4.1.7 Output Configuration:
Select the range from the table below and set Switch S3 to the required values.
Examples:
Please note that PC Software is available to provide information on switch settings for your input and output requirements.
Switch S3 Examples
1
2
3
4
5
6
7
8
9
10
11
12
4-20mA Source
1
0
1
0
1
0
0
0
0
0
0
0
0-20mA Source
1
0
1
0
1
0
0
0
0
0
0
1
0-10V
1
0
1
0
1
1
0
0
0
0
0
1
4-20mA Sink
1
1
0
1
0
0
0
0
0
0
0
0
ISOCON-6
24V AC or DC POWERED ISOLATING SIGNAL CONVERTER
Warning:
DO NOT OPEN UNIT OR ADJUST SWITCHES WITH POWER SUPPLY, INPUT OR OUTPUT CONNECTED
Switch S3
1
2
3
4
5
6
7
8
9
10
11
12
0
Buttons Disabled
1
Buttons Enabled
Output value if fault on input signal
Front panel buttons can be disabled to allow
tamper-proof operation of unit
0
Normal
1
Inverted o/p
High Burnout
0
Low Burnout
1
Normal
0
Square Root
1
0
0
1
0
1
0
mA Source
1
0
1
0
0
mA Sink
0
1
0
1
1
Voltage
4-20mA
/ 2-10V
0
0
0-20mA /0-10V
0
1
0-10mA / 0-5V
1
0
2-10mA / 1-5V
1