Zero
Crossing mode (0Cr). This selection is only valid
during the control phase. During the SoftStart
phase, the controller works in Phase Angle mode.
Navigation via “Click & Rotate” switch:
If “Increase” display
If “Decrease” display
If “Selected” (Push 2
seconds): It is possible to
modify the parameter value.
Value in Phase angle (Pha) or
in zero crossing (0Cr).
Operating mode if thermocouple fault:
The percentage of power is saved in memory
during the control phase, when in steady state.
(temperature stable at +/- 3° around setpoint, for
at least 2 minutes).
2
OPERATION
9