background image

16

INS

TALLER

US

ER

 MAINTEN

AN

CE TECHNI

CI

AN

Anti-Extruder function. 

This function reduces 

the heating temperature to 57°C in the case that 

domestic hot water circulation is detected in the 

heating mode.

Activate anti-extruder function

Range of values which can be set Parame-

ter

on

 (Standard setting) - 

oF

P3

Domestic hot water post circulation function 

With the post circulation function active after 

domestic hot water flow, the pump remains on 

for 2.5 seconds in winter time and 1.5 seconds in 

summer time to reduce the formation of limescale.

Activate domestic hot water post circula-

tion

Range of values which can be set Parame-

ter

on

 (Standard setting) - 

oF

P4

Heating power.

The Nike Star 24 4 ErP boiler 

is fitted with an electronic modulation which 

adapts the power of the boiler to effective heat 

requests of the home. Then the boiler works 

normally in a variable gas pressure field between 

the minimum heating power and the maximum 

heating power depending on the system’s hea-

ting load.

N.B.:

The Nike Star 24 4 ErP boiler is produced 

and calibrated in the heating phase to the nomi-

nal heat output. Approximately 10 minutes are 

needed to reach the nominal heat output, which 

can be changed using the parameter (P6).

N.B: 

the selection of the “Minimum heat output” 

and “Maximum heat output” parameters, in the 

presence of a heating request, allows switch-on 

of the boiler and power supply of the modulator 

with current equal to the value of the respective 

set value.

Minimum heat output

Range of values which can be set Parame-

ter

from 

0

 % Imax. to 

63

 % Imax.

P5

Maximum heat output

Range of values which can be set Parame-

ter

from 

0

 % Imax. to 

99

 % Imax. 

(Standard setting)

P6

Timer setting. 

The boiler has an electronic 

timing device that prevents the burner from 

igniting too often in the heating phase. The boiler 

is supplied as per standard with a timer adjusted 

at 3 minutes.

Heating ignitions timer

Range of values which can be set Parame-

ter

from

1

 to

1

1 = 30 seconds

2 = 2 minutes

3 = 3 minutes (Standard setting)

P7

Heating ramp timing. 

The boiler performs an 

ignition ramp of about 10 minutes to arrive from 

minimum power to nominal heating power.

Heating ramp timer

Range of values which can be set Parame-

ter

from

1

 to

10

 

1 = 30 seconds

2 = 2 minutes

10 = 10 minutes (Standard setting)

P8

3.8  AUTOMATIC SLOW IGNITION 

FUNCTION WITH TIMED RAMP 

DELIVERY.

In the ignition phase the P.C.B. carries out an 

increasing gas delivery ramp (with pressure va-

lues that depend on the type of gas selected) with 

preset duration. This prevents every calibration 

or precision adjustment of the boiler ignition 

phase in any conditions of use.

3.9  “CHIMNEY SWEEP FUNCTION”.

When activated, this function forces the boiler 

at max. output for 15 minutes.

In this state all adjustments are excluded and 

only the temperature safety thermostat and the 

limit thermostat remain active. To activate the 

chimney sweep function, press the Reset key for 

at least 10 seconds with the boiler on stand-by. Its 

activation is indicated by the flashing symbols (8 

and 11 fig. 2-1). This function allows the techni-

cian to check the combustion parameters. After 

the checks, deactivate the function switching the 

boiler off and then on again.

3.10 HEATING TIMER.

The Nike Star 24 4 ErP boiler has an electronic 

timing device that prevents the burner from 

igniting too often in the heating phase. The boiler 

is supplied as per standard with a timer adjusted 

at 3 minutes. To adjust the timer values, follow 

instructions for parameter settings by selecting 

parameter (P7) and set it with one of the values 

indicated on the relative table.

3.11 PUMP ANTI-BLOCK FUNCTION.

In summer functioning mode ( ) the boiler 

has a function that starts the pump at least once 

every 24 hours for the duration of 30 seconds in 

order to reduce the risk of the pump becoming 

blocked due to prolonged inactivity.

In winter functioning mode  ( ) the boiler has a 

function that makes the pump start at least once 

every 3 hours for 30 seconds.

3.12 DOMESTIC HOT WATER CIRCUIT 

ANTI-EXTRUDER FUNCTION.

This function reduces the heating temperature 

to 57°C if the domestic hot water circulation is 

detected in the heating mode. The function can 

be excluded using parameter (P3).

3.13 RADIATORS ANTI-FREEZE 

FUNCTION.

If the system return water is below 4°C, the boiler 

starts up until reaching 42°C.

3.14 P.C.B. PERIODICAL SELF-CHECK.

During functioning in heating mode or with 

boiler in standby, the function activates every 18 

hours after the last boiler check/power supply. In 

case of  functioning in domestic hot water mode 

the self-check starts within 10 minutes after the 

end of the withdrawing in progress, for duration 

of approx. 10 seconds.

N.B.:

 during self-check, the boiler remains off, 

including signalling.

Содержание Nike Star 24 4 ErP

Страница 1: ...Maintenance Technician 1 038183ENG Instantaneous wall hung boilers with open chamber type B and natural draught The European regulation 813 2013 provides that this boiler can be installed only to replace similar equipment connected to existing branched multiple flues ...

Страница 2: ...the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by professionally qualified staff intending staff with...

Страница 3: ...se cleaning 12 2 11 Decommissioning 12 3 Boiler start up Initial check 13 3 1 Hydraulic layout 13 3 2 Wiring diagram 14 3 3 Troubleshooting 14 3 4 Converting the boiler to other types of gas 14 3 5 Checks following conversion to another type of gas 15 3 6 Possible adjustments 15 3 7 Programming the p C B 15 3 8 Automatic slow ignition function with timed ramp delivery 16 3 9 Chimney sweep function...

Страница 4: ...ifically trained staff and original spare parts Do not attempt to modify or repair the appliance alone Failuretocomplywiththeaboveimpliespersonal responsibility and invalidates the warranty Installation regulations installation of these boilers in bedrooms studio flats and bathrooms or in premises where there are wood fired heaters or solid fuel heaters in general and in premises next to or connec...

Страница 5: ...anti backflow kit to be used upstream of the cold water inlet connection of the boiler It is also recommended that the heat transfer fluid e g water glycol entered in the primary circuit of the boiler heating circuit complies with the local regulations in force Important to preserve the duration of appliance efficiency features in the presence of water whose features can lead to the deposit of lim...

Страница 6: ...r at most in the adjoining room and must comply with the requirements indicated by the current technical regulations 1 9 FLUE EXHAUST CONTROL DEVICE Important it is prohibited to put the fumes exhaust control device out of order voluntarily Every piece of this device must be replaced using original spare parts if they have deteriorated In the case of repeated interventions of the fumes exhaust con...

Страница 7: ...rculator has various built in operation modes however the constant curve operation mode must be selected according to the following table Circulating pump LED Description G Y Y Y Y On On On Off Off Do not use G Y Y Y Y On On On On Off Constant curve speed 2 G Y Y Y Y On On On On On Constant curve speed 3 default G Y Y Y Y On On On Off On Constant curve speed 4 Constantcurve thecirculatoroperatesma...

Страница 8: ...ospha tedispenserreducestheformationoflime scale and preserves the original heat exchange and domestic hot production water conditions The boiler is predisposed for application of the polyphosphate dispenser kit Connection unit kit Includes pipes fittings and cocks including gas cock to carry out all connections to the boiler system The above mentioned kits are supplied complete with instructions ...

Страница 9: ...hot water probe 7 System filling valve 8 Flue safety thermostat 9 Delivery probe 10 Rapid heat exchanger 11 Safety thermostat 12 Combustion chamber 13 Ignition and detection electrodes 14 System expansion vessel 15 Burner 16 Vent valve 17 Manifold 18 System draining valve 19 By pass 20 3 bar safety valve N B connection group optional 1 15 BOILER COMPONENTS ...

Страница 10: ...n the vicinity of ducting or devices for flue extraction and relative accessories switch off the appliance and on completion of operations ensure that a qualified technician checks effi ciency of the ducting or other devices Never clean the appliance or connected parts with easily flammable substances Never leave containers or flammable substances in the same environment as the appliance It is pro...

Страница 11: ...eset button 1 04 Contacts resistance block The P C B detects a malfunction of the safety thermostat of the flue pressure switch or of the system pressure switch Press the Reset button 1 05 Flow probe anomaly The board detects an anomaly on the flow NTC probe The boiler does not start 1 06 Domestic hot water probe anomaly The board detects an anomaly on the domestic hot water NTC probe In this case...

Страница 12: ...ops contact qualified staff for assistance to eliminate possible system leakage 2 8 SYSTEM DRAINING To drain the boiler act on the special draining valve Fig 2 2 e 1 8 Before draining ensure that the filling valve is closed 2 9 ANTI FREEZE PROTECTION The boiler is supplied with an antifreeze function as per standard that activates the function of the pump and the burner when the internal system wa...

Страница 13: ...witchtheboileronandensurecorrectignition make sure the gas maximum intermediate and minimum flow rate and pressure values correspond to those given in the handbook par 3 17 checkactivationofthesafetydeviceintheevent of no gas as well as the relative activation time check activation of the main switch located upstream from the boiler check the existing draught during normal functioning of the appli...

Страница 14: ...ent interventions of the chimney safety thermostat This can be caused by obstructions in the fumes circuit Check the flue The flue may be obstructed or by height or section not suitable for the boiler Ventilation may be insufficient see room ventilation point Presence of air in the system Check opening of the special automatic vent valve Fig 1 6 Make sure the system pressure and expansion vessel p...

Страница 15: ...gas N B to adjust the gas valve remove the plastic cap 6 after adjusting refit the cap Adjustment of the boiler minimum heat output in heating phase N B only proceed after having calibrated the minimum domestic hot water pressure To adjust the minimum heat output during the heatingphase changeparameter 5 increasing the value the pressure increases reducing it the pressure drops The pressure to whi...

Страница 16: ...ndard setting P8 3 8 AUTOMATIC SLOW IGNITION FUNCTION WITH TIMED RAMP DELIVERY In the ignition phase the P C B carries out an increasing gas delivery ramp with pressure va lues that depend on the type of gas selected with preset duration This prevents every calibration or precision adjustment of the boiler ignition phase in any conditions of use 3 9 CHIMNEY SWEEP FUNCTION When activated this funct...

Страница 17: ...ot water control thermostat inter vention Check that the internal system is properly sealed according to specifications Check the intervention of the device against no gas ionization flame control Intervention time must be less than 10 seconds Visually check for water leaks or oxidation from on connections Visually check that the water safety drain valve is not blocked Check that after discharging...

Страница 18: ...18 3 4 3 2 2 4 1 INSTALLER USER MAINTENANCE TECHNICIAN ...

Страница 19: ...50 2 10 6 10 1 80 CO at 0 di O2 at Q Nom Min ppm 79 86 151 100 95 137 NOX at 0 di O2 at Q Nom Min ppm 58 12 110 15 97 12 Temperature of fumes at nominal output C 101 106 102 Temperature of fumes at minimum output C 85 85 76 METHANE G20 BUTANE G30 PROPANE G31 HEATING POWER HEATING POWER BURNER GAS FLOW RATE PRESS BURNER NOZZLES BURNER GAS FLOW RATE PRESS BURNER NOZZLES BURNER GAS FLOW RATE PRESS BU...

Страница 20: ...kW kcal h 23 6 20296 Domestic hot water adjustable temperature C 35 55 Min pressure dynamic domestic hot water circuit bar 0 3 Domestic hot water circuit max working pressure bar 10 Minimum D H W flow rate l min 2 0 Continuous flow rate T 30 C l min 11 1 Weight of full boiler kg 25 3 Weight of empty boiler kg 24 6 Electric attachment V Hz 230 50 Nominal absorption A 0 3 Installed electric power W ...

Страница 21: ...ber CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum heating capacity domestic Qn min Minimum heating capacity heating Qnw max Maximum heating capacity domestic Qn max Maximum heating capacity heating Pn min Minimum heat output Pn max Maximum heat output PMS Maximum pressure system PMW Maximum pressure domestic D Specific flow rate TM Maximum working temperature...

Страница 22: ...artial load elmin 0 014 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 003 kW Emissions of nitrogen oxides NOX 138 mg kWh For mixed central heating appliances Stated load profile XL Domestic hot water production efficiency ηWH 78 Daily electrical power consumption Qelec 0 119 kWh Daily gas consumption Qfuel 25 631 kWh Contact information IMMERGAS S p A VIA CISA LIGURE 95...

Страница 23: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C From fiche of heat pump The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is ...

Страница 24: ...he energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further factors such as heal loss in the distribution system and the dimensioning of the products in rela tion to building size and characteristics Seasonal space heating energy efficiency of package Seasonal s...

Страница 25: ... contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once inst...

Страница 26: ...ncy under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of t...

Страница 27: ...27 ...

Страница 28: ...immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038183ENG rev ST 002208 001 02 16 Inglese per IRLANDA IE ...

Отзывы: