2.6  FAULT AND ANOMALY SIGNALS.

The Victrix Superior TOP boiler signals any 

anomalies  by  the  flashing  symbol  (5)  along 

with the “ERRxx” indication on the indicator 

(6) where “xx” corresponds to the error code 

described in the following table. On any remote 

control the error code will be displayed by means 

of the same numerical code number represented 

according to the following example (e.g. CAR

V2

 

= Exx, Super CAR = ERR>xx).

Anomaly signalled

Error 

code

No ignition block

01

Safety thermostat block (over-

heating), flame control anomaly

02

Flue safety thermostat block

03

Contacts resistance block

04

Flow probe anomaly

05

Domestic hot water probe anomaly

06

Maximum No of resets.

08

Insufficient system pressure

10

Domestic hot water inlet probe 

anomaly

12

Configuration error

15

Fan anomaly

16

Parasite flame block

20

Return probe anomaly

23

Push button control panel anomaly

24

Block due to flue gas temperature 

gradient intervention

25

Insufficient circulation

27

Flue probe anomaly

29

Loss of remote control 

communication

31

Low power supply voltage

37

Loss of flame signal

38

ΔT high

45

Burner power limitation

47

High temperature block on return 

probe

49

Attention:

 the error codes 31 to 38 are not shown 

on the CAR

V2

 and Super CAR display, general 

code 22 is displayed in its place.

Attention: 

The anomaly can be reset up to 5 

successive times, after which the function in 

inhibited for at least one hour. One attempt is 

gained every hour for a maximum of 5 attempts. 

By switching the appliance off and on again, the 

5 attempts are re-acquired.

Ignition block.

 The boiler ignites automatically 

with each demand for room central heating or 

hot water production. If this does not occur 

within  10  seconds,  the  boiler  remains  in 

stand-by for 30 seconds; try again and if the 

second attempt fails it will go into “ignition 

block” (ERR01). To eliminate “ignition block” 

the  Reset  button  "C"  must  be  pressed.  On 

commissioning or after extended inactivity it 

may  be  necessary  to  eliminate  the  “ignition 

block”. If this phenomenon occurs frequently, 

contact  a  qualified  technician  for  assistance 

(e.g. Immergas After-Sales Technical Assistance 

Service).

Safety  thermostat  block  (over-heating).

 

During operation, if a fault causes excessive 

overheating internally, or an anomaly occurs in 

the flame control section, an overheating block 

is triggered in the boiler (ERR02). To eliminate 

“over-temperature block” the Reset button "C" 

must be pressed. If this phenomenon occurs 

frequently, contact a qualified technician for 

assistance (e.g. Immergas After-Sales Technical 

Assistance Service).

Flue safety thermostat block.

 This occurs in 

the case of partial internal obstruction (due to 

the presence of lime scale or slurry) or external 

blocking should occur (combustion residues) 

to the condensation module. To eliminate the 

“flue thermostat block” the Reset button “C” 

must be pressed. Call an authorised technician 

to remove the obstructions (e.g. Immergas After-

sales Service).

Contacts resistance block.

 To eliminate the 

“flue thermostat block” the Reset button “C” 

must be pressed. Call an authorised technician 

to  remove  the  obstructions  (e.g.  Immergas 

After-sales Service). The boiler does not start 

and a technician must be called (e.g. Immergas 

After-Sales Service).

Flow probe anomaly.

 If the board detects an 

anomaly on the system NTC delivery probe, the 

boiler will not start; contact a qualified technician 

for assistance (e.g. Immergas After-Sales Service).

Delivery probe anomaly.

 If the board detects 

an anomaly on the domestic hot water NTC 

probe, the boiler signals the anomaly. In this 

case the boiler continues to produce domestic 

hot water but not with optimal performance. 

Moreover, the anti-freeze function is prevented 

and an authorised technician must be called (e.g. 

Immergas After-Sales Service).

Maximum No of resets. 

Available number of 

resets already made.

Insufficient system pressure. 

Water pressure 

inside the central heating system that is sufficient 

to guarantee the correct functioning of the boiler 

is not detected. Check on the boiler manomater 

(1) that the system pressure is between 1÷1.2 

bar and restore the correct pressure if necessary.

Domestic hot water inlet probe anomaly.

 If 

the board detects an anomaly on the domestic 

hot water inlet probe, the boiler continues to 

produce domestic hot water but not with optimal 

performance. A qualified technician must be 

called (e.g. Immergas After-Sales Service).

Configuration error.

 If the board detects an 

anomaly or in congruency on the electric wiring, 

the boiler will not start. If normal conditions are 

restored the boiler restarts without having to be 

reset. If this anomaly persists, contact a qualified 

technician for assistance (e.g. Immergas After-

Sales Service).

Fan  anomaly.

  This  occurs  if  the  fan  has  a 

mechanical  or  electrical  fault.  To  eliminate 

the “fan anomaly” the Reset button "C" must 

be pressed. If this anomaly persists, contact a 

qualified technician for assistance (e.g. Immergas 

After-Sales Service).

Parasite flame block.

 This occurs in case of a 

leak on the detection circuit or anomaly in the 

flame control unit. The boiler can be reset in 

order to allow a new ignition attempt. If the boiler 

does not start, contact a qualified technician for 

assistance (e.g. Immergas After-Sales Service).

Return probe anomaly. 

If the board detects an 

anomaly on the system return NTC probe, the 

boiler will not start; contact a qualified technician 

for assistance (e.g. Immergas After-Sales Techni-

cal Assistance Service).

Push button control panel anomaly.

 This occurs 

when the P.C.B. detects an anomaly on the push 

button control panel. If normal conditions are 

restored the boiler restarts without having to be 

reset. If this anomaly persists, contact a qualified 

technician for assistance (e.g. Immergas After-

Sales Service).

Block due to flue gas temperature gradient 

intervention.

  If  the  board  detects  a  rapid 

increase of flue gas temperature probably due 

to a blocked pump or lack of water in the heat 

exchanger, the boiler blocks due to the flue gas 

temperature gradient intervention. To eliminate 

it,  the  Reset  button  (C)  must  be  pressed.  If 

this phenomenon occurs frequently, contact a 

qualified technician for assistance (e.g. Immergas 

After-Sales Technical Assistance Service).

Insufficient circulation. 

This occurs if there 

is overheating in the boiler due to insufficient 

water  circulating  in  the  primary  circuit;  the 

causes can be: 
- low system circulation; check that no shut-off 

devices are closed on the heating circuit and 

that the system is free of air (deaerated);

- circulating pump blocked; free the circulating 

pump.

If this phenomenon occurs frequently, contact a 

qualified technician for assistance (e.g. Immergas 

After-Sales Technical Assistance Service).

Flue probe anomaly. 

If the board detects an 

anomaly on the flue probe, the boiler will not 

start; contact a qualified technician for assistance 

(e.g. Immergas After-Sales Technical Assistance 

Service).

Loss of remote control communication.

 This 

occurs in the case of connection to a remote 

control that is not compatible or if there is a 

loss of communication between the boiler and 

CAR remote control

V2

 or Super CAR remote 

control. Try the connection procedure again by 

turning the boiler off and then back on again. If 

the Remote Control is still not detected on re-

starting the boiler will switch to local operating 

mode,  i.e.  using  the  controls  on  the  boiler 

itself. In this case the boiler cannot activate the 

“Central heating” function. To make the boiler 

function in “Central heating” mode, activate the 

“P33” function present inside the “M3” menu. 

If this phenomenon occurs frequently, contact a 

qualified technician for assistance (e.g. Immergas 

After-Sales Technical Assistance Service).

Содержание VICTRIX Superior TOP 32 E

Страница 1: ...VICTRIX Superior TOP 32 E IE Instruction and warning book 1 032471IE...

Страница 2: ...DECLARES THAT the Immergas boiler model Victrix Superior TOP 32 E is in compliance with the same European Community Directives Mauro Guareschi Research Development Director Signature Dear Client Our c...

Страница 3: ...r any damage caused to the household appliances It is also advisable to not position furnishings furniture etc under the boiler for the above mentioned reasons In the event of malfunctions faults or i...

Страница 4: ...The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percentage necessary with respect to the minimum temperature at which the system must be kept An aqueous...

Страница 5: ...lime scale apparatus is preserved for example limescale deposits from the slurry formation and other noxious deposits Waterconnectionsmustbemadeinarationalway using the couplings on the boiler templa...

Страница 6: ...the Super CAR must be used with its climate thermostat function disabled i e it must be set to On Off mode CARV2 Super CAR or On Off chrono thermostat electrical connection Optional The operations des...

Страница 7: ...This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning of the gaskets black for green range flue extraction systems Position t...

Страница 8: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust...

Страница 9: ...laps Fit the male side smooth of the exhaust terminal into the the female side of the bend 90 80 making sure that the relevant wall sealing plate is already fitted this will ensure the hold and joinin...

Страница 10: ...ested Horizontal intake exhaust kit 80 125 Kit assembly Fig 1 15 for the installation of kit 80 125 the flanged adapter kit must be used to be able to install the flue system 80 125 Install the flange...

Страница 11: ...take exhaust pipe 5 Fit the 60 100 3 concentric terminal pipe with the male end 5 smooth into the flange 2 up to the stop making sure that the wall sealing plate has been fitted 3 this will ensure sea...

Страница 12: ...flat flange present in the lateral hole with respect to the central one according to needs and replace it with the flange 3 positioning the gasket 2 already present in the boiler and tighten using th...

Страница 13: ...he removal of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a min slope of 1 5 Assemble the lid A complete with adapter 1 and wall plugs 6 and assemble the flu...

Страница 14: ...ue technical slot The max possible length of the 60 flexible ducting vertical section is equal to 30 m This length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe in exhaust two...

Страница 15: ...ent the circulation pump by loosening the front cap and keeping the motor running Re tighten the cap after the operation 1 19 FILLING THE CONDENSATE TRAP On first lighting of the boiler combustion pro...

Страница 16: ...the power supplied by the burner greater the power greater the speed Moreover inside the parameter it is possible to regulate the operation range of the pump by setting the maximum speed adjustable fr...

Страница 17: ...ly This kit is very useful for maintenance because it allows to empty just the boiler without having to empty the entire system Moreover the version with filter preserves the functioning characteristi...

Страница 18: ...e of electrical power requires some fundamental rules to be observed do not touch the appliance with wet or moist parts of the body do not touch when barefoot never pull electrical cables or leave the...

Страница 19: ...tral heating in order to evacuate residual flue gases F5 Postcirculation in progress Pump in function after a request for domestic hot water or central heating in order to cool the primary circuit P33...

Страница 20: ...By turning the selector switch 1 in a clockwise direction the temperature increases and in an anti clockwise direction it decreases During the heating of the domestic hot water DHW ON appears on the...

Страница 21: ...chnician must be called e g Immergas After Sales Service Maximum No of resets Available number of resets already made Insufficient system pressure Water pressure inside the central heating system that...

Страница 22: ...in the case of malfunctioning or anomaly the display of the temperature is replaced by the relative error code present in the table Par 2 6 2 7 BOILER SHUTDOWN Switchtheboileroffbypressingthe button d...

Страница 23: ...The display is always lit up OFF The display only lights up when the controls are accessed and remains on for 5 seconds after the last operation performed P32 D C P32 B D C ITALIANO D x select C All d...

Страница 24: ...t by the external probe See OFFSET on the external probe graphics Fig 1 8 by modifying the temperature from 15 C to 15 C P94 D x select C It defines the flow temperature of the zone number 3 at low te...

Страница 25: ...or aeration of the installation room where provided If even only a single safety check offers a negative result do not commission the system 3 1 HYDRAULIC DIAGRAM Key 1 Condensate drain trap 2 Water i...

Страница 26: ...the system pressure is within established limits Check that the radiator valves are not closed and also the functionality of the pump Siphon blocked This may be caused by dirt or combustion products...

Страница 27: ...board air gas circuit components or in the case of installations with fume extraction systems with horizontal concentric pipe measuring more than 1 metre The boiler heat output is correlated to the le...

Страница 28: ...ive take the heating selector switch to maximum turn it in a clockwise direction until 99 is seen on the display To have an exact value of CO2 in the flue gases the technician must insert the sampling...

Страница 29: ...the maximum delivery temperature With the external probe present it defines the maximum flow temperature corresponding to functioning with minimum external temperature see graphics Fig 1 8 can be set...

Страница 30: ...juster on the various levels Auto automatic functioning therefore with variable flow rate Open adjuster completely open therefore maximum flow rate available 08 L M 10 L M and 12 L M ffunctioning with...

Страница 31: ...t upstream from the boiler Set the P 71 function on P 71 1 Par 3 8 When the boiler inlet water is at a temperature that is equal or greater with respect to that set by the domestic hot water selector...

Страница 32: ...with that indicated by the regulations in force 3 17 CASING REMOVAL To facilitate boiler maintenance the casing can be completely removed as follows disassemble the front 1 of the boiler by loosening...

Страница 33: ...kg h mbar mm H2 O kg h mbar mm H2 O 32 0 27520 3 45 8 30 84 6 2 58 8 40 85 7 2 53 8 20 83 6 31 0 26660 3 34 7 80 79 6 2 49 7 88 80 4 2 45 7 76 79 2 30 0 25800 3 23 7 33 74 7 2 41 7 39 75 3 2 37 7 34...

Страница 34: ...ith burner On Off 80 60 C 0 48 0 30 Heat loss at flue with burner On Off 80 60 C 0 03 2 20 Central heating circuit max operating pressure bar 3 Central heating circuit max operating temperature C 90 A...

Страница 35: ......

Страница 36: ...immergas com Immergas S p A 42041 Brescello RE Italy T 39 0522 689011 F 39 0522 680617 This instruction booklet is made of ecological paper Code 1 032471IE rev 15 036945 001 09 2012...

Отзывы: