Immergas VICTRIX Superior TOP 32 E Скачать руководство пользователя страница 18

18 - IE

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

2

  INSTRUCTIONS FOR USE 

AND MAINTENANCE.

2.1  CLEANING AND MAINTENANCE.

Attention:

 the heating systems must undergo 

periodical maintenance (regarding this, see the 

section dedicated to the maintenance technician, 

relative to “yearly control and maintenance of 

the appliance”) and regular checks of energy 

efficiency in compliance with national, regional 

or local provisions in force.

This ensures that the optimal safety, performance 

and operation characteristics of the boiler remain 

unchanged over time.

We recommend stipulating a yearly cleaning and 

maintenance contract with your zone technician.

2.2  GENERAL WARNINGS.

Never expose the wall-mounted boiler to direct 

vapours from a cooking surface.

Use of the boiler by unskilled persons or children 

is strictly prohibited.

For safety purposes, check that the concentric 

air intake/flue exhaust terminal (if fitted), is 

not blocked.

If temporary shutdown of the boiler is required, 

proceed as follows:

a) drain the heating system if anti-freeze is not 

used;

b) shut-off all electrical, water and gas supplies.
In the case of work or maintenance to structures 

located  in  the  vicinity  of  ducting  or  devices 

for  flue  extraction  and  relative  accessories, 

switch off the appliance and on completion of 

operations ensure that a qualified technician 

checks efficiency of the ducting or other devices.

Never clean the appliance or connected parts 

with easily flammable substances.

Never leave containers or flammable substances 

in the same environment as the appliance.
• 

Attention:

 the use of components involving use 

of electrical power requires some fundamental 

rules to be observed:

  - do  not  touch  the  appliance  with  wet  or 

moist parts of the body; do not touch when 

barefoot;

  - never  pull  electrical  cables  or  leave  the 

appliance exposed to atmospheric agents 

(rain, sunlight, etc.);

  - the  appliance  power  cable  must  not  be 

replaced by the user;

  - in the event of damage to the cable, switch 

off  the  appliance  and  contact  exclusively 

qualified staff for replacement;

  - if the appliance is not to be used for a certain 

period, disconnect the main power switch.

N.B.:

 the temperatures indicated by the display 

have a tolerance of +/- 3°C due to environmental 

conditions that cannot be blamed on the boiler.

Key:

 

  -  Stand-by - On Button

 

A

  -  Summer 

( )

 and winter 

( )

 functioning mode selection button

 

B

  -  Aqua Celeris Activation Button 

( )

 

C

  - 

(RESET)

 / menu exit 

(ESC)

 reset button

 

D

  -  Menu entry button (

MENU

)/ data confirmation 

(OK)

  1  -  Domestic hot water temperature selector

  2  -  Domestic hot water temperature set

  3  -  Heating temperature selector

  4  -  Central heating temperature set

  5  -  Anomaly present

  6  -  Display of boiler functioning status

  8  -  Flame presence symbol and relative output scale

9 and 7 -  Primary heat exchanger output water temperature

  10  -  Boiler in stand-by

  11  -  Boiler connected to remote control (Optional)

  12  -  Operation in summer mode

  13  -  Anti-freeze function in progress.

  14  -  Operation in winter mode

  15  -  Functioning with Aqua Celeris active

  16  -  Connection to external tools for technician

  17  -  Display of menu items

  18  -  Functioning with external temperature probe active

  19  -  Display of data confirmation or menu access

20 and 7  -  External temperature display 

 

          with external probe connected (optional)

  21  -  Display of reset or exit menu request

  22  -  Chimney sweep function in progress

  23  -  Boiler manometer

  24  -  Multifunction display

2.3  CONTROL PANEL.

Fig. 2-1

Содержание VICTRIX Superior TOP 32 E

Страница 1: ...VICTRIX Superior TOP 32 E IE Instruction and warning book 1 032471IE...

Страница 2: ...DECLARES THAT the Immergas boiler model Victrix Superior TOP 32 E is in compliance with the same European Community Directives Mauro Guareschi Research Development Director Signature Dear Client Our c...

Страница 3: ...r any damage caused to the household appliances It is also advisable to not position furnishings furniture etc under the boiler for the above mentioned reasons In the event of malfunctions faults or i...

Страница 4: ...The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percentage necessary with respect to the minimum temperature at which the system must be kept An aqueous...

Страница 5: ...lime scale apparatus is preserved for example limescale deposits from the slurry formation and other noxious deposits Waterconnectionsmustbemadeinarationalway using the couplings on the boiler templa...

Страница 6: ...the Super CAR must be used with its climate thermostat function disabled i e it must be set to On Off mode CARV2 Super CAR or On Off chrono thermostat electrical connection Optional The operations des...

Страница 7: ...This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning of the gaskets black for green range flue extraction systems Position t...

Страница 8: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust...

Страница 9: ...laps Fit the male side smooth of the exhaust terminal into the the female side of the bend 90 80 making sure that the relevant wall sealing plate is already fitted this will ensure the hold and joinin...

Страница 10: ...ested Horizontal intake exhaust kit 80 125 Kit assembly Fig 1 15 for the installation of kit 80 125 the flanged adapter kit must be used to be able to install the flue system 80 125 Install the flange...

Страница 11: ...take exhaust pipe 5 Fit the 60 100 3 concentric terminal pipe with the male end 5 smooth into the flange 2 up to the stop making sure that the wall sealing plate has been fitted 3 this will ensure sea...

Страница 12: ...flat flange present in the lateral hole with respect to the central one according to needs and replace it with the flange 3 positioning the gasket 2 already present in the boiler and tighten using th...

Страница 13: ...he removal of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a min slope of 1 5 Assemble the lid A complete with adapter 1 and wall plugs 6 and assemble the flu...

Страница 14: ...ue technical slot The max possible length of the 60 flexible ducting vertical section is equal to 30 m This length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe in exhaust two...

Страница 15: ...ent the circulation pump by loosening the front cap and keeping the motor running Re tighten the cap after the operation 1 19 FILLING THE CONDENSATE TRAP On first lighting of the boiler combustion pro...

Страница 16: ...the power supplied by the burner greater the power greater the speed Moreover inside the parameter it is possible to regulate the operation range of the pump by setting the maximum speed adjustable fr...

Страница 17: ...ly This kit is very useful for maintenance because it allows to empty just the boiler without having to empty the entire system Moreover the version with filter preserves the functioning characteristi...

Страница 18: ...e of electrical power requires some fundamental rules to be observed do not touch the appliance with wet or moist parts of the body do not touch when barefoot never pull electrical cables or leave the...

Страница 19: ...tral heating in order to evacuate residual flue gases F5 Postcirculation in progress Pump in function after a request for domestic hot water or central heating in order to cool the primary circuit P33...

Страница 20: ...By turning the selector switch 1 in a clockwise direction the temperature increases and in an anti clockwise direction it decreases During the heating of the domestic hot water DHW ON appears on the...

Страница 21: ...chnician must be called e g Immergas After Sales Service Maximum No of resets Available number of resets already made Insufficient system pressure Water pressure inside the central heating system that...

Страница 22: ...in the case of malfunctioning or anomaly the display of the temperature is replaced by the relative error code present in the table Par 2 6 2 7 BOILER SHUTDOWN Switchtheboileroffbypressingthe button d...

Страница 23: ...The display is always lit up OFF The display only lights up when the controls are accessed and remains on for 5 seconds after the last operation performed P32 D C P32 B D C ITALIANO D x select C All d...

Страница 24: ...t by the external probe See OFFSET on the external probe graphics Fig 1 8 by modifying the temperature from 15 C to 15 C P94 D x select C It defines the flow temperature of the zone number 3 at low te...

Страница 25: ...or aeration of the installation room where provided If even only a single safety check offers a negative result do not commission the system 3 1 HYDRAULIC DIAGRAM Key 1 Condensate drain trap 2 Water i...

Страница 26: ...the system pressure is within established limits Check that the radiator valves are not closed and also the functionality of the pump Siphon blocked This may be caused by dirt or combustion products...

Страница 27: ...board air gas circuit components or in the case of installations with fume extraction systems with horizontal concentric pipe measuring more than 1 metre The boiler heat output is correlated to the le...

Страница 28: ...ive take the heating selector switch to maximum turn it in a clockwise direction until 99 is seen on the display To have an exact value of CO2 in the flue gases the technician must insert the sampling...

Страница 29: ...the maximum delivery temperature With the external probe present it defines the maximum flow temperature corresponding to functioning with minimum external temperature see graphics Fig 1 8 can be set...

Страница 30: ...juster on the various levels Auto automatic functioning therefore with variable flow rate Open adjuster completely open therefore maximum flow rate available 08 L M 10 L M and 12 L M ffunctioning with...

Страница 31: ...t upstream from the boiler Set the P 71 function on P 71 1 Par 3 8 When the boiler inlet water is at a temperature that is equal or greater with respect to that set by the domestic hot water selector...

Страница 32: ...with that indicated by the regulations in force 3 17 CASING REMOVAL To facilitate boiler maintenance the casing can be completely removed as follows disassemble the front 1 of the boiler by loosening...

Страница 33: ...kg h mbar mm H2 O kg h mbar mm H2 O 32 0 27520 3 45 8 30 84 6 2 58 8 40 85 7 2 53 8 20 83 6 31 0 26660 3 34 7 80 79 6 2 49 7 88 80 4 2 45 7 76 79 2 30 0 25800 3 23 7 33 74 7 2 41 7 39 75 3 2 37 7 34...

Страница 34: ...ith burner On Off 80 60 C 0 48 0 30 Heat loss at flue with burner On Off 80 60 C 0 03 2 20 Central heating circuit max operating pressure bar 3 Central heating circuit max operating temperature C 90 A...

Страница 35: ......

Страница 36: ...immergas com Immergas S p A 42041 Brescello RE Italy T 39 0522 689011 F 39 0522 680617 This instruction booklet is made of ecological paper Code 1 032471IE rev 15 036945 001 09 2012...

Отзывы: