Id
Param-
eter
Parameter
Description
Range
Default
Custom-
ised value
P0
Max DHW
output
Defines the maximum heat output percentage of the boiler during the
D.H.W. phase compared to the maximum heat output available
0 - 100 %
100 %
P1
Min CH output Defines in percentage the minimum output in central heating mode
0 - P2
0 %
P2
Max CH output Defines the maximum heat output percentage of the boiler during the central
heating mode compared to the maximum heat output available
0 - 100 %
G20 = 85
G31 = 83
G230 = 82
P3
Relay
configurable
Relay setting:
0 = Off
1÷ 9 = Not used
10 = Aqua Celeris device PTC resistance management
0 - 10
10
P4
Pump func-
tioning
The pump can function in two ways.
0 intermittent: in winter "mode" the circulator is managed by the room
thermostat or by the remote control
1 continuous: in "winter" mode the circulator is always powered and is
therefore always in operation
0 - 1
0
P5
External probe
correction
If the reading of the external probe is not correct it is possible to correct it
in order to compensate any environmental factors.
-9 - 9 K
0
P6
-
Not available for this model
-
-
P7
-
Not available for this model
-
-
Id
Param-
eter
Parameter
Description
Range
Default
Custom-
ised value
t0
Central heating
set point min-
imum temper-
ature
Defines the minimum flow temperature.
20 - 50 °C
25
t1
Central heating
set point max-
imum temper-
ature
Defines the maximum flow temperature.
(t0+5) - 85 °C
85
t2
Solar delay
timing
The boiler is set to switch-on immediately after a request for DHW. In the
case of coupling with a solar storage tank positioned upstream from the
boiler, it is possible to compensate the distance between the storage tank and
the boiler in order to allow the water to reach the boiler. Set the time neces-
sary to verify that the water is hot enough (see par. Solar panels coupling)
0 - 30 seconds
0
t3
Domestic hot
water priority
timing
In winter mode the boiler, at the end of a domestic hot water request, is
ready to switch to central heating mode if there is an active request. Timing
sets a time period in which the boiler waits before changing the operating
mode, in order to quickly and comfortably satisfy an additional request for
domestic hot water.
0 - 100 sec-
onds
(step 10 sec)
2
t4
Central heating
ignitions timer
The boiler has an electronic timer, which prevents the burner from ignit-
ing too often in central heating mode
0 - 600 sec-
onds
(step 10 sec)
18
t5
Central heating
ramp timer
In central heating mode, the boiler performs an ignition ramp in order to
reach the maximum output set
0 - 840
seconds
(step 10 sec)
18
t6
CH ignition
delay from TA
and CR request
The boiler is set to switch-on immediately after a request. In the event of
particular systems (e.g. area systems with motorised thermostatic valves
etc.) it may be necessary to delay ignition
0 - 600 sec-
onds
(step 10 sec)
0