It is just as important that the intake grids and exhaust
terminals are not obstructed.
It is recommended to check that no flue gas recircula-
tion is found in the air sample points (0.5% maximum
permitted CO
2
).
Keep all flammable objects away from the appliance (paper,
rags, plastic, polystyrene, etc.).
The minimum distance for exhaust pipes from flammable
materials must be at least 25 cm.
Do not place household appliances underneath the boiler as
they could be damaged if the safety valve intervenes, if the
drain trap is blocked, or if there are leaks from the hydraulic
connections; otherwise, the manufacturer cannot be held re-
sponsible for any damage caused to the household appliances.
For the aforementioned reasons, we recommend not placing
furnishings, furniture, etc. under the boiler.
In the event of malfunctions, faults or incorrect operation, turn
the appliance off immediately and contact an authorised com-
pany (e.g. the Authorised Technical Assistance centre, which
has specifically trained staff and original spare parts). Do not
attempt to modify or repair the appliance alone.
Any modification to the appliance that is not explicitly indicated
in this section of the booklet is forbidden.
Installation Standards:
- this boiler can be installed outdoors
in a partially protected area. A par-
tially protected area is one in which the
boiler is not exposed to the direct ac-
tion of the weather (rain, snow, hail, etc.).
This type of installation is only possible when
permitted by the laws in force in the appli-
ance's country of destination.
- Installation of gas appliances, flue ex-
haust pipes and combustion air intake
pipes is forbidden in places with a fire
risk (for example: garages, closed parking
stalls), and in potentially dangerous places.
- Installation on the vertical projection of
cooking hobs is forbidden.
- Installation is forbidden in the places / rooms
that constitute public areas of apartment
buildings, such as internal stairways or other
escape routes (e.g. floor landings, entrance
halls, etc.).
- Installation is also forbidden in places/rooms
that constitute public areas of apartment
buildings such as cellars, entrance halls, at-
tics, lofts, etc., unless otherwise provided for
by local regulations in force.
- These boilers are not suitable for installation
on walls made of combustible material.
N.B.: wall mounting of the boiler must guarantee
stable and efficient support for the boiler.
The
plugs (standard supply) are only to be used to fix
the boiler to the wall; they only ensure adequate
support if inserted correctly (according to technical
standards) in walls made of solid or semi-hollow
brick or block. In the case of walls made of hollow bricks or
blocks, partitions with limited static properties, or in any case
walls other than those indicated, a static test must be carried
out on the mounting system.
These boilers are used to heat water to below boiling
temperature in atmospheric pressure.
They must be connected to a central heating system
and domestic hot water circuit suited to their perfor-
mance and capacity.