Functioning with external probe (part. 18) 

optional.

 In the case of a system with optional 

external probe, the boiler flow temperature 

for room central heating is managed by the 

external  probe  depending  on  the  external 

temperature measured (Par. 1.6 and par. 3.8 

under  “P66”).  It  is  possible  to  modify  the 

delivery temperature from -15°C to +15°C with 

respect to the adjustment curve (see graphics 

fig. 1-8 Offset value). This correction, which 

can be activated using selector switch (3) is kept 

active for any external temperature measured. 

The modification of the offset temperature is 

displayed using the indicator (7). The indicator 

(4) shows the current delivery temperature and 

after a few seconds from the modification it is 

updated with the new correction. The “SET” 

indication appears on the display (see figure). 

By turning the selector switch (1) in a clockwise 

direction the temperature increases and in an 

anti-clockwise direction it decreases.

  During the request for central heating “CH” 

appears  on  the  display  (24)  on  the  status 

indicator (6) and at the same time as burner 

ignition the flame presence indicator switches 

on  (8)  with  relative  power  scale  and  the 

indicator (9 and 7) with the instantaneous 

outlet  temperature  from  the  primary  heat 

exchanger.  In  the  central  heating  phase,  if 

the temperature of the water contained in the 

system is sufficient to heat the radiators, the 

boiler can only function with the activation of 

the boiler pump.

From  this  moment  the  boiler  functions 

automatically. With no demand for heat (heating 

or domestic hot water production) the boiler goes 

to “standby” function, equivalent to the boiler 

being powered without presence of flame.

N.B.:

 the boiler may start-up automatically if the 

anti-freeze function is activated.(13). Moreover, 

the boiler can function for a brief period of time 

after a withdrawal of domestic hot water in order 

to take the domestic hot water temperature back 

into temperature.

Attention:

 with the boiler in stand-by mode (

) hot water cannot be produced and the safety 

systems cannot be guaranteed, such as: pump 

anti-block, anti-freeze and three way anti-block.

Adjustment of domestic hot water

Fig. 2-2

Fig. 2-3

Fig. 2-4

Winter functioning mode with  

room central heating

Adjustment of the system flow temperature

Fig. 2-5

2.5  USING THE BOILER.

Before ignition make sure the central heating 

system is filled with water and that the manometer 

(23) indicates a pressure of 1 - 1.2 bar.

Open the gas cock upstream from the boiler.
With the boiler off, only the stand-by symbol 

(10) appears on the display. By pressing the (

button the boiler switches on.

Once the boiler is on, by pressing button “A” 

repeatedly, the functioning mode changes and 

pass  alternatively  from  summer  functioning 
mode ( ) and winter functioning mode ( ).
• 

Summer  (

):

  in  this  mode  the  boiler 

functions only to heat domestic hot water. The 

temperature is set using the selector switch (1) 

and the relative temperature is shown on the 

display (24) by means of the indicator (2) and 

the “SET” indication appears. (see figure). By 

turning the selector switch (1) in a clockwise 

direction the temperature increases and in an 

anti-clockwise direction it decreases.

  During the heating of the domestic hot water 

“DHW ON” appears on the display (24) on 

the status indicator (6) and at the same time 

as burner ignition the flame presence indicator 

switches on (8) with relative power scale and 

the indicator (9 and 7) with the instantaneous 

outlet  temperature  from  the  primary  heat 

exchanger.

• Winter ( ):

 in this mode the boiler functions 

both  for  heating  domestic  hot  water  and 

heating the environment. The temperature of 

the domestic hot water is always adjusted using 

the selector switch (1), the heating temperature 

is adjusted using the selector switch (3) and the 

relative temperature is shown on the display 

(24) using the indicator (4) and the “SET” 

indication appears. (see figure). By turning the 

selector switch (3) in a clockwise direction the 

temperature increases and in an anti-clockwise 

direction it decreases.

  During the request for central heating “CH 

ON”  appears  on  the  display  (24)  on  the 

status indicator (6) and at the same time as 

burner ignition the flame presence indicator 

switches on (8) with relative power scale and 

the indicator (9 and 7) with the instantaneous 

outlet  temperature  from  the  primary  heat 

exchanger.  In  the  central  heating  phase,  if 

the temperature of the water contained in the 

system is sufficient to heat the radiators, the 

boiler can only function with the activation of 

the boiler pump.

• 

Operation with Comando Amico Remoto 

remote control 

V2

 (CAR

V2

) (Optional)

.  In 

the case of connection to the CAR remote 

control

V2

, the boiler automatically detects the 

display and the symbol appears on the display 
(

). 

  From this moment all controls and adjustments 

are referred to the CAR remote control

V2

, The 

stand-by button “

”, the Reset button "C", the 

menu entry button "D" and the Aqua Celeris 

button "B" however remain active.

 

Attention:

 if the boiler is put in stand-by mode 

(10) on the CAR

V2

 the “ERR>CM” connection 

error symbol will appear on the CAR

V2

. The 

CAR is however powered constantly so as not 

to loose memorised programs.

• 

Operation  with  Super  Comando  Amico 

Remoto  remote  control  (Super  CAR) 

(Optional).

  In  the  case  of  connection  to 

the  Super  CAR  remote  control,  the  boiler 

automatically  detects  the  display  and  the 
symbol appears on the display(

). 

  From  this  moment  it  is  possible  to  make 

adjustments indifferently from the Super CAR 

remote control or the boiler. Except for the 

room heating temperature that is shown on 

the display but managed by the Super RFC.

   

Attention:

 If the boiler is put into stand-by 

(10) the “ERR>CM” connection error symbol 

will appear on the Super CAR. The Super CAR 

is however powered constantly so as not to 

loose memorised programs.

• 

Aqua Celeris Function. 

By pressing button “B” 

the Aqua Celeris function is activated, which is 

marked by the switch-on of the symbol (15) on 

the display (24). The enabled function keeps the 

water contained in the mini storage tank always 

hot, thus guaranteeing an almost instantaneous 

distribution of domestic hot water.

System flow temperature adjustment with 

external probe (optional)

Functioning in winter mode with  

external probe (optional)

Fig. 2-6

Fig. 2-7

Functioning in Summer mode with  

domestic hot water heating.

Содержание VICTRIX Superior TOP 32 E

Страница 1: ...VICTRIX Superior TOP 32 E IE Instruction and warning book 1 032471IE...

Страница 2: ...DECLARES THAT the Immergas boiler model Victrix Superior TOP 32 E is in compliance with the same European Community Directives Mauro Guareschi Research Development Director Signature Dear Client Our c...

Страница 3: ...r any damage caused to the household appliances It is also advisable to not position furnishings furniture etc under the boiler for the above mentioned reasons In the event of malfunctions faults or i...

Страница 4: ...The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percentage necessary with respect to the minimum temperature at which the system must be kept An aqueous...

Страница 5: ...lime scale apparatus is preserved for example limescale deposits from the slurry formation and other noxious deposits Waterconnectionsmustbemadeinarationalway using the couplings on the boiler templa...

Страница 6: ...the Super CAR must be used with its climate thermostat function disabled i e it must be set to On Off mode CARV2 Super CAR or On Off chrono thermostat electrical connection Optional The operations des...

Страница 7: ...This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning of the gaskets black for green range flue extraction systems Position t...

Страница 8: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust...

Страница 9: ...laps Fit the male side smooth of the exhaust terminal into the the female side of the bend 90 80 making sure that the relevant wall sealing plate is already fitted this will ensure the hold and joinin...

Страница 10: ...ested Horizontal intake exhaust kit 80 125 Kit assembly Fig 1 15 for the installation of kit 80 125 the flanged adapter kit must be used to be able to install the flue system 80 125 Install the flange...

Страница 11: ...take exhaust pipe 5 Fit the 60 100 3 concentric terminal pipe with the male end 5 smooth into the flange 2 up to the stop making sure that the wall sealing plate has been fitted 3 this will ensure sea...

Страница 12: ...flat flange present in the lateral hole with respect to the central one according to needs and replace it with the flange 3 positioning the gasket 2 already present in the boiler and tighten using th...

Страница 13: ...he removal of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a min slope of 1 5 Assemble the lid A complete with adapter 1 and wall plugs 6 and assemble the flu...

Страница 14: ...ue technical slot The max possible length of the 60 flexible ducting vertical section is equal to 30 m This length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe in exhaust two...

Страница 15: ...ent the circulation pump by loosening the front cap and keeping the motor running Re tighten the cap after the operation 1 19 FILLING THE CONDENSATE TRAP On first lighting of the boiler combustion pro...

Страница 16: ...the power supplied by the burner greater the power greater the speed Moreover inside the parameter it is possible to regulate the operation range of the pump by setting the maximum speed adjustable fr...

Страница 17: ...ly This kit is very useful for maintenance because it allows to empty just the boiler without having to empty the entire system Moreover the version with filter preserves the functioning characteristi...

Страница 18: ...e of electrical power requires some fundamental rules to be observed do not touch the appliance with wet or moist parts of the body do not touch when barefoot never pull electrical cables or leave the...

Страница 19: ...tral heating in order to evacuate residual flue gases F5 Postcirculation in progress Pump in function after a request for domestic hot water or central heating in order to cool the primary circuit P33...

Страница 20: ...By turning the selector switch 1 in a clockwise direction the temperature increases and in an anti clockwise direction it decreases During the heating of the domestic hot water DHW ON appears on the...

Страница 21: ...chnician must be called e g Immergas After Sales Service Maximum No of resets Available number of resets already made Insufficient system pressure Water pressure inside the central heating system that...

Страница 22: ...in the case of malfunctioning or anomaly the display of the temperature is replaced by the relative error code present in the table Par 2 6 2 7 BOILER SHUTDOWN Switchtheboileroffbypressingthe button d...

Страница 23: ...The display is always lit up OFF The display only lights up when the controls are accessed and remains on for 5 seconds after the last operation performed P32 D C P32 B D C ITALIANO D x select C All d...

Страница 24: ...t by the external probe See OFFSET on the external probe graphics Fig 1 8 by modifying the temperature from 15 C to 15 C P94 D x select C It defines the flow temperature of the zone number 3 at low te...

Страница 25: ...or aeration of the installation room where provided If even only a single safety check offers a negative result do not commission the system 3 1 HYDRAULIC DIAGRAM Key 1 Condensate drain trap 2 Water i...

Страница 26: ...the system pressure is within established limits Check that the radiator valves are not closed and also the functionality of the pump Siphon blocked This may be caused by dirt or combustion products...

Страница 27: ...board air gas circuit components or in the case of installations with fume extraction systems with horizontal concentric pipe measuring more than 1 metre The boiler heat output is correlated to the le...

Страница 28: ...ive take the heating selector switch to maximum turn it in a clockwise direction until 99 is seen on the display To have an exact value of CO2 in the flue gases the technician must insert the sampling...

Страница 29: ...the maximum delivery temperature With the external probe present it defines the maximum flow temperature corresponding to functioning with minimum external temperature see graphics Fig 1 8 can be set...

Страница 30: ...juster on the various levels Auto automatic functioning therefore with variable flow rate Open adjuster completely open therefore maximum flow rate available 08 L M 10 L M and 12 L M ffunctioning with...

Страница 31: ...t upstream from the boiler Set the P 71 function on P 71 1 Par 3 8 When the boiler inlet water is at a temperature that is equal or greater with respect to that set by the domestic hot water selector...

Страница 32: ...with that indicated by the regulations in force 3 17 CASING REMOVAL To facilitate boiler maintenance the casing can be completely removed as follows disassemble the front 1 of the boiler by loosening...

Страница 33: ...kg h mbar mm H2 O kg h mbar mm H2 O 32 0 27520 3 45 8 30 84 6 2 58 8 40 85 7 2 53 8 20 83 6 31 0 26660 3 34 7 80 79 6 2 49 7 88 80 4 2 45 7 76 79 2 30 0 25800 3 23 7 33 74 7 2 41 7 39 75 3 2 37 7 34...

Страница 34: ...ith burner On Off 80 60 C 0 48 0 30 Heat loss at flue with burner On Off 80 60 C 0 03 2 20 Central heating circuit max operating pressure bar 3 Central heating circuit max operating temperature C 90 A...

Страница 35: ......

Страница 36: ...immergas com Immergas S p A 42041 Brescello RE Italy T 39 0522 689011 F 39 0522 680617 This instruction booklet is made of ecological paper Code 1 032471IE rev 15 036945 001 09 2012...

Отзывы: