Error 

Code

Anomaly signalled

Cause

Boiler status / Solution

0E2

Parasite flame block

This occurs during the power-on phase in the event of a leak on the 

detection circuit or anomaly in the flame control unit.

(2) (1)

0E13

Maximum N° of reset

Number of allowed resets that have already performed.

Attention: 

it is possible to reset the anom-

aly up to 5 consecutive times within 15 

minutes. (1) By switching the appliance 

on and off the 5 attempts are re-acquired.

0E25

P.C.B. error

An error is detected on the P.C.B. and the boiler does not start up

(2) (1)

0E32

DHW NTC probe in 

short circuit

The board detects a short circuit on the DHW NTC probe

(2) (1)

0E33

DHW NTC probe 

outside the operating 

range

The board detects an open contact on the DHW NTC probe.

(2) (1)

0E34

Low power supply 

voltage

This occurs when the power supply voltage is lower than the allowed 

limits for the correct boiler operation. 

(2) (1)

0E37

Insufficient system 

pressure or flow

If the system flow rate is too low the boiler switches off.

Check on the boiler pressure gauge (1) 

that the system pressure is between 1÷1.2 

bar and restore the correct pressure if 

necessary. Make sure that the boiler input 

is suitable for the installed circuit. (2) (1)

0E45

Flue NTC probe in 

short circuit

The board detects a short circuit on the flue NTC probe.

(2) (1)

0E46

Flue NTC probe outside 

the operating range

The board detects an open contact on the flue NTC probe.

(2) (1)

0E81

Flow and return NTC 

probe temperature 

detection incorrect (in 

stand-by)

With the boiler in stand-by, the board detects an anomalous difference 

between the NTC probe flow and return temperatures. The error may 

be caused by a failure in one of the two probes

(2) (1)

0E98

Simple cascade com-

munication anomaly

Occurs if the communication between the display boards breaks down

Check the bus’ electric connection.

Perform the Auto detection.

Check whether the software versions 

match. (2) (1)

0E99

Internal communica-

tion anomaly

In the event of simple cascade, even in the case of a communication 

error between the display boards.

Check the boiler’s wiring.

Check the bus’ electric connection.

Perform the Auto detection in the event 

of simple cascade installation.

(2) (1)

(1) If the block or anomaly persists, contact an authorised company (e.g. Immergas Technical After-Sales Service).

(2) If normal operating conditions are restored, the boiler re-starts without having to be reset.

Error 

Code

Anomaly signalled

Cause

Solution

FE94

Display board anomaly

An error is detected on the display's P.C.B..

(2) (1)

FE95

Shared common flow 

probe short-circuited 

or out of range

The board detects an incorrect value on the flow NTC probe or “P38” 

parameter not set correctly.

(2) (1)

FE96

External probe 

anomaly

An anomaly is detected on the external probe.

Check the boiler configuration, check 

the external probe (2) (1)

FE97

Configuration error

P.C.B. configuration error.
It may occur also in the event of replacement of the electronic boards 

with an incorrect model.

Check the configuration parameters.

Perform the Auto detection.  (2) (1)

(1) If the block or anomaly persists, contact an authorised company (e.g. Immergas Technical After-Sales Service).

(2) If normal operating conditions are restored, the boiler re-starts without having to be reset.

Содержание VICTRIX PRO 35 1 I

Страница 1: ...VICTRIX PRO 35 55 1 I IE Instruction and warning book 1 038715ENG...

Страница 2: ......

Страница 3: ...technical information for installing Immergas boilers As for the other issues related to boiler installation e g safety in the work site environment protection injury prevention it is necessary to co...

Страница 4: ...entilation of the installation rooms 21 2 3 General warnings 21 2 4 Control panel 22 2 5 Using the boiler 22 2 6 Troubleshooting 24 2 7 Info menu 26 2 8 Boiler shutdown 26 2 9 Restoring central heatin...

Страница 5: ...hey only ensure adequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In the case of walls made from hollow brick or block partit...

Страница 6: ...ating 1 5 ANTI FREEZE PROTECTION Minimum temperature 5 C The boiler comes standard with an anti freeze function that ac tivates the pump and burner when the system water temperature in the boiler fall...

Страница 7: ...ty The appliance has been de signed to operate with combustible gas free of impurities otherwise it is advisable to fit special filters upstream of the appliance to restore the purity of the fuel Stor...

Страница 8: ...s specified by current safety standards Attention Immergas S p A declines any respon sibility for damage or physical injury caused by failure to connect the boiler to an efficient earth system or fail...

Страница 9: ...uster via 2 wires Thermoregulation electrical connection Fig 1 4 Thermoregulation electrical connections must be carried out on the boiler terminal board eliminating jumper X40 Thermostat or On Off en...

Страница 10: ...ealed chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble the 80 adapter the b...

Страница 11: ...t 1 3 m Terminal complete with vertical exhaust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric be...

Страница 12: ...eft side or front outlet For installation with frontal outlet one must use the fixing plate and a concentric bend coupling in order to ensure sufficient space to carry out the tests required by law up...

Страница 13: ...ix it to the lid using the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure that rainwater runs off...

Страница 14: ...L Fig 1 15 The kit with this configuration can be extended up to a max measurement of 24 0 m with Victrix Pro 35 1 I and 30 0 m with Victrix Pro 55 1 I including the terminal Using the 80 vertical te...

Страница 15: ...4 wall sealing plate has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 80 bend 1 with the...

Страница 16: ...nd in current technical regulations in particular the declaration of conformity must be compiled at the end of work and on commissioning of the ducted system The instructions in the project or technic...

Страница 17: ...boiler operation in the case of new systems single pipe and module it is recommended to use the pump at maximum speed The circulation pump is already fitted with a capacitor Pump release If after a p...

Страница 18: ...le cover 11 Igniter 12 Ignition electrode 13 Flue probe 14 Condensing module air vent valve 15 Fumes hood 16 Sample points air A flue gas F 17 Heat exchanger safety thermal fuse 18 Manual air vent val...

Страница 19: ...d block circuit breaker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collecti...

Страница 20: ...ng circuit pump CMI 1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety thermostat CMI...

Страница 21: ...orary shutdown of the boiler is required proceed as follows a drain the heating system if anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interv...

Страница 22: ...ies 24 Pump running 25 Summer mode 2 5 USING THE BOILER Before ignition make sure that the system is full of water checking that the manometer 5 indicates a base value at which the system has been des...

Страница 23: ...maintain the previous setting 2 4 2 5 Stand by mode by pressing buttons A and C at the same time it is possible to place the boiler in stand by In this mode the boiler is considered powered on but not...

Страница 24: ...NTC probe temperature The error may be caused by a poor thermal probe contact or a system with excessive thermal inertia Press the Reset button 1 0A17 Poor thermal return NTC probe contact During boi...

Страница 25: ...th the boiler in stand by the board detects an anomalous difference between the NTC probe flow and return temperatures The error may be caused by a failure in one of the two probes 2 1 0E98 Simple cas...

Страница 26: ...s that are drained frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 12 CASE CLEANING Use damp cloths and neutral detergent to clean...

Страница 27: ...fans check that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified check sealing effici...

Страница 28: ...ostat can be used instead of B2 set P29 17 E4 Safety thermostat E5 Heat exchanger safety thermostat manual reset E13 Safety thermofuse G2 Igniter M1 Boiler circulator pump M20 Fan M30 Three way valve...

Страница 29: ...D inlet Clean contact Max 230 Vac 1 A Key B1 System flow probe NTC B2 Domestic hot water probe NTC B4 External probe M2 Plant CH pump M30 3 way valve Note probe B1 B2 B4 Connection cable diameter 3 7...

Страница 30: ...fibre panel replace the cover gasket of the manifold and reset the thermostat by pressing the specific button check that the exchanger safety thermostat has not intervened If it has check the integri...

Страница 31: ...er s modulation ratio It defines the boiler s modulation ratio Do not modify 0 100 10 P13 Boiler power Used to calculate the boiler power in the event of simple cascade 0 255 kW 35 kW 35 55 kW 50 P14...

Страница 32: ...asurement This defines the unit of measure on the display whether metric or Imperial 0 127 C kW 128 256 F kBTu h 0 P32 Set Resc Min Limits the minimum value of the heating set The parameter takes prio...

Страница 33: ...8 Off Setregulator To increase the CO2 value turn the adjustment screw 3 in a clockwise direction and vice versa to decrease it Calibration of maximum CO2 When you finish the minimum CO2 adjustment tu...

Страница 34: ...be must be connected to terminals S1 and S2 and parameter P38 must be set up whereas the pump must be connected to termi nals C and D If there is a DHW circuit it can be connected via an external 3 wa...

Страница 35: ...replaced at least every two years regardless of their state of wear Check that the burner is intact that it has no deformations or cuts and that it is properly fixed to the combustion chamber lid oth...

Страница 36: ...to de tach it from the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 re...

Страница 37: ...37 3 10 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 INSTALLER USER MAINTENANCE TECHNICIAN Ref A...

Страница 38: ...0 30 0 25800 3 24 4520 2 38 4380 29 0 24940 3 13 4400 2 30 4260 28 0 24080 3 02 4270 2 22 4130 27 0 23220 2 92 4140 2 14 4010 26 0 22360 2 81 4010 2 06 3880 25 0 21500 2 71 3890 1 99 3760 24 0 20640 2...

Страница 39: ...g h 81 82 Flue flow rate at min heat output kg h 9 9 CO2 at Q Nom Min 9 40 9 10 10 60 10 10 CO with 0 O2 at Nom Min Q Nom Min ppm 157 1 184 1 NOX at 0 of O2 at Q Nom Min mg kWh 43 17 43 21 Flue temper...

Страница 40: ...loss at casing with burner On Off 80 60 C 0 44 1 10 0 30 0 90 Heat loss at flue with burner On Off 80 60 C 0 04 1 60 0 03 1 80 Central heating circuit max operating pressure bar 4 4 4 4 Central heatin...

Страница 41: ...d Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type applianceconfiguration ref CENTR1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn ma...

Страница 42: ......

Страница 43: ......

Страница 44: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038715ENG rev ST 002094 000 09...

Отзывы: