CONDENSATE PUMP KIT 53900410
This kit is for use on 539 series IMPULSE and 968 series CWR units for the removal of condensate where gravity drain is
not practicable or desirable.
The pump is capable of overcoming a resistance equivalent to 5 metres lift.
The sensor is arranged so that residual condensate in the sump is kept to a minimum.
The kit includes an overflow protection circuit, which will prevent further cooling and condensate production if a high
condensate level occurs.
ITEM
QTY
DESCRIPTION
ITEM
QTY
DESCRIPTION
1
PUMP ASSEMBLY CONSISTING OF:
4
1
Grommet
A
1
Pump
5
1
Wire
Support
B
1
Grommet
6
4
No. 8 Screw
C
1
Hose
7
1
Cable Tie
D
1
Green/Yellow Cable
8
2
No. 6 Screw
E
1
Cable Tie
9
1
Sensor Block
2
1
Control Board
10
1
Sensor Bracket
3
4
Mounting Foot
It is preferable to fit this kit prior to installing the unit; the following instructions/diagrams refer to bench
fitting.
ISOLATE THE SYSTEM ELECTRICALLY PRIOR TO INSTALLATION OF THIS KIT
1
Remove both side panels (2 screws each side behind the plastic caps):-
WARNING:
IF THE UNIT IS ALREADY INSTALLED IN THE CEILING, THE SIDE PANELS WILL DROP
IMMEDIATELY UPON RELEASING THE SCREWS.
2
Open the grille by pulling the handles at the top edge of the grille (Fig. 1); the grille is spring loaded and some
resistance will be felt.
3
Lift the filter over the retaining lug and slide it out (Fig. 2).
Fig. 1.
Fig. 2.
Fig. 3.
4
Insert a screwdriver between the grilles and disengage the grille retaining catches
(Fig. 3). Swing the grille away and unhook from the chassis.
5
Remove and retain all the fascia support bracket fixing screws (Fig. 4)
and remove the bracket and fascia from the unit. Store the fascia in a safe
location until required.
Fig. 4.
6
The condensate drain connector is already fitted to
the pipework end of the unit, (Fig. 5).
Fig. 5.