ISOCON-6 USERS GUIDE
4.1.6 RTD Input:
Select the range from the table below and set Switch S1 to the required values.
Then select the required setting from the table below for switch S2
Please note that PC Software is available to provide information on switch settings for your input and output requirements.
RTD
Switch S2
1
2
3
4
5
6
7
8
9
10
11
12
2 Wire RTD
0
1
0
0
1
0
0
1
0
0
0
1
3 Wire RTD
0
1
0
0
0
0
0
0
1
0
0
1
4Wire RTD
1
0
0
0
0
0
1
0
1
0
0
ISOCON-6
24V AC or DC POWERED ISOLATING SIGNAL CONVERTER
Warning:
DO NOT OPEN UNIT OR ADJUST SWITCHES WITH POWER SUPPLY, INPUT OR OUTPUT CONNECTED
Range in °C
Switch S1
1
2
3
4
5
6
7
8
9
10 11
12
0 to 100
0
0
0
0
0
0
1
0
0
0 to 200
0
0
0
1
0
0
1
0
0
0 to 400
0
0
1
0
0
0
1
0
0
0 to 800
0
0
1
1
0
0
1
0
0
-50 to 50
0
1
0
0
0
0
1
0
0
-50 to 150
0
1
0
1
0
0
1
0
0
-50 to 250
0
1
1
0
0
0
1
0
0
-50 to 350
0
1
1
1
0
0
1
0
0
-100 to 50
1
0
0
0
0
0
1
0
0
-100 to 100
1
0
0
1
0
0
1
0
0
-100 to 200
1
0
1
0
0
0
1
0
0
-100 to 400
1
0
1
1
0
0
1
0
0
-200 to 200
1
1
0
0
0
0
1
0
0
-200 to 400
1
1
0
1
0
0
1
0
0
-200 to 600
1
1
1
0
0
0
1
0
0
-200 to 800
1
1
1
1
0
0
1
0
0
RTD linearisation ON 0
RTD linearisation off
1
RTD 2 or 4 wire
0
RTD 3 wire
1
PT1000
0
PT1000
1