16
Technical features and dimensions
Model/s:
ARES PRO 230
Condensing Boilers:
YES
Low temperature boiler:
NO
Boiler type B1:
NO
Co-generation appliance for central heating:
NO
Fitted with supplementary heating system:
NO
Mixed heating appliance:
NO
Element
Symbol
Value
Unit
Element
Symbol
Value
Unit
Nominal heat output
P
n
209
kW
Seasonal energy efficiency of central
heating
η
s
92
%
For central heating only and combination boilers: useful heat output
For central heating only and combination boilers: useful efficiency
At nominal heat output in high tempera-
ture mode (*)
P
4
209.3
kW
At nominal heat output in high tempera-
ture mode (*)
η
4
88.1
%
At 30% of nominal heat output in a low
temperature mode (**)
P
1
68.8
kW
At 30% of nominal heat output in a low
temperature mode (**)
η
1
96.6
%
Auxiliary electricity consumption
Other items
At full load
el
max
0.195
kW
Heat loss in standby
P
stby
0.39
kW
At partial load
el
min
0.040
kW
Annual electrical consumption
Q
HE
653
GJ
In standby mode
P
SB
0.005
kW
Emissions of nitrogen oxides ref. PCI (PCS)
NO
X
56 (51)
mg /
kWh
For mixed central heating appliances
Stated load profile
Domestic hot water production efficiency
η
WH
%
Daily electrical power consumption
Q
elec
kWh
Daily gas consumption
Q
fuel
kWh
Contact information
IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return temper-
ature.
Model/s:
ARES PRO 300
Condensing Boilers:
YES
Low temperature boiler:
NO
Boiler type B1:
NO
Co-generation appliance for central heating:
NO
Fitted with supplementary heating system:
NO
Mixed heating appliance:
NO
Element
Symbol
Value
Unit
Element
Symbol
Value
Unit
Nominal heat output
P
n
274
kW
Seasonal energy efficiency of central
heating
η
s
94
%
For central heating only and combination boilers: useful heat output
For central heating only and combination boilers: useful efficiency
At nominal heat output in high tempera-
ture mode (*)
P
4
274.5
kW
At nominal heat output in high tempera-
ture mode (*)
η
4
88.3
%
At 30% of nominal heat output in a low
temperature mode (**)
P
1
91.5
kW
At 30% of nominal heat output in a low
temperature mode (**)
η
1
98.1
%
Auxiliary electricity consumption
Other items
At full load
el
max
0.210
kW
Heat loss in standby
P
stby
0.34
kW
At partial load
el
min
0.032
kW
Annual electrical consumption
Q
HE
844
GJ
In standby mode
P
SB
0.005
kW
Emissions of nitrogen oxides ref. PCI (PCS)
NO
X
59 (53)
mg /
kWh
For mixed central heating appliances
Stated load profile
Domestic hot water production efficiency
η
WH
%
Daily electrical power consumption
Q
elec
kWh
Daily gas consumption
Q
fuel
kWh
Contact information
IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return temper-
ature.
STD.005480/001