13
ARES PRO
150
ARES PRO
230
ARES PRO
300
ARES PRO
348 - 400 -
500
ARES PRO
600
Technical features and dimensions
2.3.1 DETERMINATION OF THE PRIMARY CIRCUIT PUMP
OR BOILER PUMP
The boiler pump must have head that can ensure circulator flow rates
according to the circuit’s
∆
.
The pumps must be determined by the installer or
designer based on the data for the boiler and system.
2.3 DIAGRAM OF WATER SIDE HEAD
LOSSES
H
ea
d l
os
se
s (m/H20)
Flow rate (m3/h)
ARES PRO
150
230
300
348
400
500
600
Maximum flow rate in l/h (
∆
t=15K)
7,818
11,999
15,740
19,575
21,386
25,338
30,978
Nominal requested flow rate in l/h (
∆
t = 20K)
5,863
9,000
11,805
14,681
16,039
19,004
23,234
The pump is not an integral part of the boiler.
It is advisable to choose a pump with a flow rate and head of approx-
imately 2/3 of its typical curve.