BOILER
INSTALLATION
1.1 INSTALLATION
RECOMMENDATIONS.
Only professionally qualified heating/plumbing
technicians are authorised to install Immergas
gas appliances.
Victrix Pro 35 1 I boilers installed in cascade (2 or
more) and Victrix Pro 55 1 I boilers in individual
or cascade installation can be installed outdoors
or in a suitable room.
The installation must comply with all laws and
standards in force.
The Victrix Pro 35 1 is also suitable for domestic
installations in accordance with the pertinent
installation standard.
The place of installation of the appliance and
relative Immergas accessories must have suitable
features (technical and structural) such to allow
(always in safety, efficiency and comfortable
conditions):
- installation (according to the provisions of the
technical legislation and technical regulations);
- maintenance operations (including scheduled,
periodic, routine and special maintenance);
- removal (to outdoors in the place for loading
and transporting the appliances and compo-
nents) as well as their eventual replacement
with appliances and/or equivalent components.
Attention:
these boilers must be used to heat
rooms and the like; they are for heating water
to a temperature lower that boiling point at
atmospheric pressure. Therefore, they must be
connected to a heating system that is suitable for
their performance and their power.
Before installing the appliance, ensure that it is
delivered in perfect condition; if in doubt, contact
the supplier immediately.
Packaging materials (staples, nails, plastic bags,
polystyrene foam, etc.) constitute a potential haz-
ard and must be kept out of the reach of children.
Keep all flammable objects away from the ap-
pliance (paper, rags, plastic, polystyrene, etc.).
In the event of malfunctions, faults or incorrect
operation, turn the appliance off and contact a
qualified company (e.g. the Immergas Technical
After-Sales Centre, which has specifically trained
staff and original spare parts).
Do not attempt to modify or repair the appli-
ance alone.
Failure to comply with the above implies personal
responsibility and invalidates the warranty.
• Installation regulations: these boilers are not
in any way designed for installation on bases
or floors (Fig. 1-1), but exclusively for wall
installation. The wall surface must be smooth,
without any protrusions or recesses enabling
access to the rear part. Wall mounting of the
boiler must guarantee stable and efficient sup-
port for the boiler.
The plugs (standard supply)
are to be used only in conjunction with the
mounting brackets or fixing template to fix the
appliance to the wall;
they only ensure adequate
support if inserted correctly (according to
technical standards) in walls made of solid or
semi-hollow brick or block. In the case of walls
made from hollow brick or block, partitions
with limited static properties, or in any case
walls other than those indicated, a static test
must be carried out to ensure adequate support.
The boilers must be installed in a way to prevent
collisions and tampering.
N.B.: the hex head screws supplied in the blis-
ter pack are to be used exclusively to fix the
mounting bracket to the wall.
1.2 POSITION OF THE APPLIANCES.
The boilers can be installed:
- outdoors;
- in outdoor environments, also adjoining the
building served, located in uncovered space, as
long as structurally separated and without walls
in common, or situated on the flat covering of
the building served, always without walls in
common;
- in building also destined for other use or in
places inserted in the volume of the building
served.
These rooms must be intended exclusively to
house CH systems and must have characteristics
that comply with legislation in force.
N.B.:
with Victrix Pro 35 1 I in individual instal-
lation it is also possible to set the appliance up
in household settings, or similar, in accordance
with legislation in force.
Attention:
the installation of appliances powered
with gas with a greater density than 0.8 (L.P.G.)
is only allowed in places out of the ground,
also communicating with places that are on the
ground. In both cases the walkway must not have
hollows or depressions such to create gas pockets
that determine dangerous conditions.
Height of the installation room.
Installation of individual appliance
: the room
must have a minimum ceiling height of 2 m.
Installation of multiple appliances in cascade (2 ÷ 5
Victrix Pro):
considering the size of the boiler, the
flue manifold (which must be installed on a 3%
gradient) and the hydraulic manifolds, the room
must have a minimum ceiling height of 2.3 m.
The aforementioned heights allow for correct
installation of the appliances and observe the
technical regulations in force.
Position of the appliances in the room.
Individual appliance
: the distances between
any external point of the boiler and the vertical
and horizontal walls of the room must allow
accessibility to the regulation, safety and control
elements for routine maintenance.
Multiple appliances, not interconnected, but in-
stalled in the same room
: the minimum distance
to maintain between several boilers installed
on the same wall must be 200 mm, in order to
allow accessibility to the regulation, safety and
control elements and routine maintenance of all
appliances installed.
Cascade installation (2 ÷ 5 Victrix Pro)
: The
instructions for correct cascade installation are
provided in the respective documents or on the
www.immergas.com website in the high power
section.