Wire them properly. 

The PV display keeps indicating 
the value which was set in the 
Scaling low limit setting. 
 

• Check if the input signal source for DC voltage (0 to 5V DC,   

0 to 10V DC) and DC current (0 to 20mA DC) is normal. 

How to check each signal wire

 

[DC voltage (0 to 5V DC, 0 to 10V DC)] 

If the input to the input terminals of the instrument is 1V DC and   

if the value corresponding to 1V DC is indicated, the instrument     

should be normal and the signal wire may be disconnected. 

[DC current (0 to 20mA DC)] 

If the input to the input terminals of the instrument is 1mA DC and 

if the value corresponding to 1mA DC is indicated, the instrument   

should be normal and the signal wire may be disconnected. 

• Are the input lead wire terminals for DC voltage (0 to 5V DC, 0 to   

10V DC) or DC current (0 to 20mA DC) securely mounted to the 
instrument input terminals? 

Mount the sensor terminals to the instrument input terminals securely. 

The indication of PV display is 
abnormal or unstable. 

• Is sensor input or temperature unit (  or  ) correct? 

Select the proper sensor input and temperature unit (  or  ). 

• Sensor correcting value is unsuitable. Set the value suitably. 
• Is the specification of the sensor correct? 
    Set the sensor to the proper specification. 
• AC leaks into the sensor circuit. Use an ungrounded type sensor. 
• There may be a piece of equipment producing inductive 

interference or noise near the controller. 
Keep the equipment producing inductive interference or noise 
away from the controller. 

The PV display is indicating   
[

]. 

• Internal memory is defective. 

  Contact our agency or us. 

10.2 Key operation 

Problem 

Presumed cause and solution 

• Unable to set the SV, P, I, D, 

proportional cycle or alarm 
setting  

• The values do not change by   

,     key operation. 

• Setting value lock (Lock 1 or Lock 2) is designated. 

Release the lock designation. 

• During PID auto-tuning or auto-reset. 

In the case of PID auto-tuning, cancel the auto-tuning. 
It takes approximately 4 minutes 

until auto

-reset is finished. 

The setting indication does not 
change in the input range even if 
the    ,     keys are pressed, 
and unable to set the value. 

• SV high or low limit value in Auxiliary function setting mode 1 may 

be set at the point the value does not change. 
Set the proper value while in the Auxiliary function setting 
mode 1. 

10.3 Control 

Problem 

Presumed cause and solution 

Temperature does not rise. 

• Sensor is out of order. 

Replace 

the sensor. 

• Sensor or control output terminals are not securely mounted to 

the instrument input terminals. 

  Mount the sensor or control output terminals to the instrument 

input terminals securely. 

• The wiring of sensor or control output terminals is incorrect. 

Connect it properly. 

The control output remains   

ON status. 

• OUT1 or OUT2 low limit value is set to 100% or greater 

in Auxiliary function setting mode 2. 

Set the value appropriately. 

The control output remains   

OFF status. 

• OUT1 or OUT2 high limit value is set to 0% or less in   

Auxiliary function setting mode 2. 

Set the value appropriately. 

• If you have any inquiries, please consult our agency or the shop where you purchased the unit. 

 
 
 
 
 
 
 
 

 

20 

Содержание TP40A

Страница 1: ...it might deform or tarnish the unit As the display section is vulnerable do not strike or scratch it with a hard object Any unauthorized transfer or copying of this document in part or in whole is pr...

Страница 2: ...key the setting value or selected value can be registered 14 OUT OFF key The control output ON OFF function or Auto Manual control function can be switched To cancel the control output ON OFF function...

Страница 3: ...unting Mount the controller vertically to fulfill the Dust proof Drip proof specification IP66 Mountable panel thickness Within 1 to 15mm Insert the controller from the front side of the panel Attach...

Страница 4: ...uilt in power switch circuit breaker or fuse Therefore it is necessary to install them in the circuit near the external controller Recommended fuse Time lag fuse rated voltage 250V AC rated current 2A...

Страница 5: ...he input range high limit value is indicated on the SV display for approximately 3 seconds Table 5 1 If any other value is set during the scaling high limit setting the set value is indicated on the S...

Страница 6: ...OUT1 high limit setting A1 action delayed timer setting OUT1 proportional cycle setting Data transfer rate selection OUT1 low limit setting A2 action delayed timer setting OUT2 proportional cycle sett...

Страница 7: ...Not available when OUT1 is ON OFF action Auto reset can be performed when PD action I 0 Setting range 0 to 1000 seconds 200 seconds Derivative time setting Sets derivative time for OUT1 Setting the va...

Страница 8: ...ds on the designation When Lock 1 or Lock 2 is designated PID Auto tuning and Auto reset cannot be carried out Unlock Unlock All setting values can be changed Lock 1 None of the setting values can be...

Страница 9: ...0 4 to 20mA 1999 to 9999 0 to 20mA 1999 to 9999 0 to 1V 1999 to 9999 0 to 5V 1999 to 9999 1 to 5V 1999 to 9999 0 to 10V 1999 to 9999 K 320 to 2500 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200...

Страница 10: ...to 100 0 or 1 to 1000 0 OUT2 ON OFF action hysteresis setting Sets ON OFF action hysteresis for OUT2 Available only when the option DT is added Setting range 0 1 to 100 0 or 1 to 1000 1 0 A1 action se...

Страница 11: ...is overscale or underscale Available only for DC current output type with DC inputs Output OFF Output ON Output OFF OUT OFF key function selection Selects whether OUT OFF key is used for control outp...

Страница 12: ...of the unused instrument of the plural units OFF even if the power to the instrument is supplied is indicated on the PV display while the function is working Once the control output OFF function is en...

Страница 13: ...dby High Low limit alarm with standby Low limit alarm with standby OFF ON A1 hysteresis OFF ON SV setting OFF ON A1 hysteresis OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Alarm action Alarm action Alarm...

Страница 14: ...or OFF unlit Represents Heating control action Represents Cooling control action 7 6 OUT2 Heating Cooling control action When setting Dead band Changes continuously according to deviation Non contact...

Страница 15: ...the temperature rises When AT bias is set to 20 fluctuation is applied at the temperature 20 lower than the setting value 15 1 2 3 4 Temperature Setting value 1 Calculating PID constant 2 PID constant...

Страница 16: ...reater Allowable input voltage 15V or less Allowable signal source resistance 100 or less OUT1 output Relay contact 1a Control capacity 3A 250V AC resistive load 1A 250V AC inductive load cos 0 4 Elec...

Страница 17: ...370 to 1850 370 to 1850 0 to 1760 50 to 1810 50 to 1810 R S 0 to 3200 50 to 3250 50 to 3250 0 to 1820 50 to 1870 50 to 1870 B 0 to 3300 50 to 3350 50 to 3350 200 to 800 250 to 850 250 to 850 E 320 to...

Страница 18: ...breaking status on the loop such as heater burnout sensor burnout or actuator trouble The output terminals will be common if the options W and A2 are applied together Setting range Loop break alarm ac...

Страница 19: ...e the function is blinking on the PV display Thermocouple RTD or DC voltage 0 to 1V DC is burnt out Change each sensor How to check sensor burnout Thermocouple If the input terminal of the instrument...

Страница 20: ...nterference or noise away from the controller The PV display is indicating Internal memory is defective Contact our agency or us 10 2 Key operation Problem Presumed cause and solution Unable to set th...