-7-
HYDRAULIC RESISTANCES
CHILLED WATER
LPHW
OPTIONAL ELECTRIC HEATING (kW)
CWR
240V 50Hz
230V 50Hz
25
0.9
0.84
45
1.75
1.63
65
2.6
2.43
85
3.5
3.27
SOUND LEVELS CWR UNITS
Sound Pressure Levels
Sound Power Levels
MODEL
Speed
dBA
NC
63Hz
125Hz
250Hz
500Hz
1kHz
2kHz
4kHz
8kHz
25
Min
27
22
38
45
50
48
46
41
32
29
Med
34
28
40
49
55
52
52
48
41
32
Max
40
35
47
55
59
57
58
55
49
42
45
Min
32
25
40
48
52
52
48
44
35
28
Med
35
29
42
51
54
55
52
49
41
31
Max
42
37
48
58
60
59
60
56
51
42
65
Min
31
25
40
47
51
53
46
41
32
29
Med
37
30
43
54
56
57
53
50
42
34
Max
46
42
53
62
65
63
64
61
56
49
85
Min
33
27
42
53
53
54
48
44
33
28
Med
41
35
48
59
60
60
58
55
48
39
Max
46
43
52
61
63
63
65
61
54
47
Sound Pressure Levels (SPL) at 3m distance, 1m below units running in
free field conditions, (dB re: 2x10
-5
N/m
2
).
Sound Power Levels (SWL) in dB re: 1pW.
COIL WATER VOLUMES (LITRES)
Model
25
45
65
85
Chilled Water Coil
0.642
1.103
1.565
2.026
LPHW Coil
0.345
0.510
0.675
0.840
Heronhill - for all your Airking requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807