6.1.5 Low Limit (Only With DCP Installed)
The operation of the Low Limit, available only with a pressure
module installed, is identical to the High Limit except this value sets
the pressure where the cleaning cycle will end. The upper setable
value is the calibration pressure of the pressure module and the
lower limit is zero. Pressing “SELECT” will change the system to the
High Alarm Setup mode.
6.1.6 High Alarm (Only With DCP Installed)
The operation of the High Alarm Setup is identical to the High and Low
Limit Setup and is only available when a pressure module is installed.
The High Alarm default is 0. The upper setable value is the full scale
pressure of the pressure module and the lower limit is zero. Pressing
“SELECT” will change the system to the Low Alarm Setup mode.
6.1.7 Low Alarm (Only With DCP Installed)
The operation of the Low Alarm Setup is identical to the High and
Low Limit Setup. The Low Alarm default is “0”. The upper setable
value is the full scale pressure of the pressure module and the lower
limit is zero. Pressing “SELECT” will change the system to the Cycle
Delay Setup mode.
6.1.8 Cycle Delay (min)
The cycle delay inserts a delay time between the end of the last
channel and the beginning of the first channel. This may be set to
between zero and 255 minutes. The factory default is zero. Setting
the value to zero will disable the delay. Pressing “SELECT” will
change the system to the Down Time Cycles Setup mode.
6.1.9 Down Time Cycles (min)
The Down Time Cycles Setup will select a value between zero and 255
minutes. The factory default is one minute. Selecting zero will
disable the operation. When the Down Time Cycles is activated by
shorting the down time cycles input to the common terminal, the
system will enter a forced cleaning mode for the programmed
duration. NOTE: The cycle delay, if one is programmed, will not be
inserted in the timing cycle. Pressing “SELECT” will change the
system to the Auto Alarm Reset Setup mode, if a pressure module is
installed, or to Process when no pressure module is available.
6.1.10 Auto Alarm Reset (sec) (Only With DCP Installed)
The Auto Alarm Reset Setup, available only when a pressure module
is installed, allows the auto alarm reset time to be selected. This
value may be set between zero and 255 seconds. The factory default
value is five seconds. When the auto alarm reset is enabled by
shorting the auto alarm reset terminal to a common terminal, the
alarm will be reset after the pressure returns to the normal range
and the timeout has expired. Pressing “SELECT” will change the
system to Process mode.
6.2 MAINTENANCE SUPPORT AND DIAGNOSTICS
We have also included a number of features that will aid
maintenance personnel in diagnosing problems or verifying that the
system is operating.
Содержание CMAXX
Страница 9: ...imperialsystemsinc com 9 Imperial Systems Inc 3 Safety Labels...
Страница 24: ...imperialsystemsinc com 24 Imperial Systems Inc 11 ELECTRICAL 11 1 SOLENOID SCHEMATIC...
Страница 25: ...imperialsystemsinc com 25 Imperial Systems Inc 11 2 DCT1000 SCHEMATIC...
Страница 26: ...imperialsystemsinc com 26 Imperial Systems Inc 11 3 SOLENOID HEATER SCHEMATIC OPTIONAL...
Страница 27: ...imperialsystemsinc com 27 Imperial Systems Inc 11 4 INTEGRATED CONTROLS WIRING DIAGRAM...
Страница 28: ...MADE IN THE USA 8 0 0 9 1 8 3 0 1 3 i m p e r i a l s y s t e m s i n c c o m...