IMO TP40A Скачать руководство пользователя страница 2

2. Name and functions of the sections 

                                                                                 (1) 

PV display

: Indicates the input value with a red LED. 

                                                                                 (2) 

SV display

: Indicates the setting value with a green LED. 

                                                                                 (3) 

SV1 indicator

: A green LED lights up when SV1 is indicated 

 

on the SV display. 

 

(4) 

SV2 indicator

: A yellow LED lights up when SV2 is indicated 

 

on the SV display.

 

                                                                                 (5) 

OUT1 indicator

: When OUT1 or heating output is ON,   

 

a green LED lights up. (For A/      type,   

 

it blinks corresponding to the manipulated

 

 

variable in

 a 

0.25 second

 

cycle)

 

 

 (6) 

OUT2 indicator

: When OUT2 (option DT) is ON, a yellow   

 

LED lights up. 

                                             

(7) 

A1 indicator 

: When A1 output is ON, a red LED lights up.

 

                                                                 (8) 

EVT indicator

: When Event output (option: A2, LA or W)   

 

is ON, a red LED lights up. 

  

(9) 

AT indicator 

: When auto-tuning or auto-reset is being 

(10)

 

(1)

 

(2)

 

(3)

 

(5)

 

(7)

 

(8)

 

(9)

 

(11)

 

(12)

 

(13)

 

(14)

 

(4)

 

TP40

TP40A 

(6)

 

 

(Fig. 2-1)                               

performed, a yellow LED blinks. 

 (10) 

TX/RX indicator

: A yellow LED blinks during serial communication output (transmitting). 

(11) 

Increase key

  : Increases the numeric value. 

(12) 

Decrease key

 : Decreases the numeric value. 

(13) 

Mode key

 

: Selects the setting mode or registers the setting value. 

 

(By pressing the Mode key, the setting value or selected value can be registered) 

(14) 

OUT/OFF key

  : The control output ON/OFF function or Auto/Manual control function can be 

 

  switched. (To cancel the control output ON/OFF function, press the OUT/OFF key 

 

again for approx. 1 second.) 

 

Notice

 

When setting the specifications and functions of this controller, connect the terminals 1 and 2 for power 
source first, then set them referring to “5. Setup” before performing “3. Mounting to control panel” and 
“4. Wiring connection”. 

 

3. Mounting to control panel 

3.1 Site selection 

This instrument is intended to be used under the following environmental conditions 
(IEC61010-1): Overvoltage category  , Pollution degree 2 

 

Mount the controller in a place with: 

• 

A minimum of dust, and an absence of corrosive gases 

 No flammable, explosive gasses 

 

• 

Few mechanical vibrations or shocks 

 

• 

No exposure to direct sunlight, an ambient temperature of 0 to 50   (32 to 122 ) 

that does not change rapidly 

 

• 

An ambient non-condensing humidity of 35 to 85%RH 

 

• 

No large capacity electromagnetic switches or cables through which large current is flowing 

 

• 

No water, oil or chemicals or where the vapors of these substances can come into direct 

contact with the controller 
 

3.2 External dimension 

 

Screw type mounting bracket

 

Gasket

 

59

7

44

5

95

 

11.5

48

 

 

 

 

 

 

 

 
                                                               (Fig.  3.2-1) 

Содержание TP40A

Страница 1: ...it might deform or tarnish the unit As the display section is vulnerable do not strike or scratch it with a hard object Any unauthorized transfer or copying of this document in part or in whole is pr...

Страница 2: ...key the setting value or selected value can be registered 14 OUT OFF key The control output ON OFF function or Auto Manual control function can be switched To cancel the control output ON OFF function...

Страница 3: ...unting Mount the controller vertically to fulfill the Dust proof Drip proof specification IP66 Mountable panel thickness Within 1 to 15mm Insert the controller from the front side of the panel Attach...

Страница 4: ...uilt in power switch circuit breaker or fuse Therefore it is necessary to install them in the circuit near the external controller Recommended fuse Time lag fuse rated voltage 250V AC rated current 2A...

Страница 5: ...he input range high limit value is indicated on the SV display for approximately 3 seconds Table 5 1 If any other value is set during the scaling high limit setting the set value is indicated on the S...

Страница 6: ...OUT1 high limit setting A1 action delayed timer setting OUT1 proportional cycle setting Data transfer rate selection OUT1 low limit setting A2 action delayed timer setting OUT2 proportional cycle sett...

Страница 7: ...Not available when OUT1 is ON OFF action Auto reset can be performed when PD action I 0 Setting range 0 to 1000 seconds 200 seconds Derivative time setting Sets derivative time for OUT1 Setting the va...

Страница 8: ...ds on the designation When Lock 1 or Lock 2 is designated PID Auto tuning and Auto reset cannot be carried out Unlock Unlock All setting values can be changed Lock 1 None of the setting values can be...

Страница 9: ...0 4 to 20mA 1999 to 9999 0 to 20mA 1999 to 9999 0 to 1V 1999 to 9999 0 to 5V 1999 to 9999 1 to 5V 1999 to 9999 0 to 10V 1999 to 9999 K 320 to 2500 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200...

Страница 10: ...to 100 0 or 1 to 1000 0 OUT2 ON OFF action hysteresis setting Sets ON OFF action hysteresis for OUT2 Available only when the option DT is added Setting range 0 1 to 100 0 or 1 to 1000 1 0 A1 action se...

Страница 11: ...is overscale or underscale Available only for DC current output type with DC inputs Output OFF Output ON Output OFF OUT OFF key function selection Selects whether OUT OFF key is used for control outp...

Страница 12: ...of the unused instrument of the plural units OFF even if the power to the instrument is supplied is indicated on the PV display while the function is working Once the control output OFF function is en...

Страница 13: ...dby High Low limit alarm with standby Low limit alarm with standby OFF ON A1 hysteresis OFF ON SV setting OFF ON A1 hysteresis OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Alarm action Alarm action Alarm...

Страница 14: ...or OFF unlit Represents Heating control action Represents Cooling control action 7 6 OUT2 Heating Cooling control action When setting Dead band Changes continuously according to deviation Non contact...

Страница 15: ...the temperature rises When AT bias is set to 20 fluctuation is applied at the temperature 20 lower than the setting value 15 1 2 3 4 Temperature Setting value 1 Calculating PID constant 2 PID constant...

Страница 16: ...reater Allowable input voltage 15V or less Allowable signal source resistance 100 or less OUT1 output Relay contact 1a Control capacity 3A 250V AC resistive load 1A 250V AC inductive load cos 0 4 Elec...

Страница 17: ...370 to 1850 370 to 1850 0 to 1760 50 to 1810 50 to 1810 R S 0 to 3200 50 to 3250 50 to 3250 0 to 1820 50 to 1870 50 to 1870 B 0 to 3300 50 to 3350 50 to 3350 200 to 800 250 to 850 250 to 850 E 320 to...

Страница 18: ...breaking status on the loop such as heater burnout sensor burnout or actuator trouble The output terminals will be common if the options W and A2 are applied together Setting range Loop break alarm ac...

Страница 19: ...e the function is blinking on the PV display Thermocouple RTD or DC voltage 0 to 1V DC is burnt out Change each sensor How to check sensor burnout Thermocouple If the input terminal of the instrument...

Страница 20: ...nterference or noise away from the controller The PV display is indicating Internal memory is defective Contact our agency or us 10 2 Key operation Problem Presumed cause and solution Unable to set th...

Отзывы: