Parity selection
• Selects the parity.
• Not available when the option C5 is not added or when IMO
protocol is selected in the Communication protocol selection.
• No parity:
, Even parity:
, Odd parity:
Even parity
Stop bit selection
• Selects the stop bit.
• Not available when option C5 is not added or when IMO
protocol is selected in the Communication protocol selection.
• Setting range: 1, 2
1
5.5 Auxiliary function setting mode 2
Character
Name, Function, Setting range
Default value
Input type selection
• The input type can be selected from thermocouple (10 types),
RTD (2 types), DC current (2 types) and DC voltage (4 types),
and the unit / can be selected as well.
• When changing the input from DC voltage to other inputs,
remove the sensor connected to this controller first, then change
for the input. If the input is changed with the sensor connected,
the input circuit may be broken.
K
(–200 to 1370 )
K
–200 to 1370 :
–199.9 to 400.0 :
J
–200 to 1000 :
R
0 to 1760 :
S
0 to 1760 :
B
0 to 1820 :
E
–200 to 800 :
T
–199.9 to 400.0 :
N
–200 to 1300 :
PL-
0 to 1390 :
C (W/Re5-26)
0 to 2315 :
Pt100
–199.9 to 850.0 :
JPt100
–199.9 to 500.0 :
Pt100
–200 to 850 :
JPt100 –200 to 500 :
4 to 20mA
–1999 to 9999:
0 to 20mA
–1999 to 9999:
0 to 1V
–1999 to 9999:
0 to 5V
–1999 to 9999:
1 to 5V –1999 to 9999:
0 to 10V
–1999 to 9999:
K
–320 to 2500 :
–199.9 to 750.0 :
J
–320 to 1800 :
R
0 to 3200 :
S
0 to 3200 :
B
0 to 3300 :
E
–320 to 1500 :
T –199.9 to 750.0 :
N
–320 to 2300 :
PL-
0 to 2500 :
C (W/Re5-26) 0 to 4200 :
Pt100
–199.9 to 999.9 :
JPt100
–199.9 to 900.0 :
Pt100
–300 to 1500 :
JPt100
–300 to 900 :
Scaling high limit setting
• Sets scaling high limit value.
• Available only for DC inputs
• Setting range: Scaling low limit value to input range high limit value
9999
Scaling low limit setting
• Sets scaling low limit value.
• Available only for DC inputs
• Setting range: Input range low limit value to scaling high limit value
–1999
Decimal point place selection
• Selects decimal point place.
• Available only for DC inputs
•
No decimal point
:
1 digit after decimal point:
2 digits after decimal point
:
3 digits after decimal point
:
No decimal
point
PV filter time constant setting
• Sets PV filter time constant. (If the value is set too large, it
affects control result due to the delay of response)
• Setting range: 0.0 to 10.0 seconds
0.0 seconds
OUT1 high limit setting
• Sets the high limit value of OUT1.
•
Not available when OUT1 is ON/OFF action
• Setting range: OUT1 low limit value to 105%
(Setting greater than 100% is effective to DC current output type)
100%
9