Loop break alarm action time setting 

• 

Sets the time to assess the Loop break alarm. 

 Available only when the option LA is applied. 

 Setting range: 0 to 200 minutes

 

0 minutes 

 

Loop break alarm action span setting 

• 

Sets the temperature to assess the Loop break alarm. 

 Available only when the option LA is applied. 

• 

Setting range: 0 to 150

 

( ), 0.0 to 150.0

 

( ) or 0 to 1500

 

0  

 (Table 

5.3-1) 

Alarm action type 

Setting range 

High limit alarm 

– (Input span) to input span ( )  

*1 

Low limit alarm 

– (Input span) to input span ( )  

*1 

High/Low limits alarm 

0 to input span ( )  

*1 

High/Low limit range alarm 

0 to input span ( )  

*1 

Process high alarm 

Input range low limit value to input range high limit value *2 

Process low alarm 

Input range low limit value to input range high limit value *2 

High limit alarm with standby 

– (Input span) to input span ( )  

*1 

Low limit alarm with standby 

– (Input span) to input span ( )  

*1 

High/Low limits alarm with standby 

0 to input span ( )  

*1 

• 

When input has a decimal point, the negative low limit value is –199.9, and the positive high limit 

value is 999.9. 

• 

All alarm actions except process alarms are 

deviation setting to the main setting.   

*1: For DC input, the input span is the same as the scaling span. 

*2: For DC input, input range low (high) limit value is the same as scaling low (high) limit value. 

5.4 Auxiliary function setting mode 1 

Character 

Name, Function, Setting range 

Default value 

Setting value lock selection 

• Locks the setting values to prevent setting errors. 

The setting item to be locked depends on the designation. 

• When Lock 1 or Lock 2 is designated, PID Auto- tuning and   

Auto-reset cannot be carried out. 

Unlock 

 

• 

 (Unlock) : All setting values can be changed. 

   

  (Lock 1): None of the setting values can be changed. 

   

  (Lock 2): Only main setting value can be changed. 

   

  (Lock 3): All setting values can be changed. However, do not change the 

 

setting items in the Auxiliary function setting mode 2. They return to their former 

 

value after power is turned off because they are not saved in the non-volatile 

 

memory. It is suitable to use in combination with our programmable controller  

(with  SVTC) as this has no relation to memory life. 

 

SV high limit setting 

• Sets the SV high limit. 

• Setting range: SV low limit to input range high limit value 

or SV low limit to scaling high limit value 

Input range 
high limit value 
 

 

SV low limit setting 

• Sets the SV low limit. 

• Setting range: Input range low limit value to SV high limit 

or scaling low limit value to SV high limit   

Input range 
low limit value 
 

 

Sensor correction setting 

• Sets the correction value for the sensor. 

• Setting range: –100.0 to 100.0   ( ), or –1000 to 1000 

0.0  

 

Communication protocol selection 

• Selects communication protocol. 

• Available only when the option C5 is applied. 

• IMO protocol

Modbus ASCII mode

 

Modbus RTU mode

 

IMO protocol 

 

Instrument number setting 

• Sets the instrument number individually to each instrument when 

communicating by connecting plural instruments in serial 

communication. 

• Available only when option C5 is added. 

• Setting range: 0 to 95 

 

Data transfer rate selection 

• Selects a transfer rate to be equal to the rate of the host   

computer. 

• Available only when option [C5] is added. 
• 2400bps: 

, 4800bps: 

, 9600bps: 

, 19200bps:

 

9600bps 

Содержание TP40A

Страница 1: ...it might deform or tarnish the unit As the display section is vulnerable do not strike or scratch it with a hard object Any unauthorized transfer or copying of this document in part or in whole is pr...

Страница 2: ...key the setting value or selected value can be registered 14 OUT OFF key The control output ON OFF function or Auto Manual control function can be switched To cancel the control output ON OFF function...

Страница 3: ...unting Mount the controller vertically to fulfill the Dust proof Drip proof specification IP66 Mountable panel thickness Within 1 to 15mm Insert the controller from the front side of the panel Attach...

Страница 4: ...uilt in power switch circuit breaker or fuse Therefore it is necessary to install them in the circuit near the external controller Recommended fuse Time lag fuse rated voltage 250V AC rated current 2A...

Страница 5: ...he input range high limit value is indicated on the SV display for approximately 3 seconds Table 5 1 If any other value is set during the scaling high limit setting the set value is indicated on the S...

Страница 6: ...OUT1 high limit setting A1 action delayed timer setting OUT1 proportional cycle setting Data transfer rate selection OUT1 low limit setting A2 action delayed timer setting OUT2 proportional cycle sett...

Страница 7: ...Not available when OUT1 is ON OFF action Auto reset can be performed when PD action I 0 Setting range 0 to 1000 seconds 200 seconds Derivative time setting Sets derivative time for OUT1 Setting the va...

Страница 8: ...ds on the designation When Lock 1 or Lock 2 is designated PID Auto tuning and Auto reset cannot be carried out Unlock Unlock All setting values can be changed Lock 1 None of the setting values can be...

Страница 9: ...0 4 to 20mA 1999 to 9999 0 to 20mA 1999 to 9999 0 to 1V 1999 to 9999 0 to 5V 1999 to 9999 1 to 5V 1999 to 9999 0 to 10V 1999 to 9999 K 320 to 2500 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200...

Страница 10: ...to 100 0 or 1 to 1000 0 OUT2 ON OFF action hysteresis setting Sets ON OFF action hysteresis for OUT2 Available only when the option DT is added Setting range 0 1 to 100 0 or 1 to 1000 1 0 A1 action se...

Страница 11: ...is overscale or underscale Available only for DC current output type with DC inputs Output OFF Output ON Output OFF OUT OFF key function selection Selects whether OUT OFF key is used for control outp...

Страница 12: ...of the unused instrument of the plural units OFF even if the power to the instrument is supplied is indicated on the PV display while the function is working Once the control output OFF function is en...

Страница 13: ...dby High Low limit alarm with standby Low limit alarm with standby OFF ON A1 hysteresis OFF ON SV setting OFF ON A1 hysteresis OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Alarm action Alarm action Alarm...

Страница 14: ...or OFF unlit Represents Heating control action Represents Cooling control action 7 6 OUT2 Heating Cooling control action When setting Dead band Changes continuously according to deviation Non contact...

Страница 15: ...the temperature rises When AT bias is set to 20 fluctuation is applied at the temperature 20 lower than the setting value 15 1 2 3 4 Temperature Setting value 1 Calculating PID constant 2 PID constant...

Страница 16: ...reater Allowable input voltage 15V or less Allowable signal source resistance 100 or less OUT1 output Relay contact 1a Control capacity 3A 250V AC resistive load 1A 250V AC inductive load cos 0 4 Elec...

Страница 17: ...370 to 1850 370 to 1850 0 to 1760 50 to 1810 50 to 1810 R S 0 to 3200 50 to 3250 50 to 3250 0 to 1820 50 to 1870 50 to 1870 B 0 to 3300 50 to 3350 50 to 3350 200 to 800 250 to 850 250 to 850 E 320 to...

Страница 18: ...breaking status on the loop such as heater burnout sensor burnout or actuator trouble The output terminals will be common if the options W and A2 are applied together Setting range Loop break alarm ac...

Страница 19: ...e the function is blinking on the PV display Thermocouple RTD or DC voltage 0 to 1V DC is burnt out Change each sensor How to check sensor burnout Thermocouple If the input terminal of the instrument...

Страница 20: ...nterference or noise away from the controller The PV display is indicating Internal memory is defective Contact our agency or us 10 2 Key operation Problem Presumed cause and solution Unable to set th...

Отзывы: