Parity selection 

• Selects the parity. 

• Not available when the option C5 is not added or when IMO 

  protocol is selected in the Communication protocol selection. 
• No parity: 

,  Even parity: 

,  Odd parity: 

 

Even parity 

 

Stop bit selection 

• Selects the stop bit. 

• Not available when option C5 is not added or when IMO 

  protocol is selected in the Communication protocol selection. 

• Setting range: 1, 2 

5.5 Auxiliary function setting mode 2 

Character 

Name, Function, Setting range 

Default value 

Input type selection 

• The input type can be selected from thermocouple (10 types), 

  RTD (2 types), DC current (2 types) and DC voltage (4 types), 

and the unit  /   can be selected as well. 

• When changing the input from DC voltage to other inputs,   

remove the sensor connected to this controller first, then change 

for the input. If the input is changed with the sensor connected, 

the input circuit may be broken. 

K  
(–200 to 1370 ) 
 
 

 

–200 to 1370 :         

–199.9 to 400.0 :   

 

–200 to 1000  :         

0 to 1760  :         

0 to 1760  :         

0 to 1820  :         

–200 to 800    :         

–199.9 to 400.0 :   

 

–200 to 1300  :         

PL-  

0 to 1390  : 

 

C (W/Re5-26) 

0 to 2315  :         

Pt100 

–199.9 to 850.0 : 

 

JPt100 

–199.9 to 500.0 : 

 

Pt100 

–200 to 850  : 

     

JPt100       –200 to 500  : 

 

4 to 20mA 

–1999 to 9999: 

 

0 to 20mA 

–1999 to 9999: 

 

0 to 1V 

–1999 to 9999:     

 

0 to 5V       

–1999 to 9999:     

 

1 to 5V          –1999 to 9999:     

 

0 to 10V       

–1999 to 9999: 

 

–320 to 2500  :         

 

–199.9 to 750.0 :   

 

–320 to 1800  :         

0 to 3200  :         

0 to 3200  :         

0 to 3300  :         

–320 to 1500  :         

T          –199.9 to 750.0 :   

 

–320 to 2300  :         

PL-  

0 to 2500  : 

 

C (W/Re5-26)  0 to 4200  :         

Pt100 

–199.9 to 999.9 : 

 

JPt100 

–199.9 to 900.0 : 

 

Pt100 

–300 to 1500 : 

     

JPt100 

–300 to 900  : 

 

 

Scaling high limit setting 

• Sets scaling high limit value. 

• Available only for DC inputs 

• Setting range: Scaling low limit value to input range high limit value 

9999 

 

Scaling low limit setting 

• Sets scaling low limit value. 

• Available only for DC inputs 

• Setting range: Input range low limit value to scaling high limit value 

–1999 

 

Decimal point place selection 

• Selects decimal point place. 

• Available only for DC inputs 
• 

No decimal point

       

1 digit after decimal point: 

 

2 digits after decimal point

 

3 digits after decimal point

:

 

 

No decimal 
point 
 

 

PV filter time constant setting 

• Sets PV filter time constant. (If the value is set too large, it 

affects control result due to the delay of response) 

• Setting range: 0.0 to 10.0 seconds 

0.0 seconds 

 

OUT1 high limit setting 

• Sets the high limit value of OUT1. 

• 

Not available when OUT1 is ON/OFF action 

• Setting range: OUT1 low limit value to 105% 

(Setting greater than 100% is effective to DC current output type) 

100% 

Содержание TP40A

Страница 1: ...it might deform or tarnish the unit As the display section is vulnerable do not strike or scratch it with a hard object Any unauthorized transfer or copying of this document in part or in whole is pr...

Страница 2: ...key the setting value or selected value can be registered 14 OUT OFF key The control output ON OFF function or Auto Manual control function can be switched To cancel the control output ON OFF function...

Страница 3: ...unting Mount the controller vertically to fulfill the Dust proof Drip proof specification IP66 Mountable panel thickness Within 1 to 15mm Insert the controller from the front side of the panel Attach...

Страница 4: ...uilt in power switch circuit breaker or fuse Therefore it is necessary to install them in the circuit near the external controller Recommended fuse Time lag fuse rated voltage 250V AC rated current 2A...

Страница 5: ...he input range high limit value is indicated on the SV display for approximately 3 seconds Table 5 1 If any other value is set during the scaling high limit setting the set value is indicated on the S...

Страница 6: ...OUT1 high limit setting A1 action delayed timer setting OUT1 proportional cycle setting Data transfer rate selection OUT1 low limit setting A2 action delayed timer setting OUT2 proportional cycle sett...

Страница 7: ...Not available when OUT1 is ON OFF action Auto reset can be performed when PD action I 0 Setting range 0 to 1000 seconds 200 seconds Derivative time setting Sets derivative time for OUT1 Setting the va...

Страница 8: ...ds on the designation When Lock 1 or Lock 2 is designated PID Auto tuning and Auto reset cannot be carried out Unlock Unlock All setting values can be changed Lock 1 None of the setting values can be...

Страница 9: ...0 4 to 20mA 1999 to 9999 0 to 20mA 1999 to 9999 0 to 1V 1999 to 9999 0 to 5V 1999 to 9999 1 to 5V 1999 to 9999 0 to 10V 1999 to 9999 K 320 to 2500 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200...

Страница 10: ...to 100 0 or 1 to 1000 0 OUT2 ON OFF action hysteresis setting Sets ON OFF action hysteresis for OUT2 Available only when the option DT is added Setting range 0 1 to 100 0 or 1 to 1000 1 0 A1 action se...

Страница 11: ...is overscale or underscale Available only for DC current output type with DC inputs Output OFF Output ON Output OFF OUT OFF key function selection Selects whether OUT OFF key is used for control outp...

Страница 12: ...of the unused instrument of the plural units OFF even if the power to the instrument is supplied is indicated on the PV display while the function is working Once the control output OFF function is en...

Страница 13: ...dby High Low limit alarm with standby Low limit alarm with standby OFF ON A1 hysteresis OFF ON SV setting OFF ON A1 hysteresis OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Alarm action Alarm action Alarm...

Страница 14: ...or OFF unlit Represents Heating control action Represents Cooling control action 7 6 OUT2 Heating Cooling control action When setting Dead band Changes continuously according to deviation Non contact...

Страница 15: ...the temperature rises When AT bias is set to 20 fluctuation is applied at the temperature 20 lower than the setting value 15 1 2 3 4 Temperature Setting value 1 Calculating PID constant 2 PID constant...

Страница 16: ...reater Allowable input voltage 15V or less Allowable signal source resistance 100 or less OUT1 output Relay contact 1a Control capacity 3A 250V AC resistive load 1A 250V AC inductive load cos 0 4 Elec...

Страница 17: ...370 to 1850 370 to 1850 0 to 1760 50 to 1810 50 to 1810 R S 0 to 3200 50 to 3250 50 to 3250 0 to 1820 50 to 1870 50 to 1870 B 0 to 3300 50 to 3350 50 to 3350 200 to 800 250 to 850 250 to 850 E 320 to...

Страница 18: ...breaking status on the loop such as heater burnout sensor burnout or actuator trouble The output terminals will be common if the options W and A2 are applied together Setting range Loop break alarm ac...

Страница 19: ...e the function is blinking on the PV display Thermocouple RTD or DC voltage 0 to 1V DC is burnt out Change each sensor How to check sensor burnout Thermocouple If the input terminal of the instrument...

Страница 20: ...nterference or noise away from the controller The PV display is indicating Internal memory is defective Contact our agency or us 10 2 Key operation Problem Presumed cause and solution Unable to set th...

Отзывы: