ISOCON-6 USERS GUIDE
4.1.3 Millivolt (mV) Input:
Select the range from the table below and set Switch S1 to the required values.
Then select the required setting from the table below for switch S2
Please note that PC Software is available to provide information on switch settings for your input and output requirements.
mV
Range
Switch S1
1
2
3
4
5
6
7
8
9
10
11
12
0-25mV
0
0
0
0
0
0
0
1
1
1
0
0
0-50mV
0
0
0
1
0
0
0
1
1
1
0
0
0-100mV
0
0
1
0
0
0
0
1
1
1
0
0
0-125mV
0
1
0
0
0
0
0
1
1
1
0
0
0-150mV
1
0
0
0
0
0
0
1
1
1
0
0
0-200mV
0
0
1
1
0
0
0
1
1
1
0
0
0-250mV
0
1
0
1
0
0
0
1
1
1
0
0
0-300mV
1
0
0
1
0
0
0
1
1
1
0
0
0-500mV
0
1
1
0
0
0
0
1
1
1
0
0
0-600mV
1
0
1
0
0
0
0
1
1
1
0
1
0-1000mV
0
1
1
1
0
0
0
1
1
1
0
1
0-1200mV
1
0
1
1
0
0
0
1
1
1
0
1
-125 to +125mV
1
1
0
0
0
0
0
1
1
1
0
1
-125 to +1000mV
1
1
1
1
0
0
0
1
1
1
0
0
mV Range
Switch S2
1
2
3
4
5
6
7
8
9
10
11
12
All Unipolar Ranges (e.g.
0-500mV)
0
1
0
0
0
0
1
1
0
0
0
0
S2Bipolar Ranges (e.g.
-125 to +125mV)
0
1
0
0
1
0
1
0
0
0
0
0
ISOCON-6
24V AC or DC POWERED ISOLATING SIGNAL CONVERTER
Warning:
DO NOT OPEN UNIT OR ADJUST SWITCHES WITH POWER SUPPLY, INPUT OR OUTPUT CONNECTED